background image

9

Vertical Vent Termination

The Jøtul GF 300 DV can be vertically vented through a
ceiling or to a roof termination with the following
guidelines:

„

The termination should fall within the shaded areas
of the grids depicted in the Vent Window diagrams on
pages 10 - 11.

„

Maximum Vertical 

run should not exceed 

35 ft.

 (10.66 m).

„

Minimum Vertical

 run must be at least 

8 ft.

 (2.43 m).

„

Max. Colinear Horizontal run is 2 ft.

 (61 cm).

„

Vent Terminus Clearance: 

In no case shall any dis-

charge opening on the cap be less than 18 in. (610
mm) horizontally from the roof surface.

„

Steep roofs, nearby trees, and predominantly windy
conditions can contribute to poor draft and/or
promote down-draft occurances. Increasing the
height of the vent may alleviate these conditions.

„

Use Wall Straps to support an offset pipe run at three
feet intervals to avoid excessive stress on the offsets.

„

Elbows:

 Four 45°, or two 90° elbows may be used. Do

not include the 45° elbow attached to the stove.
Whenever possible use 45° elbows instead of 90°
elbows as they are less restrictive to exhaust gas and
intake air flow.

„

A firestop is required at every floor.  The opening
should be framed to 10" X 10" inside dimension.

„

Any venting that is exposed above the first floor,
regardless of attic space or living space, must be
enclosed. Always maintain the required 1" clearance
from all sides of the vertical vent system.

Figure 7. Use a nut driver to change the Exhaust
Restrictor setting.

Figure 6.  Exhaust restrictor positions - viewed from front
with top plate removed.

Figure 8. Vertical vent termination height above roof.

A

C

D

B

See Fig. 6

Detail

Horizontal Overhang

Vertical W

all

Termination

Cap

18”.

min.

Lowest Discharge

Opening

18” min.

18”.

min.

Summary of Contents for Allagash GF 300 DV

Page 1: ...IRE DEPARTMENT AVERTISSEMENT ASSUREZ VOUS DE BIEN SUIVRE LES IN STRUCTIONS DANS CETTE NOTICE POUR REDUIRE AU MINIMUM LE RISQUE D INCENDIE OU POUR EVITER TOUT DOMMAGE MATERIEL TOUTE BLESSURE OU MORTALIT E NE PAS ENTREPOSER NI UTILISER D ESSENCE NI OU LIQUIDES INFLAMMABLES DANS LE VOISINAGE DE CET APPAREIL OU DE TOUT AUTRE APPAREIL L INSTALLATION LE SERVICE DOIVENT ETRE EXECUTES PAR UN INSTALLATEUR ...

Page 2: ...ood and coal stoves and fireplaces continuously since 1853 The GF 300 DV Allagash combines advanced gas technology with the warm traditional elements of cast iron With proper care and use your Jøtul stove will provide you with many years of safe dependable and satisfying service The Jøtul GF 300 DV Allagash is a direct vented gas heater designed and approved for installation into a variety of conf...

Page 3: ...red and Distributed by Jøtul A S A Fredrikstad Norway Jøtul North America Portland Maine Test Standards This appliance complies with National Safety standards and is tested and listed by Intertek Testing Services of Middleton Wisconsin to ANSI Z21 88 2002 CSA 2 33 M02 and CAN CGA 2 17 M91 CSA P 4 01 2 for Canada DO NOT ATTEMPT TO ALTER OR MODIFY THE CONSTRUCTION OF THE APPLIANCE OR ITS COM PONENTS...

Page 4: ...nitor Standing Pilot C L 25 635 mm 28 711 mm 3 1 4 83 mm 28 1 2 724 mm 13 330 mm 15 1 4 500 mm 27 1 2 698 mm 22 1 4 565 mm 22 1 2 572 mm C L Suggested Tools for Installation and Service External regulator for Propane only Piping which complies with local code Manual shutoff valve T Handle in Massachusetts Sediment trap if required by code Tee joint Pipe wrench Pipe sealant 10 mm open end wrench 1 ...

Page 5: ...e U S these require ments are established in the National Fuel Code ANSI Z223 1 NFPA 54 current edition In Canada the codes have been established in CAN CGA B149 Fuel Installation Code current edition Installer l appareil selon les codes ou reglements locaux ou en l absence de tels reglements selon les Codes d installation CAN CGA B149 DO NOT OPERATE THIS STOVE IF ANY PART HAS BEEN UNDER WATER Cal...

Page 6: ...on any combustible material OTHER THAN WOOD a floor pad must be installed that is either metal or wood or a listed hearth pad This floor protection must extend the full width and depth of the appliance It is not necessary to remove carpeting vinyl or linoleum from underneath the floor protection See fig 1 Safety Information During normal operation the GF 300 DV gas stove will reach high surface te...

Page 7: ...ort Legs 2 51 mm To Rear Wall 52 1 2 1334 mm 55 1 2 1410 mm 12 5 10 25 8 5 75 3 5 18 1 2 419 mm Max Mantel Depth Min Mantel Depth Minimum Ceiling or Alcove Height 61 1550 mm 54 1372 mm 58 1 2 1486 mm 57 1449 mm 28 711 mm Max Top Trim Depth 1 46 1 2 1182 mm Stove and Vent Clearance Requirements Minimum Clearances from the Stove to Combustibles See figs 2 4 Rear 2 51 mm Ceiling 33 838 mm Corner 2 51...

Page 8: ...rtical or horizontal termination and must conform to the configuration requirements described below This appliance is approved for use with vent systems from the following manufacturers Simpson Dura Vent GS Amerivent Corporation Security Vent Ltd Selkirk Metalbestos Use parts of one manufacturer only DO NOT MIX VENT COMPONENTS FROM DIFFERENT MANUFACTURERS IN THE SAME SYSTEM Installation of any com...

Page 9: ...s Use Wall Straps to support an offset pipe run at three feet intervals to avoid excessive stress on the offsets Elbows Four 45 or two 90 elbows may be used Do not include the 45 elbow attached to the stove Whenever possible use 45 elbows instead of 90 elbows as they are less restrictive to exhaust gas and intake air flow A firestop is required at every floor The opening should be framed to 10 X 1...

Page 10: ...ALWAYS MAINTAIN THE PROPER CLEARANCES TO COMBUSTIBLES The circled letter designations in the vent diagram correspond to the Exhaust Restrictor Setting on the stove First determine which vent termination zone is appropriate for your installation and fuel type then adjust the restrictor to the corresponding position as shown in figure 7 page 9 Vent Windows for Natural Gas COLINEAR VENT COAXIAL VENT ...

Page 11: ... to position C for a vertical colinear termination Max Offset 2 ft 610 mm VENTING MUST TERMINATE END WITHIN ONE OF THE DESIGNATED AREAS SET STOVE EXHAUST RESTRICTOR TO THE POSITION THAT CORRESPONDS TO THE VENT TERMINATION AREA IN THE DIAGRAM ABOVE ALWAYS MAINTAIN THE PROPER CLEARANCES TO COMBUSTIBLES The circled letter designations in the vent diagram correspond to the Exhaust Restrictor Setting o...

Page 12: ...mney and connect to both the unit and the termination cap A METAL BLOCK OFF PLATE MUST BE CONSTRUCTED AND INSTALLED ABOVE THE UNIT PRIOR TO THE END OF THE INTAKE FLEX AND MUST COMPLETELY SEAL THE CHIMNEY FLUE FROM THE ROOM Consult with the local code authority having juris diction before proceeding with this type of installation Refer to the vent manufacturer s instructions for specific installati...

Page 13: ... mm Prefabricated chimneys must be listed for the specific Simpson Dura Vent Chimney Conversion Kit USE KIT 931 932 or 933 Figure 16 Vent System through a masonry chimney using the Simpson Dura Vent Chimney Conversion Kit 934 May also be used in listed prefabricated chimneys Drawing is for illustrative purposes only DO NOT VENT TWO APPLIANCES INTO A SINGLE CHIMNEY 991 Vertical Termination Cap Cap ...

Page 14: ...ARD FROM STOVE TO TERMINATION DOWNWARD VENT RUNS TRAP HEAT AND CAUSE HIGH TEMPERA TURES TO DEVELOP WITHIN THE VENT THAT COULD START A FIRE Install a Vinyl Siding Standoff Simpson Dura Vent 950 between the vent termination and an exterior wall covered by vinyl siding material to prevent potential heat damage to the siding Do not recess the termination cap into a wall or siding Figure 17 Minimum ven...

Page 15: ... 16 cm minimum Jøtul N A strongly recommends 12 inches 30 cm particu larly where windy conditions are prevalent H Not to be installed above a meter regulator assembly within 3 feet 90 cm horizontally from the centerline of the regulator I Clearance to service regulator vent outlet U S 3 feet CAN 6 feet 1 8 m minimum J Clearance to nonmechanical air supply inlet to building or the combustion air in...

Page 16: ...STRUCTION AND SAFETY STAN DARD TITLE 24 CFR PART 3280 THIS APPLI ANCE IS ONLY FOR USE WITH THE TYPE OF GAS THAT IS INDICATED ON THE STOVE S RATING PLATE A GAS CONVERSION KIT IS PROVIDED WITH THE GF 300 DV GAS STOVE THIS APPLIANCE MAY BE INSTALLED IN AN AFTERMARKET PERMANENTLY LOCATED MANUFACTURED MOBILE HOME WHERE NOT PROHIBITED BY LOCAL CODES CET APPAREIL PEUT ETRE INSTALLE DANS UN MAISON PREFABR...

Page 17: ... stem under the stove but do not tighten You will set its final position later 10 Replace the Burner Plate Engage the burner tube with the Air Shutter assembly as in fig 25 Be sure the burner is securely engaged with the two support brackets at the front of the firebox and push the plate back toward the rear of the firebox When correctly positioned there will be 1 2 13 mm clearance between the bur...

Page 18: ...ew gasket is properly positioned and tighten screws securely 16 Install the identification labels to the stoveso that they can be seen by any person that may be servicing the stove Label A apply to back of stove Label B apply to the rating plate attached to the back of the stove Small Valve Label apply to valve 17 Reassemble the stove apply gas to the system and check for leaks using a soapy water...

Page 19: ... INLET GAS PRESSURES inches water column MIN MAX NATURAL GAS 5 0 7 0 PROPANE 12 0 14 9 The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing on that system at test pressures in excess of 1 2 psig 3 5 kPa The appliance must be isolated from the gas supply line by closing its individual manual gas shut off valve gas cock dur...

Page 20: ...e Appearance Air Shutter Adjustment The GF 300 DV gas stove is shipped from the factory equipped to burn Natural gas If the stove has been converted for use with propane the Air Shutter may require adjustment to achieve the desired flame appear ance Other installation related variables can also affect the flame picture The Air Shutter may be opened or closed to provide the best flame picture for y...

Page 21: ...gs DO NOTOBSTRUCTTHEPILOTASSEMBLYOPENING Donot pile up the embers in front ot the burner skirt edges See fig 36 Figure 32 Engage the holes in the underside ot the Rear Log with the two pegs in the burner skirt Figure 33 Install Right Log Figure 34 Install Left Log Figure 35 Install Middle Log Figure 36 Position embers loosely and maintain 1 4 clearance from the burner skirt edges 1 4 6 mm 1 4 6 mm...

Page 22: ... ADJUSTMENT This stove is equipped with a variable gas control valve that allows easy adjust ment of the flame height appearance and heat output To adjust the flame between the HI and LOW setting rotate the HI LOW knob located in the center of the valve face Flame height will adjust approximately 1 to 2 between the LOW and HIGH settings See fig 38 NO SMOKE OR SOOT SHOULD BE PRESENT CHECK LOG PLACE...

Page 23: ...ee of debris vacuum this area frequently Always keep the appliance area clear and free from combus tible materials gasoline and other flammable liquids If a vacuum is used during any service on the stove ALWAYS be sure the stove is cold and there are NO hot embers 5 Remember this appliance has a continuous burning pilot flame Exercise caution when using products having combustible vapors Always sh...

Page 24: ...turer s instructions provided at the initial installation Burner and Logset Periodically inspect the Firebox Valve Compartment Convection Airways and optional Blower to BE CERTAIN THAT THE FLOW OF COMBUSTION AND VENTILATION AIR IS UNOBSTRUCTED The firebox should be vacuumed annually to remove any surface build up Use a soft brush attachment and handle the logs carefully as they are fragile Be sure...

Page 25: ...g it all the way into the slot in the bottom of the Snapstat Bracket as shown in fig 43 3 Attach the Snapstat Bracket to the studs located in the middle of the firebox floor using the two M6 hex nuts and a 10 mm wrench See fig 43 4 Attach the Blower Bracket to the stove using the two M6 flange head hex bolts as shown in fig 43 5 Install the Blower with the duct openings oriented up and to the rear...

Page 26: ...tat knob If the burner turns off the blower will be shut off automatically when the stove cools down If automatic blower circulation is not desired place the blower control switch in the MANUAL position Wingscrew Male Quickconnector Female Quickconnector Figure 44 Attach Blower to the Mounting Bracket with the wingscrew and connect wires to Snapstat and female control quick connect Figure 45 Blowe...

Page 27: ... wall resting on the burner skirt Fig 49 5 Install a Side Panel Tilt the panel bottom edge first into position against the side wall The panel will stand on its own against the wall fitting snugly between the rear panel and the front wall of the firebox Fig 50 6 Install the Upper Rear Panel Simply rest it on the other two panels Fig 51 7 Install the other Side Panel 8 Reinstall the Logset Refer to...

Page 28: ...64 30 3 55 44 49 50 51 14 13 12 11 45 10 9 6 1 8 52 47 17 47 57 19 18 16 47 58 47 15 47 20 47 58 47 57 47 56 47 21 47 54 47 15 53 62 60 61 63 47 64 67 67 68 69 66 64 23 Figure 52 Illustrated Parts Breakdown GF 300 DV Allagash GF 300 DV Illustrated Parts Breakdown ...

Page 29: ...e Black Blue Black Ivory Forest Green Jøtul Iron 1 Side Plate 10203292 102033 10203229 10203232 10203285 2 Base Plate 10390092 10390027 10390029 10390032 10390085 3 Legs 4 10192592 101966 102251 10192532 10192585 4 Front Panel 10390192 10390127 10390129 10390132 10390185 5 Right Door 10390492 10390427 10390429 10390432 10390485 6 Top Plate 10390292 10390227 10390229 10390232 10390285 7 Left Door 1...

Page 30: ...____________ NAME OF INSTALLER ___________________ TYPE OF FUEL ________________________ WAS STOVE CONVERTED _______________ NOTES GF 300 DV Record the following information to help your dealer determine what you will need for parts and service RETAIN THIS MANUAL FOR REFERENCE AND MAKE IT AVAILABLE TO ANYONE USING OR SERVICING THE STOVE ...

Page 31: ...ol system and any gas control which has been under water 1 STOP Read the safety information above 2 Access the lower controls 3 Turn the stove ON OFF switch to OFF or set the thermostat to lowest setting if used 4 Confirm that the gas supply line shut off valve is open 5 Pushingascontrolknobslightlyand turnclockwise to OFF NOTE Knobcannot be turnedfrom PILOT to OFF unless the knob is pushed in sli...

Page 32: ...al product development Consequently products may differ in specification color or type of accessories from those illustrated or described in various publications Jøtul vise sans cesse a ameliorer ses produits C est pourquoi il se reserve le droit de modifier les specifications couleurs etequipement sans avis prelable Jøtul ASA P O Box 1411 N 1602 Fredrikstad Norway Jøtul North America 400 Riversid...

Reviews: