ZFR1812 Wall Mount Wireless Field Bus Router Installation Instructions

1

Application  

A ZFR1812 Wireless Field Bus Router is used with 
Advanced Application Field Equipment Controllers 
(FACs), Field Equipment Controllers (FECs), Input/
Output Modules (IOMs), and Variable Air Volume 
Modular Assembly (VMA) Series field controllers.

The ZFR1812 Router provides a wireless interface 
between:

a field controller and the supervisory controller (by
means of a ZFR1810 Coordinator)

a field controller and associated WRZ Series
Wireless Room Sensors

Additionally, the ZFR1812 Wireless Field Bus Router 
can be used as a repeater in WRZ-7860-0 One-to-One 
Wireless Room Temperature Sensing System. For 
more information, refer to the 

WRZ Series One-to-One 

Wireless Room Sensing System Technical Bulletin 
(LIT-12011641)

Up to nine WRZ Series Sensors can be associated 
with a single field controller. In multi-sensor 
applications, the ZFR1812 Router passes all the 
sensor data to an FAC, FEC, IOM, or VMA controller, 
which can be configured to either average the sensors’ 
input or select the highest or lowest sensed condition 
for control of the target zone.

A ZFR1812 Router is powered directly from the 
connected field controller’s 15 VDC output. 

The ZFR812 Router is also included in the Repeater 
Accessory Kits, MS-ZFRRPTK-H1 or MS-ZFRRPTK-
H2. These kits include a 24 VAC to 15 VDC converter 
power supply for stand-alone operation. As a repeater, 
the ZFR1812 extends the range and strengthens the 
wireless mesh network.

Refer to the 

ZFR1800 Series Wireless Field Bus 

System Technical Bulletin (LIT-12011295)

 or the 

ZFR1800 Series Wireless Field Bus System Quick 
Reference Guide (LIT-12011630)

 for information on 

commissioning and configuring a ZFR1800 Series 
Wireless Field Bus System for operation.

North American Emissions Compliance

United States

Canada

Use the ZFR1812 Wireless Field Bus Router

 

only to 

provide an input to equipment under normal 
operating conditions. Where failure or malfunction of 
the ZFR1812 Router could lead to personal injury or 
property damage to the controlled equipment or 
other property, additional precautions must be 
designed into the control system. Incorporate and 
maintain other devices, such as supervisory or 
alarm systems or safety or limit controls, intended to 
warn of or protect against failure or malfunction of 
the ZFR1812 Router.

IMPORTANT:

The ZFR1800 Series Wireless Field 

Bus System is not designed or intended for use in 
mission-critical or life/safety applications.

Compliance Statement (Part 15.19)

This device complies with Part 15 of the FCC Rules. 
Operation is subject to the following two conditions:

1.

This device may not cause harmful interference,
and

2.

This device must accept any interference
received, including interference that may cause
undesired operation.

Warning (Part 15.21)

Changes or modifications not expressly approved by 
the party responsible for compliance could void the 
user’s authority to operate the equipment.

Industry Canada Statement

The term 

IC

 before the certification/registration 

number only signifies that the Industry Canada 
technical specifications were met.

Le terme « IC » précédant le numéro d'accréditation/
inscription signifie simplement que le produit est 
conforme aux spécifications techniques d'Industry 
Canada.

ZFR1812 Wall Mount Wireless Field Bus Router

Installation Instructions

MS-ZFR1812-x

Part No. 24-10325-45, Rev. A

Issued April 2016

Summary of Contents for ZFR1812

Page 1: ...es Wireless Field Bus System Quick Reference Guide LIT 12011630 for information on commissioning and configuring a ZFR1800 Series Wireless Field Bus System for operation North American Emissions Compliance United States Canada Use the ZFR1812 Wireless Field Bus Router only to provide an input to equipment under normal operating conditions Where failure or malfunction of the ZFR1812 Router could le...

Page 2: ...deal See Location Considerations Mounting Directly to Drywall with Drywall Anchors ZFR1812 1 Separate the plastic base and circuit board assembly cover Do not remove the security screw from the cover See Figure 2 IMPORTANT The label showing the unit MAC address is on the plastic base of the unit Be sure to keep the plastic base and circuit board assemblies together so the correct MAC address is sh...

Page 3: ...g the ZFR1812 flush for a professional appearance A hole is provided in the base of the assembly for this purpose Figure 3 IMPORTANT If you are using a ceiling mounting clip you must make sure that no part of the clip makes contact with the circuit board assembly when installed 3 Assemble the external power and adapters as necessary Figure 4 a The 24 VAC to 15 VDC power supply 1 uses screw termina...

Page 4: ... the circuit board assembly in the plastic base 6 Tighten the security screw to prevent tampering using a 1 5 mm 1 16 in Allen wrench or a Johnson Controls T 4000 119 Allen Head Adjustment Tool Use caution when tightening the screw to avoid stripping the plastic threads in the ZFR1812 7 Assemble the external power and adapters as necessary Figure 4 Note that the power supply can be secured in an e...

Page 5: ...810 Coordinator ZFR1812 Router and a WRZ Sensor can be less than the maximum distances shown in Table 1 The effective transmission range for indoor applications varies because of wireless signal absorption and reflection due to metal obstructions walls or floors and furniture found in typical building interiors Wiring Wiring Considerations and Guidelines Wiring with an FEC or VMA16 Series Field Co...

Page 6: ...AC26 FC Bus RJ 12 Jack SA Bus RJ 12 Jack SA Bus Terminals FAC36 FC Bus RJ 12 Jack SA Bus RJ 12 Jack SA Bus Terminals FEC16 FC Bus RJ 12 Jack SA Bus RJ 12 Jack SA Bus Terminals FEC26 FC Bus RJ 12 Jack SA Bus RJ 12 Jack SA Bus Terminals IOM172 3 SA FC Bus RJ 12 Jack Not available in wireless mode Use CCT with ZFR Dongle N A IOM272 3 SA FC Bus RJ 12 Jack Not available in wireless mode Use CCT with ZF...

Page 7: ... then all on and then set the switches to the desired PAN Restore power to the ZFR1812 and see that it joins the correct network If the ZFR1812 misread the dip switches it might become the child of another network and use up an available child slot in a device you did not expect If this situation occurred a reform on the incorrect network should clear up the now unusable child address Note On some...

Page 8: ...Wireless Room Temperature Sensors Installation Instructions Part No 24 10332 2 for more information Approximately once every 10 seconds the Signal Strength LED flashes to indicate the strength of the signal received from neighboring devices See Table 3 Note The Signal Strength LEDs on all the ZFR1812 routers in a network extinguish after approximately 2 hours of normal operation making the ZFR1812...

Page 9: ...trength 3 Flashes Excellent 2 Flashes Good 1 Flash Weak OFF for 3 seconds None Network Reform Operation during network reform Rapid Flashes for 5 minutes rapid flashes occur for up to 5 minutes when the Reform Network option is initiated to the network the ZFR1812 Router disconnects itself from the network when the PAN OFFSET is changed on the ZFR1812 Router when the PAN OFFSET is changed on the Z...

Page 10: ...FR router is better facilitated using a Inch conduit EMT connector MS ZFRRPTK H1 ZFR1812 0 wireless router repeater kit Includes ZFR1812 router 24 VAC to 15 VDC power supply RJ 12 cable for power extension and mounting hardware Use the ZFRRPT H1 for flush wall mount or ceiling mount applications MS ZFRRPTK H2 ZFR1812 0 wireless router repeater kit Includes ZFR1812 router 24 VAC to 15 VDC power sup...

Page 11: ... for the repeater power supply has a flexible input power range and provides regulated 12 VDC output Input power 20 28 VAC at 78 62 mA maximum 16 30 VDC at 45 28 mA maximum Output power 12 VDC regulated at 500 mA maximum Current Consumption 90 mA maximum Addressing DIP Switches Field Adjustable Wireless Band Direct Sequence Spread Spectrum 2 4 GHz ISM Bands Transmission Power 10 mW Maximum Transmi...

Page 12: ...810 1 279A WRZRADIO Australia and New Zealand RCM Mark Australia NZ Emissions Compliant Europe CE Mark Johnson Controls Inc declares that this product is in compliance with the essential requirements and other relevant provisions of the RED Directive The performance specifications are nominal and conform to acceptable industry standard For application at conditions beyond these specifications cons...

Page 13: ...tion Instructions Metasys and Johnson Controls are registered trademarks of Johnson Controls Inc All other marks herein are the marks of their respective owners 2016 Johnson Controls Inc Building Efficiency 507 E Michigan Street Milwaukee WI 53202 13 Figure 11 ZFR1812 Mounting Template Scale 1 000 ...

Reviews: