![JS Automation EMC8485 User Manual Download Page 13](http://html1.mh-extra.com/html/js-automation/emc8485/emc8485_user-manual_2028613013.webp)
12
7.
System Reset
The system reset switch SW2 has provide normal system reset and reset to default functions.
7.1
Normal system reset
Push the SW2 for more than 5 seconds, the power LED will flick at 3 Hz to signal the system has
already reset. Once you release the switch, the LED will return to normal flick rate.
7.2
Reset to default
Push the switch while power on (We suggest to push the switch first then power on and wait for 3
seconds) for 3 seconds, the LED will:
1.
stop flick
2.
flicking at 3 Hz--- system now setting default data
3.
flicking at normal speed --- system now already reset, you can release the switch.
item
default value
IP
192.168.0.100
password
12345678
socket port
6936
MAC
0x02 12 34
xx xx xx
default gateway
192.168.0.1
mask
255.255.255.0
IO_config
ALL input (0xFF)
polarity
ALL inactive (0x0)
WDT timer
1second(0xA)
WDT output state
ALL inactive (0x0)
Standalone function
ALL clean (0x0)
Power on standalone
Disable (0x0)
xx xx xx
is serial number (Hex)