SECTION 4 - PRINTERS
NAMEPLATE INFORMATION
-----------------------------------------------
MOTOR CODE
=
POWER (VOLTS)
=
PHASES =
FREQUENCY ( HZ)
=
LOOKED ROTOR AMPS
=
FULL LOAD AMPS
=
INRUSH AMPS
=
SYSTEM INFORMATION
-----------------------------------------------
REFRIGERANT =
TONS =
GEAR CODE
=
LIQUID TYPE
=
BRINE PERCENT
=
KILOWATTS INPUT
=
VSD / SSS / EM
=
FIGURE 46 -
SAMPLE PRINTOUT (SALES ORDER)
(CONT’D)
YORK HISTORY 1
CHILLER ID 0
(c) 1997 – 2004 YORK INTERNATIONAL CORPORATION
Mon 22 Nov 2004 9:23:12 AM
SYSTEM READY TO START
LCSSS – LOGIC BOARD POWER SUPPLY
[Any warnings active at shutdown will be listed here]
Controls
C.MLM.08.01
Run Time
0 Days 2 Hr 59 Min
Operating Hours
= 25 Hr
Number Of Starts
= 6
Control Source
= Local
Evaporator
-----------------------------------------------------
Leaving Chilled Active Setpoint
= 45.0 ºF
Chilled Liquid Pump
= Stop
Chilled Liquid Flow Switch
= Open
Leaving Chilled Liquid Temperature
= 45.0 ºF
Return Chilled Liquid Temperature
= 55.0 ºF
Evaporator Pressure
= 75.0 Psig
Evaporator Saturation Temperature
= 44.4 ºF
Evaporator Refrigerant Temperature
= 44.5 ºF
[If Refrigerant Sensor enabled]
Small Temperature Difference
= 0.5 ºF
Condenser
-----------------------------------------------------
Condenser Liquid Pump
= Stop
Condenser Liquid Flow Switch
= Open
Leaving Condenser Liquid Temperature
= 95.0 ºF
Return Condenser Liquid Temperature
= 85.0 ºF
Condenser Pressure
= 200.0 Psig
Condenser Saturation Temperature
= 101.4 ºF
Small Temperature Difference
= 6.4 ºF
Drop Leg Refrigerant Temperature
= 83.0 ºF
[If Drop Leg Sensor enabled]
Sub Cooling Temperature
= 18.4 ºF
[If Drop Leg Sensor enabled]
Compressor
-----------------------------------------------------
Discharge Temperature
= 120.0 ºF
Vent Line Solenoid
= Off
Oil Sump
-----------------------------------------------------
Oil Pump Run Output
= Off
Sump Oil Pressure (LOP)
= 75.8 Psig
Pump Oil Pressure (HOP)
= 76.6 Psig
Oil Pressure
= 0.0 Psid
Oil Sump Temperature
= 150.0 ºF
[Skip the following section if Hot Gas Bypass is not enabled]
Hot Gas
-----------------------------------------------------
Valve Position
= 0 %
Pre-Rotation Vanes Position
= 0 %
FIGURE 47 -
SAMPLE PRINTOUT (HISTORY)