4.   Remove the condensate hose and the one screw 

attaching the pump bracket to the base

5.   Replace the pump, hose, wiring, bolts, and cover in the 

reverse order

4.7 Refrigerant Charging

If the refrigerant charge is lost due to service or a leak, a 

new charge must be accurately weighed in. If any of the 

old charge is left in the system, it must be removed before 

weighing in the new charge. Refer to the unit nameplate for 

the correct charge weight and refrigerant type.

4.8 Compressor/Capacitor Replacement

This compressor is equipped with a two terminal external 

overload, run capacitor, but no start capacitor or relay (see 

Fig. 3).

4.9 Gravity Drain Option

If the condensate pump fails and cannot be replaced 

immediately, the Ultimate 340 can be used by draining by 

gravity.
1.  Unplug the unit and remove the front cover.
2.  Push the plastic plug on the right side (see Fig. 4) out 

from inside the unit.

3.  Locate the heavy vinyl hose that connects the drain pan 

to the condensate pump. Pull the end out of the pump.

4.  Push that end of the vinyl hose through the hole in the 

right side.

5.  Connect a garden hose and run it to a drain. Keep the 

hose as flat to the floor as possible to avoid air pockets 

that would hinder draining. Placing the unit on something 

above the floor will also improve draining.

4.10 Relay

The contacts of the single pole, single throw relay complete 

the power circuit to the compressor. The contacts are closed 

when power is provided to the relay coil via the control circuit. 

The control circuit includes the power switch, low pressure 

control, defrost thermostat and timer.

Summary of Contents for Ultimate 340

Page 1: ...ntially drier air as well as for drying areas to much lower humidity levels than conventional dehumidifiers The Ultimate 340 LGR High Capacity Dehumidifier Improved water removal 145 pints per day AHA...

Page 2: ...always be used in the upright position The air inlet on top the side outlet must be at least 1 foot from walls and other obstructions to air flow Read the operation and maintenance instructions caref...

Page 3: ...before the final purge 2 8 Hour Meter The digital hour meter displays the cumulative and job time the dehumidifier has been turned on to the tenth of an hour The total and job hours measured are stor...

Page 4: ...claim authorization and technical assistance 4 2 Technical Description The Ultimate 340 uses a refrigeration system similar to an air conditioner s to remove heat and moisture from incoming air and to...

Page 5: ...d pump phase Unit pumps water automatically but not when PURGE button is pushed 1 Bad connection in PURGE button circuit 2 Defective control board Evaporator coil frosted continuously low dehumidifyin...

Page 6: ...pump fails and cannot be replaced immediately the Ultimate 340 can be used by draining by gravity 1 Unplug the unit and remove the front cover 2 Push the plastic plug on the right side see Fig 4 out f...

Page 7: ...L 7 WHT 9 WHT 7 YEL BLU GRY WHT RUN CAPACITOR COMPRESSOR BLOWER MOTOR LEVEL SWITCH RUN CAPACITOR RELAY LOW PRESSURE PUMP FLOAT SAFETY NC NO THERMISTOR PLUG R C S E5 E4 E1 E2 E3 6 0 4 1 WIRE NUT YEL YE...

Page 8: ...3 EA 1 Front 19 PH 4026304 EA 2 12 Wheel Item Part No Qty Description 20 PH 4026311 EA 1 Axle 21 PH 1284404 EA 2 Cotter Pin 22 PH 4027273 EA 1 Skid Plate 23 PH 4023080 EA 1 Coupling Insert 38 Tube 24...

Page 9: ...9 www jondon com Toll Free 1 800 556 6366 This page intentionally left blank...

Page 10: ...tion etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident acts of nature or any other cause beyond Jon...

Reviews: