Magnetic bearing controller screen
Figure 17: Magnetic bearing controller screen
This screen displays the orientation of the magnetic bearing axes relative to the compressor
driveline. Pertinent parameters transmitted to the control panel from the Magnetic Bearing
Controller (MBC) are displayed on this screen. Many parameters are shown in the diagram in the
locations they represent. The left end of the motor shaft graphic represents the low stage (single
stage) impeller end bearing. The right end of the motor shaft graphic represents the opposite end
bearing.
Table 22: Display only fields
Field/LED name
Description
V13 Position
Displays the shaft position in micrometers from center along the radial axis designated “V”
for the Impeller End Bearing.
W13 Position
Displays the shaft position in micrometers from center along the radial axis designated “W”
for the Impeller End Bearing.
W1 (Current)
Displays the magnetizing current to the upper bearing on the radial axis designated “W” for
the Impeller End.
W3 (Current)
Displays the magnetizing current to the lower bearing on the radial axis designated “W” for
the Impeller End.
V1 (Current)
Displays the magnetizing current to the upper bearing on the radial axis designated “V” for
the Impeller End.
V3 (Current)
Displays the magnetizing current to the lower bearing on the radial axis designated “V” for
the Impeller End.
Z1 (Current)
Displays the magnetizing current to the axial bearing at the Impeller End.
V24 Position
Displays the shaft position in micrometers from center along the radial axis designated “V”
for the Opposite Impeller End Bearing.
W24 Position
Displays the shaft position in micrometers from center along the radial axis designated “W”
for the Opposite Impeller End Bearing.
W2 (Current)
Displays the magnetizing current to the upper bearing on the radial axis designated “W” for
the Opposite Impeller End.
W4 (Current)
Displays the magnetizing current to the lower bearing on the radial axis designated “W” for
the Opposite Impeller End.
V2 (Current)
Displays the magnetizing current to the upper bearing on the radial axis designated “V” for
the Opposite Impeller End.
YVAM Control Center
42
Summary of Contents for YORK YVAM 0350
Page 2: ...2 YVAM Control Center...
Page 10: ...Figure 4 Variable speed drive nomenclature YVAM Control Center 10...
Page 15: ...Figure 8 System piping and instrumentation diagram P ID 15 YVAM Control Center...
Page 154: ...Figure 62 Sample printout status or history YVAM Control Center 154...
Page 155: ...Figure 63 Sample printout status or history continued 155 YVAM Control Center...
Page 156: ...Figure 64 Sample printout setpoints YVAM Control Center 156...
Page 157: ...Figure 65 Sample printout setpoints continued 157 YVAM Control Center...
Page 158: ...Figure 66 Sample printout schedule YVAM Control Center 158...
Page 159: ...Figure 67 Sample printout sales order 159 YVAM Control Center...
Page 160: ...Figure 68 Sample printout security log report YVAM Control Center 160...