JUDO PROFI

3

Installation Example

flushed out as optimally as when installed
horizontally.

Tension-free installation has to be ob-
served!

Installation Example

The installation of the Backwash Protective
Filter is effectuated up to a water pressure
of 10 bar behind the water meter, and the
backflow preventer before a possibly mount-
ed  pressure  reducer (see Fig. 3).

In the event of 

water pressure above 10

bar

, the pressure reduction valve should be

fitted 

in front 

of the Backwash Protective

Filter (see Fig. 3). If the operating pressure is
above 10 bar, this may result in defects during
operation.   

For the backwashing water a wastewater
connection [for example a floor drainage] in
accordance with DIN 1986 must be in place.
If a wastewater connection directly under

the filter is not possible, the rinse water can
be led by means of a line to be mounted on
the rinse water valve [same dimension as
the rinse water valve] a few meters away to
the next wastewater connection. When piv-

Fig. 2: Application

> 100 mm

> 200 mm

> 40 mm

We recommend  the installation of
a pressure reducer at a 

water pres-

sure  between 5 bar and 10 bar

.

Fig. 3: Pressure reducer upstream of the unit. Ex-
ample JPF DN65

1

1 = Pressure reducer

Summary of Contents for PROFI JPF DN125

Page 1: ...and putting the unit into service These must always be issued to the owner user Prolongated guarantee period if a maintenance contract has been concluded Installation and Operating Instructions JUDO P...

Page 2: ...r pipes usual in the trade in each flow direc tion To ensure easy operation and maintenance the indicated minimum distances have to be observed The installation into vertical lines should be effected...

Page 3: ...see Fig 3 If the operating pressure is above 10 bar this may result in defects during operation For the backwashing water a wastewater connection for example a floor drainage in accordance with DIN 19...

Page 4: ...ve Doing this it is prevented that the sieve cloth is damaged by a too strong pressuring of the suction tube At the same time the rinse wa ter consumption is reduced With a flush valve opened to one h...

Page 5: ...2 100 and DIN EN 1334 1 The maximum operat ing pressure is lower in order to ensure the optimum function of the filter Installed dimensions Model Pipe con nection Order No JPF DN125 DN125 8010035 JPF...

Page 6: ...6 JUDO PROFI Spare Parts JPF DN125 DN200 Spare Parts JPF DN125 DN200 JPF DN125 two filterunits JPF DN150 three filterunits JPF DN125 four filterunits...

Page 7: ...14 Plate Screw 4 2x9 5 1 1650125 1 15 Mouthpiece Nozzle 4 1120135 11 16 Suction Pipe complete 1 2010029 320 17 Filter Screen MW 0 10 mm silver plated 1 2010028 350 18 O ring 12x3 2 1607110 2 19 Water...

Page 8: ...5 6 92 0 Fax 49 0 71 95 6 92 188 e mail info judo eu www judo eu JUDO Wasseraufbereitung GmbH Niederlassung sterreich Zur Schleuse 5 A 2000 Stockerau Tel 43 0 22 66 6 40 78 Fax 43 0 22 66 6 40 79 e ma...

Reviews: