background image

ZFR1810 Wireless Field Bus Coordinator Installation Instructions

10

Accessories

Technical Specifications      

Table 4:  Accessories (Order Separately)

Product Code 
Number

Product Description

TP-2420

Transformer, Wall Plug Mount, 120 VAC to 24 VAC, 20 VA, Class 2

WRZ-SST-120

Wireless Sensing System Tool. Requires WRZ Series Sensor to function as a site survey tool for 
ZFR1800 Wireless Field Bus System, or for WRZ-7860-0 One-to-One Room Sensing System.

Y65T31-0

1

Transformer, 120/208/240 VAC to 24 VAC, 40 VA, Class 2, Foot Mount, 20 cm (8 in.) Primary Leads 
and Secondary Screw Terminals

ZFR-USBHA-0

USB Dongle with ZFR Driver provides a wireless connection through the CCT to allow wireless 
commissioning of the wireless enabled FAC, FEC, IOM, and VMA16 controllers. The USB ZFR Dongle 
is also used with the ZFR Checkout Tool used to troubleshoot and validate ZFR wireless meshes using 
a laptop computer. 

ZFR-1810ANT-700

Replacement antenna kit for ZFR1810 Wireless Field Bus Coordinator. Includes antenna, coaxial 
cable, and mounting hardware.

1.

Additional Y60 Series Transformers are available from Johnson Controls.

ZFR1810 Wireless Field Bus Coordinator (Part 1 of 2)

Product Code Number

MS-ZFR1810-x

Power Supply Input

One of the following:

• 

24 VAC +10%/-15%, 50/60 Hz, Class 2. Transformer allowance should be 2.5 VA 
maximum, 2 VA typical. Provided through the three-position 24 V~ screw terminal 
pluggable block.

• 

15 VDC, 180 mA (7 to 18 VDC, 185 mA maximum current draw) on the FC Bus 
provided through the FC/SA BUS IN RJ-12 jack from the FC Bus Jack on a Field 
Controller or NxE supervisory engine.

Power Supply Output

15 VDC; Provided through the FC/SA BUS, FC/SA BUS OUT RJ-12 jack for external 
devices.

Addressing

DIP Switches, Field Adjustable

Wireless Band

Direct-Sequence Spread-Spectrum, 2.4 GHz ISM Bands

Transmission Power

10 mW Maximum

Transmission Range

76.2 m (250 ft)

 

Maximum Line-of-Sight 

15 m (50 ft) Recommended

Ambient Conditions

Operating:

 0 to 50°C (32 to 122°F), 5 to 95% RH, Noncondensing

Storage:

 -20 to 70°C (-4 to 158°F), 5 to 90% RH, Noncondensing

Materials

White Plastic Housing with Plenum rating per UL1995 UL94-5VB Flammability Rating

Terminations

Two spade terminals with three-position screw terminal pluggable block for 24 VAC power 
supply input.
Four spade terminals with four-position screw terminal pluggable block for RS-485 
communications.
RJ-12 IN jack for 15 VDC power supply and communications connection from an NxE or 
FEC FC Bus jack. 
RJ-12 OUT jack supplies 15 VDC and communications to BTCVT Wireless 
Commissioning Converter.

Dimensions

146 x 122 x 52 mm (5.8 x 4.8 x 2.1 in.)

Summary of Contents for ZFR1810

Page 1: ...FR1800 Series Wireless Field Bus System Technical Bulletin LIT 12011295 or the ZFR1800 Series Wireless Field Bus System Quick Reference Guide LIT 12011630 for information on commissioning and configuring a ZFR1800 Series Wireless Field Bus System for operation IMPORTANT Use the ZFR1810 Wireless Field Bus Coordinator only to provide an input to equipment under normal operating conditions Where fail...

Page 2: ...term IC before the certification registration number only signifies that the Industry Canada technical specifications were met This device has been designed to operate with an antenna having a maximum gain of 2 dB Antenna having a higher gain is strictly prohibited per regulations of Industry Canada The required antenna impedance is 50 ohms To reduce potential radio interference to other users the...

Page 3: ...minimum position a ZFR1810 Coordinator within 15 2 m 50 ft of at least two ZFR1811 Routers At a minimum position all ZFR1811 Routers within 15 2 m 50 ft of at least two other ZFR1811 Routers or one ZFR1811 Router and the ZFR1810 Coordinator Locate the ZFR1810 Coordinator on the same floor as the associated ZFR1811 Router and WRZ Series Sensors Test the transmission signal strength between the ZFR1...

Page 4: ... Routers Use Figure 3 and the following steps to assemble the remote mount antenna 1 Remove the knock out tab on the enclosure panel box or drill a 7 8 in diameter hole in the desired location on the top of the enclosure 2 Insert the round bushing into the hole in the enclosure 3 Insert the hexagonal bushing into the antenna mounting bracket 4 Thread the antenna cable through the hexagonal bushing...

Page 5: ...ive bonding to the panel is completely attached Note Extra pieces of RFT are provided so that you can change the mounting location on the top of the panel at a later date if necessary Attaching the Antenna to the ZFR1810 Wireless Field Bus Coordinator To attach the antenna to the ZFR1810 Coordinator 1 Remove the top cover of the ZFR1810 Coordinator by simultaneously pushing in both flexible tabs o...

Page 6: ...nd Figure 1 FC Bus Jack Power and Communication Use a six conductor SA Bus RS 485 cable with RJ12 connectors to connect the ZFR1810 Coordinator to the FC Bus connector FC SA BUS IN on the NAE or NCE supervisory engine This connection provides both power and communication to the ZFR1810 Coordinator IMPORTANT Do not connect supply power to the ZFR1810 Coordinator before finishing wiring and checking...

Page 7: ...ireless mesh network the ZFR1810 Coordinator and each associated ZFR1811 Router and WRZ Series Sensor PAN Offset and MS TP Address Interaction At Release 4 1 and later the MS TP address of the ZFR1810 Coordinator is no longer fixed at 2 The new address is 120 plus the sum of the first three values of the PAN Offset that are set to the ON position giving an MS TP address range of 120 to 127 IMPORTA...

Page 8: ... the signal from neighboring devices See Table 3 and Figure 1 Refer to the ZFR1800 Series Wireless Field Bus System Technical Bulletin LIT 12011295 for more information on determining the signal strength between ZFR1800 Series devices in your application WRZ SST 120 Wireless Sensing System Tool Use the WRZ SST 120 Wireless Sensing System Tool with a WRZ Series Sensor as a site survey tool to deter...

Page 9: ... Actuator FC SA Bus IN jack Fault Red Off Off Steady Normal On Steady Internal Errors detected FC Bus Green Blink Blink 2 Hz Normal operation ZFR1810 Coordinator is receiving BACnet frames over the wire Off Steady Attempting to Auto Baud or not connected to active MS TP network On Steady Auto Baud complete and not receiving BACnet frames Wireless Green Blink Blink 2 Hz Normal operation ZFR1810 Coo...

Page 10: ...Power Supply Input One of the following 24 VAC 10 15 50 60 Hz Class 2 Transformer allowance should be 2 5 VA maximum 2 VA typical Provided through the three position 24 V screw terminal pluggable block 15 VDC 180 mA 7 to 18 VDC 185 mA maximum current draw on the FC Bus provided through the FC SA BUS IN RJ 12 jack from the FC Bus Jack on a Field Controller or NxE supervisory engine Power Supply Out...

Page 11: ... Industry Canada IC Compliant to Canadian ICES 003 Class B Limits Industry Canada IC RSS 210 Transmitter Identification ZFR1810 0 5969A MATRIXLP Transmitter Identification ZFR1810 1 279A WRZRADIO Australia and New Zealand RCM Mark Australia NZ Emissions Compliant Europe CE Mark Johnson Controls Inc declares that this product is in compliance with the essential requirements and other relevant provi...