Table 4: ZY04-06 Unit Clearances
Direction
Distance (in.)
Direction
Distance (in.)
Top
72
Right
18
Front
36
Left
12
Rear
18
2
/36
Bottom
1
1
Units must be installed outdoors. Overhanging structure or
shrubs should not obscure condenser air discharge outlet.
2
Units without economizer or power exhaust.
3
Units equipped with an Economizer or Power Exhaust. Flue
products must not be discharged within 10 Feet of the rear
of the unit.
4
Units may be installed on combustible floors made from
wood or class A, B or C roof covering materials.
Table 5: ZYA7 and ZY07-12 Unit Clearances
Direction
Distance (in.)
Direction
Distance (in.)
Top
72
Right
18
Front
48
Left
12
Rear
18
2
/36
Bottom
1
1
Units must be installed outdoors. Over hanging structure or
shrubs should not obscure condenser air discharge outlet.
2
Units without economizer or power exhaust.
3
Units equipped with an Economizer or Power Exhaust. Flue
products must not be discharged within 10 Feet of the rear
of the unit.
4
Units may be installed on combustible floors made from
wood or class A, B or C roof covering materials.
Figure 16: 1RC0456, 1RC0458 Roof Curb Dimensions
Table 6: Unit Models used with 1RC0456, 1RC0458
Roof Curb
• ZY04
• ZY05
• ZY06
Note:
If utilities are required through the
base of the unit or through the roof curb the
following field installed accessories can be
purchased through your dealer or contractor:
1TB0401 - through the base electrical and
through the curb gas
1TB0403 - through the base electrical and gas
INSTALLATION MANUAL ZY SERIES 3 - 10 ton 60 Hertz R-410A
21
Johnson Controls Ducted Systems
Summary of Contents for ZY Series
Page 2: ...2 INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A Johnson Controls Ducted Systems ...
Page 140: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 140 Johnson Controls Ducted Systems ...
Page 141: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 141 Johnson Controls Ducted Systems ...
Page 142: ...INSTALLATION MANUAL ZY SERIES 3 10 ton 60 Hertz R 410A 142 Johnson Controls Ducted Systems ...