3. Connect the SA bus cable.

Five seconds after you applied power, the red

LED flashes to indicate the firmware revision.

For example, the LED flashing three times

during the startup process indicates firmware

revision 3.

Result

For each WRZ-7860-0 Receiver, record the following:
• the 

AREA

 and 

TRANSMITTER I.D

. DIP switch settings

• the location or identification of the controller that the

WRZ-7860-0 Receiver connects to with the SA bus cable

Use this information to adjust the DIP switch settings of

the WRZ Series Wireless Room Sensor assigned to the

WRZ-7860-0 Receiver, and to associate the room sensor

and receiver with the correct controller.

Figure 5: WRZ-7860-0 Receiver, back view

Refer to the 

WRZ-7860-0 Receiver for One-to-One Wireless

Room Sensing Systems Technical Bulletin (LIT-12011641) 

for

more information about how to determine the settings for

the 

AREA

 and 

TRANSMITTER I.D.

 DIP switches for a WRZ

Series Wireless Room Sensor and a WRZ-7860 Receiver.

Troubleshooting

Use the status LEDs illustrated in Figure 1 with the

information in the following table to troubleshoot the

WRZ-7860-0 Receiver.

Table 2: Status LEDs

Name

Color

Normal

Description

Flickering = SA bus

activity

SA bus

Green Flickering

Off steady = no SA

bus activity
Green = good

room sensor

battery

1 blink = marginal

RF signal strength

2 blinks = good RF

signal strength

3 blinks = excellent

RF signal strength

RF

wireless

signal

strength

and

power

status

Green

or red

bi-color

1

Green – On,

blinks signal

strength every

60 seconds

1

Red = weak room

sensor battery

1

Pressing the occupancy override button on the associated

WRZ Series Wireless Room Sensor causes the RF LED on the

WRZ-7860-0 Receiver to blink.

Repair information

If The WRZ-7860-0 Receiver fails to operate in its

specifications, replace the unit. For a replacement

receiver, contact the nearest Johnson Controls

representative.

Ordering information

To order a WRZ Receiver, contact the nearest Johnson

Controls representative. Specify the required product

code number from Table 3 and accessories from Table 4.

WRZ-7860-0 Receiver for One-to-One Wireless Room Sensing Systems Installation Guide

4

Summary of Contents for WRZ-7860-0

Page 1: ... malfunction of the receiver could lead to personal injury or property damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of or protect against failure or malfunction of the WRZ 7860 Receiver Important Le WRZ 7860...

Page 2: ...s as direct as possible Line of sight is preferred but not required as long as the path is not blocked by large metal objects Mount the receiver so that the antenna symbol on the cover near the LEDs is in a vertical orientation up or down The antenna symbol indicates the approximate location of the receiver s internal onboard antenna Figure 2 Correct mounting orientation If you mount the receiver ...

Page 3: ...se with screws Wiring The WRZ 7860 0 Receiver has a modular jack on the edge of the enclosure opposite the side with the tamper resistant set screw This modular jack for the SA bus requires a straight through one to one connection cable not a crossover to the SENSOR jack on a Controller Important Configure the field controller as if connected to a wired network sensor Configuring the field control...

Page 4: ... Troubleshooting Use the status LEDs illustrated in Figure 1 with the information in the following table to troubleshoot the WRZ 7860 0 Receiver Table 2 Status LEDs Name Color Normal Description Flickering SA bus activity SA bus Green Flickering Off steady no SA bus activity Green good room sensor battery 1 blink marginal RF signal strength 2 blinks good RF signal strength 3 blinks excellent RF si...

Page 5: ...less Room Sensor temperature LCD display F C manual occupancy override button button setpoint adjustment ZFR183x compatible WRZ THB0000 0 Temperature Humidity Sensor with display Warmer Cooler setpoint dial adjustment or scaled setpoint dial adjustment 55 F to 85 F 13 C to 29 C F C button RH button and manual occupancy override button WRZ THN0000 0 Wireless Room Temperature and Humidity Sensor wit...

Page 6: ...ne RJ 12 Port for SA Communication Bus output sensed zone temperature and humidity temperature setpoint and occupancy override data Temperature sensor accuracy 1 0 F 0 6 C over the range of 55 F to 85 F 13 C to 29 C 1 5 F 0 9 C over the range of 32 F to 55 F 0 C to 13 C and 85 F to 110 F 29 C to 43 C Temperature sensor type Internal 10k ohm Negative Temperature Coefficient NTC thermistor Humidity ...

Page 7: ...s product constitutes an agreement to such terms Patents Patents https jcipat com Single point of contact APAC Europe NA SA JOHNSON CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 32 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA Contact information Contact your local branch offi...

Page 8: ... 2020 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www johnsoncontrols com ...

Reviews: