background image

Figure 4: ZFR1831 wired to a Field Controller via RJ12

Figure 5: RJ12 pin out on the controller

Note: 

See MS/TP Communications Bus Technical Bulletin (LIT-12011034) for more information.

7

ZFR1831 Pro Series Wireless Router Installation Guide

Johnson Controls - CONFIDENTIAL

Summary of Contents for ZFR1831 Pro Series

Page 1: ...nt The WRG1830 ZFR183x Series Wireless Field Bus System is not designed or intended for use in mission critical or life safety applications North American emissions compliance United States Compliance Statement Part 15 19 This device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must ac...

Page 2: ...uct warranty Important The modular phone jack and screw terminal connections cannot be used simultaneously Location Considerations Follow these guidelines when locating an ZFR1831 within an ZFR183x Pro Series Wireless Field Bus system The ZFR1831 wireless router can be installed on wall wall box conduit or ceiling grid Do not mount inside metal enclosures or on surfaces that can block RF signals L...

Page 3: ...es for an WRG1830 ZFR183x Series system and for estimating the number of ZFR1831 Routers needed as repeaters for extending wireless transmission range refer to the applicable WRG1830 ZFR183x Series Wireless Field Bus System Technical Bulletin Parts included Verify that the following parts shipped with the ZFR Pro Router ZFR1831 Wireless Router 3m 10ft wiring cable ZFR1831 Pro Series Wireless Insta...

Page 4: ...Figure 2 ZFR1831 Router conduit installation mounting view ZFR1831 Pro Series Wireless Router Installation Guide 4 Johnson Controls CONFIDENTIAL ...

Page 5: ...s to transmit a message to the coordinator In a well designed system the layout design should minimize the required hops based on the recommended transmission ranges and should typically be kept below five Information on determining the numbers of hops being used is covered in the WRG1830 Wireless Gateway Users Guide LIT 12013550 The WRZ sensors list a lower line of sight range because they transm...

Page 6: ...und the ZFR1831 to promote good ventilation LED visibility and ease of service Important Do not connect supply power to the ZFR1831 before finishing wiring and checking all wiring connections Short circuits or improperly connected wires may result in permanent damage to the ZFR1831 Important Use copper conductors only Make all wiring in accordance with local national and regional regulations The Z...

Page 7: ...d Controller via RJ12 Figure 5 RJ12 pin out on the controller Note See MS TP Communications Bus Technical Bulletin LIT 12011034 for more information 7 ZFR1831 Pro Series Wireless Router Installation Guide Johnson Controls CONFIDENTIAL ...

Page 8: ...or ceiling grid 2 Connect a 15VDC to 24 VAC source to the wireless router s screw terminal pin connectors Figure 7 ZFR1831 wired as Stand alone Repeater Using as a coordinator connected to WRG 1 Follow the mounting instructions above for mounting to either wall wall box conduit or ceiling grid ZFR1831 Pro Series Wireless Router Installation Guide 8 Johnson Controls CONFIDENTIAL ...

Page 9: ... and adjustments Selecting a PAN OFFSET for a Wireless Network When selecting a PAN OFFSET for a wireless network keep these points in mind All devices within one wireless mesh network must be set to the same PAN setting Select PAN settings that are unique for the site The AREA rotary switch should be set to 0 Figure 9 ZFR1831 Router Rotary Switches 9 ZFR1831 Pro Series Wireless Router Installatio...

Page 10: ...r Controller and Repeater Product code number ZFR1831 0 Wireless Field Bus Router Power supply input 15VDC with cable connected to field controller or 24 VAC nominal 20 VAC minimum 30 VAC maximum 50 60 Hz power supply Class 2 Addressing Rotary Switches Field Adjustable Wireless band Direct Sequence Spread Spectrum 2 4 GHz ISM Bands Transmission power 100 mW Maximum selectable Transmission range 75...

Page 11: ...egulations for Low Power Unlicensed Transmitters Transmitter Identification ZFR1831 FCC OEJ ZFRRADIO Canada CAN CSA E60730 1 15 Canadian Standard For Automatic electrical controls for Household and Similar use Part 1 General requirements Energy Management Equipment Industry Canada IC Compliant to Canadian ICES 003 Class B Limits Industry Canada IC RSS 210 Transmitter Identification ZFR1831 279A ZF...

Page 12: ...Johnson Controls CONFIDENTIAL www johnsoncontrols com ...

Reviews: