WT-ROUTER Router Installation Instructions
4
Technical Specifications
Table 1: WT-ROUTER BACnet Object List (for WT-BAC-IP 1.3.5)
Register
Number
Point Name
Description
BACnet
Object
Type
201
Hop_Count
The number of hops through which the device’s data is routed to reach the
MeshGate; 65535 indicates that the device is offline.
AI
202
1st_Hop_ID_H
High byte of the device ID of the first hop node.
AI
1st_Hop_ID_L
Low byte of the device ID of the first hop node.
AI
204
RSSI
High byte indicates radio received signal strength (RSSI) (signed 8 bit for
Modbus register; BACnet object shows actual value).
AI
Batt_Voltage
Low byte indicates the battery voltage level in VDC multiplied by 10 (BACnet
object shows actual value).
AI
224
RF_Channel
Radio channel number used by the device.
AV
510
Dev_Type
The integer value that identifies the device type in the wireless network; for use
by the MeshGate, not customer applications.
AI
WT-ROUTER Router
Power Requirements
External DC Supply:
5 to 30 VDC from the power adaptor (included with the router)
Minimum Supply Voltage:
3.1 VDC
Wireless Band
Direct-sequence, spread-spectrum, 2.4 GHz ISM band
Operating Frequency Range
2,405 to 2,475 MHz
Channels
Quantity:
15
Spacing:
5 MHz
Transmissions
Power:
18 dBm maximum
Rate:
250 Kbits per second
Ambient Conditions
Operating:
14 to 131°F (-10 to 55°C), 5 to 95% RH, noncondensing
Storage:
-
40 to 185°F (
-
40 to 85°C), 5 to 95% RH, noncondensing
Materials
Gray ABS plastic housing
Compliance
United States:
Transmission Complies with FCC Part 15.247 Regulations for Low Power Unlicensed
Transmitters
Transmitter FCC Identification: HSW-Z2430HPA
RoHS compliant (EU Directive)
Canada:
Industry Canada IC: 4492A-Z2430HPA
Shipping Weight
0.41 lb (0.19 kg)
The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or
misuse of its products.
European Single Point of Contact:
NA/SA Single Point of Contact:
APAC Single Point of Contact:
JOHNSON CONTROLS
WESTENDHOF 3
45143 ESSEN
GERMANY
JOHNSON CONTROLS
507 E MICHIGAN ST
MILWAUKEE WI 53202
USA
JOHNSON CONTROLS
C/O CONTROLS PRODUCT
MANAGEMENT
NO. 22 BLOCK D NEW DISTRICT
WUXI JIANGSU PROVINCE 214142
CHINA