background image

19

Derating Procedure:

To derate this unit, install the appropriate orifice as

shown in the High Altitude chart.

1. Remove the two ¼” hex head screw that holds

the burner tube/log support to the bottom of the
stove.

2. Remove the burner tube/log support to expose

the main burner orifice.

3. Remove the air deflector shield around the main

burner orifice.

4. Remove the orifice and replace with the appropri-

ate one from the high altitude kit.

5. Be sure to attach the high altitude conversion

sticker provided with the kit to the rating plate on
the appliance.

A self-adhesive Conversion Label ( Fig. 21) is

included with the High Altitude Kit. Apply this label
to the control valve after it has been converted for
high altitude.

E

P

Y

T

S

A

G

E

C

I

F

I

R

O

E

Z

I

S

N

O

I

T

A

V

E

L

E

T

R

A

P

R

E

B

M

U

N

L

A

R

U

T

A

N

S

A

G

8

4

#

'

0

0

0

2

-

0

)

m

0

1

6

-

0

(

7

0

4

9

2

1

L

A

R

U

T

A

N

S

A

G

9

4

#

'

0

0

5

4

-

1

0

0

2

)

m

0

7

3

1

-

1

1

6

(

1

1

4

9

2

1

E

N

A

P

O

R

P

S

A

G

4

6

/

3

'

0

0

0

2

-

0

)

m

0

1

6

-

0

(

9

0

4

9

2

1

E

N

A

P

O

R

P

S

A

G

6

5

#

'

0

0

5

4

-

0

0

0

2

)

m

0

7

3

1

-

1

1

6

(

3

7

3

4

5

1

Table 3.  High Altitude Orifice Chart.

Figure 21.  High Altitude Conversion Label.

High Altitude Adjustment

When installing the Lillehammer in high altitude
(above 2500 ft.) locations, it becomes necessary to
compensate for the thinner air (less volume of oxygen
per cubic foot). High altitudes affect the atmospheric
pressure and heat value of gaseous fuels. The lower
oxygen content in the air and the lower gas viscosity
require the use of a different orifice to achieve
efficient, clean combustion at the burner tube.

U.S. Requirements

THE DERATING KIT MUST BE INSTALLED BY AN

AUTHORIZED SERVICE TECHNICIAN IN ACCORDANCE
WITH THE MANUFACTURER’S INSTRUCTIONS AND ALL
CODES AND REQUIREMENTS OF THE AUTHORITY
HAVING JURISDICTION.  THE INFORMATION STICKER
MUST BE FILLED OUT BY THE INSTALLER AND AD-
HERED TO THE APPLIANCE AT THE TIME OF THE
CONVERSION. THE QUALIFIED SERVICE AGENCY
PERFORMING THIS WORK ASSUMES RESPONSIBILITY
FOR THIS DERATING.

Canadian Requirements

This unit has been tested for installation at high
altitudes in accordance with Canadian test standard
CAN/CGA-2.17.

THE DERATING SHALL BE CARRIED OUT IN ACCOR-

DANCE WITH THE REQUIREMENTS OF THE PROVIN-
CIAL AUTHORITIES HAVING JURISDICTION AND IN
ACCORDANCE WITH THE REQUIREMENTS OF THE
CAN1-B-149.1 AND .2 INSTALLATION CODE.

For installations from 610 - 1370 meters (2000-

4500 ft.) the orifice size for natural gas is #49

 

and for

propane gas #56. SEE THE HIGH ALTITUDE ORIFICE
CHART

See the Rating Plate for additional information.

For high altitude installations, consult the local gas
distributor or the authority having jurisdiction for
proper rating methods.  If the installer must convert
the unit to adjust for varying altitudes, the informa-
tion sticker must be filled out by the installer and
adhered to the appliance at the time of the conver-
sion.

THIS STOVE HAS BEEN CONVERTED FOR USE
AT AN ALTITUDE OF ____________________
Orifice Size _______  Manifold Press: ______
Input BTU/Hr. _____   Fuel Type  __________
Date of Conversion  ____________________

Summary of Contents for GF 200 DV

Page 1: ...ENT AVERTISSEMENT ASSUREZ VOUS DE BIEN SUIVRE LES IN STRUCTIONS DANS CETTE NOTICE POUR REDUIRE AU MINIMUM LE RISQUE D INCENDIE OU POUR EVITER TOUT DOMMAGE MATERIEL TOUTE BLESSURE OU MORTALIT E NE PAS...

Page 2: ...ances for over 140 years We ve been making fine quality cast iron wood and coal stoves and fireplaces continuously since 1853 In the Lillehammer we ve combined advanced gas technology with the warm tr...

Page 3: ...Fredrikstad Norway J tul North America Portland Maine Test Standards This appliance complies with National Safety standards and is tested and listed by Intertek Testing Services of Middleton Wisconsin...

Page 4: ...0 WC 1 74 kPa Propane 11 0 WC 2 73 kPa 13 5 WC 3 36 kPa Manifold Pressure MIN MAX Natural Gas 2 2 WC 54 kPa 3 5 WC 87 kPa Propane 6 5 WC 1 61 kPa 10 0 WC 2 49 kPa Efficiency 82 Steady State A F U E 73...

Page 5: ...our area for a safe and legal installation Some areas require a permit to install a gas burning appliance Always consult your local building inspector or authority having jurisdiction to determine wha...

Page 6: ...ace temperatures and should stay away to avoid burns or clothing ignition Young children should be supervised while they are in the same room as the Lillehammer gas stove Clothing or other flammable m...

Page 7: ...ation Mantel and Trim Clearances Alcove Installation Maximum Depth 24 610mm Minimum Width 35 890mm Minimum Ceiling Height 42 1067mm Figure 5 Clearance to rear corners Figure 3 Mantel Trim Clearances 2...

Page 8: ...IN THE SAME SYSTEM Simpson Dura Vent GS Amerivent Corporation Security Vent Ltd Installation of any components not manufac tured or approved by J tul or failure to meet all clearance requirements will...

Page 9: ...Whenever possible use 45 elbows instead of 90 elbows as they are less restrictive to exhaust gas and intake air flow n GAS VENT RULE In no case shall any discharge opening on the cap be less than 2 61...

Page 10: ...MNEY FLUE FROM THE ROOM Consult with the local code authority having jurisdiction before proceeding with this type of installation Refer to the vent manufacturer s instructions for specific installati...

Page 11: ...AND IN THE INSTRUCTIONS PROVIDED WITH EACH SIMPSON DURA VENT COMPONENT Figure 10 Vent System through a masonry chimney using the Simpson Dura Vent Chimney Conversion Kit 934 May also be used in liste...

Page 12: ...or wall Simpson Dura Vent 950 The Standoff prevents exposure of the vinyl siding to excessive heat that can damage the siding material A 10 X 10 250 mm x 250 mm square hole is required to maintain pro...

Page 13: ...hroud Wall Shield Figure 14 Install the Wall Shield 18 Max 460 mm Simpson Dura Vent Horizontal Termination Cap 984 or 985 6 150 mm Simpson Dura Vent 908B Two 90 Degree Elbows OPTION 5 Figure 12 5 Hori...

Page 14: ...cm min J tul N A strongly recommends 12 inches 30 cm particularlywhere windy conditions are prevalent H Not to be installed above a meter regulator assembly within 3 feet 90 cm horizontally from the c...

Page 15: ...ITH THE TYPE OF GAS THAT IS INDICATED ON THE STOVE S RATING PLATE A GAS CONVERSION KIT IS PRO VIDED WITH THE LILLEHAMMER DIRECT VENT GAS STOVE THIS APPLIANCE MAY BE INSTALLED IN AN AFTERMARKET PERMANE...

Page 16: ...e shield to the rear wall of the firebox Slide the shield left and remove 9 Change the Main Burner Orifice 38 Use a openendwrench toremove theburner orificeand replace with the appropriate orifice sup...

Page 17: ...ropriate tools and sealing compounds For propane units be sure to use compounds that are propane resistant Turn on gas supply and test for gas leaks using a soapy water solution ALWAYS REFER TO THE LI...

Page 18: ...e Testing the available gas pressure should be done by attaching a manometer to the appropriate test point on the valve The gauge connections are located on the front of the valve under the On Off Pil...

Page 19: ...air and the lower gas viscosity require the use of a different orifice to achieve efficient clean combustion at the burner tube U S Requirements THE DERATING KIT MUST BE INSTALLED BY AN AUTHORIZED SE...

Page 20: ...ral Gas 3 4 open for Propane The air shutter can also help achieve the desired flame appearance Generally flame appearance is a matter of preference however most consumers enjoy the warm yellowish fla...

Page 21: ...that may affect the accuracy of the thermostat The thermostat should be connected to the Lillehammer using a minimum of 16 gauge wire with a maximum length of 35 feet of wire Connect the two thermost...

Page 22: ...is equipped with an On Off T stat rocker switch or can be controlled using an optional wall mounted thermostat 3 When lit for the first time the Lillehammer will emit an odor for several hours This od...

Page 23: ...impor tant to prevent combustion gases from escaping into the room Replace the gasket if necessary refer to the replacement parts list on page 25 Always replace any damaged or broken parts with J TUL...

Page 24: ...s _______________________________ _________________________________ Phone _________________________________ Type of Fuel Natural Gas ____ Propane _____ Fuel Conversion YES _______ NO ________ Installe...

Page 25: ...25 3 21 Illustrated Parts List GF 200 DV Lillehammer 39 40 Figure 29 12A 20 2 24 23 22 19 4 12 11 10 13 36 C A B 37 38 D 41 43 42 1 35 5 34 15 17 18 16 14 27 26 20 2 33 28 25 29 30 31 32...

Page 26: ...8 129129 43 Main Gas Line flexible 129462 Exhaust Restrictor 129344 Air Intake Restrictor 129347 Spud Plate Assembly 154336 Firebox Assembly Part No Firebox Assembly Part No To order replacement part...

Page 27: ...nnot be turnedfrom PILOT to OFF unless the knob is pushed in slightly Do not force 6 Wait five 5 minutes to clear out any gas If you then smell gas STOP Follow B in the safety information above on thi...

Page 28: ...s important that all instructions issued with the unit are carefully read and strictly followed J tul pursues a policy of continual product develop ment Products supplied may therefore differ in speci...

Reviews: