Table 52: Condenser nozzle dimensions
Condenser nozzle dimensions ft in. (mm)
1-pass
2-pass
3-pass
Condenser shell code
H
K
H
J
K
H
K
U
6
2 ft 8 in.
(813)
1 ft 3 in.
(381)
2 ft 4 in.
(711)
1 ft 2 1/4 in.
(362)
1 ft 1 in.
(330)
2 ft 4 in.
(711)
1 ft 1 in.
(330)
X,Z
3 ft 5 1/2 in.
(1,054)
1 ft 6 1/2 in.
(470)
3 ft 0 1/2 in.
(927)
1 ft 2 in.
(356)
1 ft 4 1/4 in.
(413)
2 ft 9 1/2 in.
(851)
1 ft 2 in.
(356)
Y
6
3 ft 4 3/4 in.
(1,035)
1 ft 7 1/4 in.
(489
3 ft 0 1/4 in.
(921)
1 ft 8 3/4 in.
(527)
1 ft 5 in.
(432)
3 ft 0 1/4 in.
(921)
1 ft 5 in.
(432)
Note:
1. All dimensions are approximate.
2. Standard water nozzles are Schedule 40 pipe size, furnished as welding stub-outs with
grooves, allowing the option of welding, flanges, or use of grooved couplings. Factory-
installed, class 150 (ANSI B16.5, round slip-on, forged carbon steel with 1/16 in. raised
face), water flanged nozzles are optional (add 1/2 in. to nozzle length). Companion
flanges, nuts, bolts, and gaskets are not furnished.
3. One-, two-, and three-pass nozzle arrangements are available only in pairs shown and
for all shell codes. Any pair of evaporator nozzles may be used in combination with any
pair of condenser nozzles. Compact waterboxes on one heat exchanger may be used
with Marine Waterboxes on the other heat exchanger.
4. Condenser water must enter the waterbox through the bottom connection for proper
operation of the sub-cooler to achieve rated performance.
5. Add dimension M as shown in Table 5 or Table 13 according to the isolator type.
6. Heat recovery units offer marine waterbox option for tower (lower) bundle only.
55
Model YK (Style G) Centrifugal Liquid Chiller
Summary of Contents for YORK YK Series
Page 2: ...2 Model YK Style G Centrifugal Liquid Chiller...
Page 14: ...Figure 3 Long term storage tube side Model YK Style G Centrifugal Liquid Chiller 14...
Page 19: ...Figure 6 Neoprene isolators in mm 19 Model YK Style G Centrifugal Liquid Chiller...
Page 20: ...Figure 7 Spring isolators in mm Model YK Style G Centrifugal Liquid Chiller 20...
Page 21: ...Figure 8 Spring isolators continued in mm 21 Model YK Style G Centrifugal Liquid Chiller...