background image

3170 Wasson Road  •  Cincinnati, OH  45209  USA

Phone 513-533-5600  •  Fax 513-871-0105

[email protected]  •  www.steriflowvalve.com

I & M Mark 95LL Series

1-1/2” to 3” Valves

Installation & Maintenance Instructions for 

MK95LL Sanitary Back Pressure Regulators

Warning:

 Steriflow Sanitary Pressure Regulators must only be used, installed and repaired in accordance with these 

Installation & Maintenance Instructions. Observe all applicable public and company codes and regulations. In the 
event of leakage or other malfunction, call a qualified service person; continued operation may cause system failure 
or a general hazard. Before servicing any valve, disconnect, shut off, or bypass all pressurized fluid. Before disassem-
bling a valve, be sure to release all spring tension.

**VIP** - If you purchased your MK95A Valve, or any stem repair component for this valve after 9/17/2018 - 
please see assembly instruction change on page 2, top-right, section 3.

Please read these instructions carefully!

Your Steriflow product will provide you with long, trouble 
free service if it is correctly installed and maintained. 
Spending a few minutes now reading these instructions 
can save hours of trouble and downtime later. When 
making repairs, use only genuine Jordan Valve parts, 
available for immediate shipment from the factory.

Ideal Installation

1.  The valve is designed for sanitary service and it is 

assumed that it will be installed into a clean system. 
Under these conditions, special considerations to 
protect the valve such as providing line strainers at 
the valve inlet are not necessary.

2.  The regulator is to be installed with the inlet 

horizontal and the outlet pointed down. This will 
provide the best drainage inside the valve. These 
restrictions apply only for drainage considerations; 
the valve will function in any position. Contact factory 
for other possible orientations.

3.  Steam regulators are best located at the highest 

point in the piping with the take-off out of the top of 
the steam header. This will minimize the possibility of 
water in the regulator.

4.  For best control, 3’ 0” straight sections of pipe 

should be installed on either side of the regulator.

5.  Use caution in tightening commercial sanitary 

fittings. Over-tightening can cause the gasket to 
extrude into the flow passage.

6.  If possible, install a relief valve downstream from the 

regulator. Set at about 30% above the control point 
of the regulator.

7.  Operate the regulator within its pressure and tem- 

perature rating as stamped on the valve nameplate.

Start Up

1.  Slowly open the inlet shutoff valve and slowly turn 

the adjusting screw until the desired inlet pressure 
is shown on the inlet pressure gauge, without dis- 
charging fluid.

2.  To change the controlled pressure, turn the adjusting 

block (28) with handles (43) clockwise to increase 
the pressure, or counterclockwise to decrease the 
pressure.

3.  See section on cleaning cycle for lift cam instructions 

and usage. (see section on Clean-In-Place/ Steam-In-
Place.)

Maintenance

Caution: Make certain that there is no pressure in the 
valve before loosening any fittings or joints. The following 
steps are recommended:

1.  Close the inlet shutoff valve.
2.  Turn the adjusting block (28) counterclockwise until 

there is no pressure on the spring, allowing any 
trapped pressure to release downstream.

3.  Allow pressure to bleed off through the down- 

stream piping. Do not attempt to reverse the flow 
through the valve by bleeding pressure from the 
upstream side of the valve.

4.  When the pressure gauges indicate that all pressure 

has been removed from the system, close the outlet 
shutoff valve. The valve may be removed from the 
line and serviced.

Note: refer to the drawing at the end of this document 
for description and proper orientation of parts.

PROTECT VALVES WITH LINESTRAINERS

Reviews: