4 Electrical connection
4
Electrical connection
4.1
Installation notes
4.2
Connection diagram
Type 71 with fixed cable, 6 × 0.14 mm, shielded
Type 70 with M12 connector, 8-pole, A-coded
•
Route input, output, and supply lines separately and not parallel to one another
•
To connect the conductivity sensor, use the CR 4P-cable (see "Accessories") if possible; do not run
the connecting cable close to current-carrying components or cables
•
Implement the cables continuously (not via terminal blocks or similar)
•
Do not connect any additional loads to the supply terminals of the sensor
•
Follow the instructions regarding the electrical connection in the operating manual for the transmitter
used
•
Make sure that you always use safety devices that are independent of the device, and ensure that
only qualified personnel configure the settings. In addition to incorrect installation, incorrectly set val-
ues on the transmitter can impair the performance of the downstream process or cause damage
Figure
Wire color
Function
Green
Pt1000
Yellow
Pt1000
Gray
Inner electrode 2
Brown
Outer electrode 2
White
Outer electrode 1
Pink
Inner electrode 1
Figure
PIN
Function
1
Pt100/Pt1000
2
Pt100/Pt1000
3
Inner electrode 2
4
Outer electrode 2
5
Pt100/Pt1000 three-wire circuit
6
Outer electrode 1
7
Inner electrode 1
8
Not used