Technical Specifications    

Table 1:  WT-ROUTER BACnet Object List (for WT-BAC-IP 1.3.5)

Register 
Number

Point Name

Description

BACnet 
Object 
Type

201

Hop_Count

The number of hops through which the device’s data is routed to reach the 
MeshGate; 65535 indicates that the device is offline.

AI

202

1st_Hop_ID_H

High byte of the device ID of the first hop node.

AI

1st_Hop_ID_L

Low byte of the device ID of the first hop node.

AI

204

RSSI

High byte indicates radio received signal strength (RSSI) (signed 8 bit for 
Modbus register; BACnet object shows actual value).

AI

Batt_Voltage

Low byte indicates the battery voltage level in VDC multiplied by 10 (BACnet 
object shows actual value).

AI

224

RF_Channel

Radio channel number used by the device.

AV

510

Dev_Type

The integer value that identifies the device type in the wireless network; for use 
by the MeshGate, not customer applications.

AI

WT-ROUTER Router 

Power Requirements

External DC Supply:

 5 to 30 VDC from the power adaptor (included with the router)

Minimum Supply Voltage:

 3.1 VDC

Wireless Band

Direct-sequence, spread-spectrum, 2.4 GHz ISM band

Operating Frequency Range

2,405 to 2,475 MHz

Channels

Quantity:

 15

Spacing:

 5 MHz

Transmissions

Power:

 18 dBm maximum

Rate:

 250 Kbits per second

Ambient Conditions

Operating: 

14 to 131°F (-10 to 55°C), 5 to 95% RH, noncondensing

Storage:

 

-

40 to 185°F (

-

40 to 85°C), 5 to 95% RH, noncondensing

Materials

Gray ABS plastic housing

Compliance

United States:

Transmission Complies with FCC Part 15.247 Regulations for Low Power Unlicensed 
Transmitters
Transmitter FCC Identification: HSW-Z2430HPA
RoHS compliant (EU Directive)

Canada:

Industry Canada IC: 4492A-Z2430HPA

Shipping Weight

0.41 lb (0.19 kg)

The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these 
specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or 
misuse of its products.

European Single Point of Contact:

NA/SA Single Point of Contact:

APAC Single Point of Contact:

JOHNSON CONTROLS
WESTENDHOF 3
45143 ESSEN
GERMANY

JOHNSON CONTROLS
507 E MICHIGAN ST
MILWAUKEE WI 53202
USA

JOHNSON CONTROLS
C/O CONTROLS PRODUCT 
MANAGEMENT
NO. 22 BLOCK D NEW DISTRICT
WUXI JIANGSU PROVINCE 214142
CHINA

Summary of Contents for WT-ROUTER

Page 1: ...tes Canada IMPORTANT Use the WT ROUTER Router only to provide an input to equipment under normal operating conditions Where failure or malfunction of the router could lead to personal injury or property damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such as supervisory or alarm systems or s...

Page 2: ...he device the router is not user serviceable Parts Included one WT ROUTER Router one power adaptor one installation instructions sheet Mounting The WT ROUTER Router can be surface mounted using two field furnished screws Mount the unit to the surface at the two mounting hole locations on the device Figure 1 The router can also be secured to a bracket above a drop ceiling using field furnished tie ...

Page 3: ... installing the router near equipment that may interfere with the 2 4 GHz RF signal such as cordless telephones or Wi Fi access points that operate on the 2 4 GHz ISM band 2 Document the device ID and location of each router on the floor plan prior to installation The device ID sticker is located on the back of the router Note You may operate the router while it is resting on a desktop or mounted ...

Page 4: ...ge 3 1 VDC Wireless Band Direct sequence spread spectrum 2 4 GHz ISM band Operating Frequency Range 2 405 to 2 475 MHz Channels Quantity 15 Spacing 5 MHz Transmissions Power 18 dBm maximum Rate 250 Kbits per second Ambient Conditions Operating 14 to 131 F 10 to 55 C 5 to 95 RH noncondensing Storage 40 to 185 F 40 to 85 C 5 to 95 RH noncondensing Materials Gray ABS plastic housing Compliance United...

Page 5: ...Installation Instructions 5 Metasys and Johnson Controls are registered trademarks of Johnson Controls All other marks herein are the marks of their respective owners 2017 Johnson Controls Building Technologies Solutions 507 E Michigan Street Milwaukee WI 53202 ...