Johnson Controls York YH9FZH12-AFX Installation Manual Download Page 5

1. If the supply cord is damaged, it must be replaced by the manufacturer or its

service agent or a similar quali ed person. The type of connecting wire is

H05RN-F or H07RN-F.

2. If the fuse on PC board is broken please change it with the type of 

T. 3.15A/250V.

3. The wiring method should be in line with the local wiring standard.
4. After installation, the power plug should be easily reached.
5. A breaker should be incorporated into xed wiring. The breaker should be

all-pole switch and the distance between its two contacts should be not less
than 3mm.

3

Outdoor unit

Indoor unit

A

B

Outdoor unit

Indoor unit

A

B

A

B

Outdoor unit

Indoor unit

Oil trap

Outdoor unit

Install according to

Drawing for the installation of indoor and outdoor units

To bend a pipe, give the roundness as large as possible not to crush the pipe ,

and the bending radius should be 30 to 40 mm or longer.

Connecting the pipe of gas side rst makes working easier.
The connection pipe is specialized for R410A.

Use the same method on indoor unit. Loosen the screws on terminal block and

insert the plugs fully into terminal block, then tighten the screws.

Insert the cable according to terminal number in the same manner as the indoor
unit.
If wiring is not correct, proper operation can not be carried out and controller
may be damaged.
Fix the cable with a clamp.

Installation of Outdoor Unit

Half union

Flare nut

Torque wrench

CAUTION

Be careful that matters, such as wastes of sands, etc. shall not enter the pipe.
The standard pipe length is 5m. If it is over 7m, the function of the unit will be
affected. If the pipe has to be lengthened, the refrigerant should be charged,

according to 20 g/m. But the charge of refrigerant must be conducted by profes-

sional air conditioner engineer. Before adding additional refrigerant, perform air
purging from the refrigerant pipes and indoor unit using a vacuum pump,then

Spanner

Forced fastening without careful centering may
damage the threads and cause a leakage of gas.

Pipe Diameter( )

Fastening torque

Liquid side6.35mm(1/4")

18N.m

Liquid/Gas side9.52mm(3/8")

42 N.m

Gas side 12.7mm(1/2")

55N.m

Gas side 15.88mm(5/8")

60 N.m

Max.Elevation:

In case the elevation A is more
than 5m, oil trap shoud be
installed every 5~7m
Max. Length:
In case the pipe length B is
m
diameter is 6.35mm the refrigerant 
should be charged, according to 20g/m
;if the liquid diameter is 6.35mm the
refrigerant should be charged, 
according to 50g/m

ore than 7m, if the liquid pipe 

1

Connection of pipes

2

charge additional refrigerant.

Connection

3

If the drain-elbow is used,

please attach it as gure. (Note:
Only for heat pump unit.)

Detach the service port’s cap of

1.

3-way valve, the valve rod’s cap for 2-way valve

and 3-way’s, connect the service port into the projection of charge hose (Iow)

for gaugemanifold. Then connect the projection of charge hose (center) for gau-

gemanifold into vacuum pump.

Open the handle at Iow in

2.

gaugemanifold, operate vacuum pump. If the scale-

moves of gause (Iow) reach vacuum condition in a moment, check 1. again.

Vacuumize for over 15min.And check the level gauge which should read -0.1MPa

3.

(76 cm Hg) at Iow pressure side. After the completion of vacuumizing, close the

handle ‘Lo’ in gaugemanifold and stop the operation of the vacuum pump. Check

condition of the scale and hold it for 1-2min. If the scale-moves back in spite of

tightening, make aring work again, the return to the beginning of 3 .

Attaching Drain-Elbow

4

Purging Method:To use vacuum pump

5

Open the valve rod for the 2-way valve to an angle  of

4.

anticlockwise 90 degrees.

After 6 seconds, close the 2-way valve and make the inspection of gas leakage.

Amax=15m

Bmax=25m

Indoor unit

Outdoor unit

2

 3G2.5mm

-mod     18:

2

1

/

POWER
SUPPLY

BL

BR

Y/G

Indoor unit

Outdoor unit

6G0.75mm

Power cable:

3G2.5mm

<+)<+%$+$;

<+)<+%$+$;

<+)<+%$+$;

Power cable:

3G2.5mm

Summary of Contents for York YH9FZH12-AFX

Page 1: ...INSTALLATION MANUAL High Wall Fixed R 410A 60Hz YH9FZH12 18 24BAH AFX Read this manual before installation and operation Make sure that it is well kept for later reference ...

Page 2: ......

Page 3: ...n a wall place where the indoor unit can receive signals when the Àuorescent ƽ lamps in the room are lightened Outdoor Unit Place which is less affected by rain or direct sunlight and is suf ciently ventilated ƽ Place possible to bear the unit where vibration and noise are not increased ƽ Place where discharged wind and noise do not cause a nuisance to the neighbors ƽ Place where a distance marked...

Page 4: ...f indoor unit and pull it out on the front side then connect them 3 Coat the aring seal face with refrigerant oil and connect pipes Cover the connection part with heat insulation materials closely and make sure xing with adhesive tape Fixing the indoor unit body Hang surely the unit body onto the upper notches of the mounting plate Move the body from side to side to verify its secure xing In order...

Page 5: ... perform air purging from the refrigerant pipes and indoor unit using a vacuum pump then Spanner Forced fastening without careful centering may damage the threads and cause a leakage of gas Pipe Diameter Fastening torque Liquid side6 35mm 1 4 18N m Liquid Gas side9 52mm 3 8 42 N m Gas side 12 7mm 1 2 55N m Gas side 15 88mm 5 8 60 N m Max Elevation In case the elevation A is more than 5m oil trap s...

Page 6: ...rth leakage breaker 4 Flare pipe Lean Damage of Àare Crack Partial Too outside Correct Incorrect 3 On Drainage It becomes high midway The gap with the ground is too smal There is the bad smell from a ditch It waves The end is imm ersed in water Please install the drain hose so as to be downward slope without fail Please don t do the drainage as shown below ƽ ƽ Please pour water in the drain pan of...

Page 7: ......

Page 8: ...2015 Johnson Controls Inc www johnsoncontrols com Doc No AH9FZHAH 151103 ...

Reviews: