12. Digital Output Function
【Note】Version:if function version >= version,the function can be used。
Example:CA23
C=2012 year / A=10 month /23 day
12.1 STD Mode - DOx(Digital Output Function)
Function
Function Description
Version Chapter
0
Always OFF
1
Always ON
2
SERVO-READY
3
OL Warning
4
ALARM
5
NO ALARM
8
PG-C(10ms INDEX Output)
Function
Function Description【Speed Mode】
Version Chapter
6
Forward Running ( ABS(Rpm) > Pr.184(SPZrpm) )
14.1
7
Reverse Running ( ABS(Rpm) > Pr.184(SPZrpm) )
9
SPZ:ABS(Rpm) <= Pr.184
10
NSPZ:ABS(Rpm) > Pr.184
14
Actual-Speed > Pr.010: Speed-Reference
15
Actual-Speed <= Pr.010:Speed-Reference
Function
Function Description【Torque Mode】
Version Chapter
18
Driver Torque-Current(%) > Pr.016:Warning Level
14.2
19
Driver Torque-Current(%) <= Pr.016:Warning Level
83
Motor-Torque(%) > Pr.016:Warning Level
84
Motor-Torque(%) <= Pr.016:Warning Level
Function
Function Description【32 BIT COUNTER Block】
Version Chapter
112
32 bit Counter >= Pr.216:Compare Level
13.1
113
32 bit Counter < Pr.216:Compare Level