Figure 31: Unit Control Board
Table 25: Unit Control Board Flash Codes
Flash
Codes
Description
Green
LED 16
Red
LED 8
Red
LED 4
Red
Led 2
Red
LED 1
On Steady
This is a Control Failure
-
-
-
-
-
1 Flash
Not Applicable
-
-
-
-
-
2 Flashes
Control waiting ASCD
1
1. Non-alarm conditions.
Flashing
Off
Off
On
Off
3 Flashes
HPS1 Compressor Lockout
Off
Off
Off
On
On
4 Flashes
HPS2 Compressor Lockout
Off
Off
On
Off
Off
5 Flashes
LPS1 Compressor Lockout
Off
Off
On
Off
On
6 Flashes
LPS2 Compressor Lockout
Off
Off
On
On
Off
7 Flashes
FS1 Compressor Lockout
Off
Off
On
On
On
8 Flashes
FS2 Compressor Lockout
Off
On
Off
Off
Off
9 Flashes
Ignition Control Locked Out / Ignition Control Failure
Off
On
Off
Off
On
10 Flashes
Compressors Locked Out on Low Outdoor Air Temperature
1
Flashing
On
Off
On
Off
11 Flashes
Compressors locked out because the Economizer is using free Cooling
1
Flashing
On
Off
On
On
12 Flashes
Unit Locked Out due to Fan Overload Switch Failure
Off
On
On
Off
Off
13 Flashes
Compressor Held Off due to Low Voltage
1
Flashing
On
On
Off
On
14 Flashes
EEPROM Storage Failure
Off
On
On
On
Off
15 Flashes
HPS3 Compressor Lockout
Off
On
On
On
On
16 Flashes
HPS4 Compressor Lockout
On
Off
Off
Off
Off
17 Flashes
LPS3 Compressor Lockout
On
Off
Off
Off
On
18 Flashes
LPS4 Compressor Lockout
On
Off
Off
On
Off
19 Flashes
FS3 Compressor Lockout
On
Off
Off
On
On
20 Flashes
FS4 Compressor Lockout
On
Off
On
Off
Off
21 Flashes
Compressor Off due to Low SAT
1
On
Off
On
Off
On
OFF
No Power or Control Failure
Off
Off
Off
Off
Off
Check
Alarm
History
Reset All ASCDs
For One Cycle
Non Alarm Condition
Green LED Flashing
Current Alarm