10 Operation
40
10.6.4 TEMPERATURE OUT
SIGNAL TYPE
0 — 20 mA
4 — 20 mA
20 — 0 mA
20 — 4 mA
0 — 10 V
2 — 10 V
10 — 0 V
10 — 2 V
SCALING START
-20.0 to 0.0°C = 4 mA (depending on the signal type)
SCALING END
+200 to 150.0°C = 20 mA (depending on the signal type)
DURING ALARM
LOW
(0 mA / 0 V / 3.4 mA / 1.4 V)
HIGH
(22 mA / 10.7 V)
SAFE VALUE (depending on the signal type)
DURING CALIBRATION
MOVING
FROZEN
SAFE VALUE
SAFE VALUE
0.0 — 4.0 — 22.0 mA (depending on the signal type)
0 — 10.7 V
MANUAL MODE
OFF
ON
MAN. VALUE
0.0 — 4.0 — 22.0 mA (depending on the signal type)
0 — 10.7 V