Technical data
7
Technical data
Backwash protective filter
JUDO PROFI-QC DN 125 - 200
JPF-QC DN 125 - 200
The water to be filtered must comply with the European Drinking Water Directive.
Information about:
JPF-QC DN 125 JPF-QC DN 150 JPF-QC DN 200
Pipe connection
DN 125
DN 150
DN 200
Backwashing volume flow
1)
0,5 - 1,5 L/s
0,5 - 1,5 L/s
0,5 - 1,5 L/s
Nominal pressure
PN 10
PN 10
PN 10
Operating pressure
1,5 - 10 bar
1,5 - 10 bar
1,5 - 10 bar
Rated flow after backwashing with
0,2 (0,5) bar Druckverlust
100 m³/h
150 m³/h
200 m³/h
Mesh size
2)
sieve insert
100 μm
0.1 mm
100 μm
0.1 mm
100 μm
0.1 mm
Water temperature and ambient
temperature
max. 30 °C
max. 30 °C
max. 30 °C
Threaded connection according to
DIN EN 10226-1
Weight
80 kg
122 kg
188 kg
Order no.
8290025
8290026
8290027
1) Applies to a fully opened backwashing valve and 2 - 3 bar mains pressure.
2) Standard sieve mesh size
Available special sieve mesh sizes (30 μm / 0.03 mm, 320 μm / 0.32 mm and 500 μm
/ 0.5 mm) for the industrial use are not part of the testing acc. to DIN EN 13443-1 and
DIN 19628 and therefore can not bear the DIN-DVGW mark.
1701803 • 2019/11
JUDO JPF-QC
15