22
7 Technical data
7
Technical data
7.1
Control ranges and temperature probes
7.2
Capillary and temperature probe
Type
Control/limit
value ranges
max. admissible
excessive probe
temperature
Length of the temperature probe
in mm
Copper (Cu)
Stainless steel (CrNi)
°C
°C
Ø 6
Ø 8
Ø 6
Ø 8
ATH.-SE-2
0 to 100
125
107
75
99
67
20 to 90
125
138
91
130
83
30 to 110
135
125
84
117
76
20 to 120
140
107
75
99
67
60 to 140
165
123
83
117
76
20 to 150
175
88
65
80
57
50 to 200
230
101
72
93
64
50 to 250
290
-
-
73
54
50 to 300
345
-
-
63
49
ATH.-SE-20
30 to 110
135
112
78
104
70
ATH.-SE-70
60 to 140
165
110
77
102
68
20 to 150
175
80
61
72
53
50 to 250
290
-
-
66
50
50 to 300
345
-
-
58
-
Type
Scale limit value
Capillary
Temperature probe
ATH.-SE-2
≤ 200 °C
Copper (Cu)
Copper (Cu)
ATH.-SE-20
Ø 1.5 mm
Material no. 2.0090
ATH.-SE-70
Material no. 2.0090
hard soldered
> 200 °C
Copper (Cu)
Stainless steel (CrNi)
Ø 1.5 mm
Material no. 1.4571
Material no. 2.0090
hard soldered
all areas
Stainless steel (CrNi)
Stainless steel (CrNi)
Ø 1.5 mm
Material no. 1.4571
welded
Capillary length
1000 mm, max. 2000 mm as standard
Min. bending radius of the capillary 5 mm