FORM 145.18-EG2 (317)
12
JOHNSON CONTROLS
Performance Data - EC Motor
TABLE 4 -
VPCS09 - EC MOTOR (ECM)- COOLING AIRFLOW: 375 CFM AND HEATING AIRFLOW: 400 CFM
EWT
GPM
WPD
COOLING
HEATING
PSI
FT
TC
SC
SHR
KW
HR
EER
HTG
KW
HE
LAT
COP
20
3.2
5.7
13.1
5.8
0.55
4.2
81.4
3.1
30
1.6
1.9
4.5
12.7
9.3
0.73
0.34
13.6
37.7
7.0
0.59
5.3
84.1
3.5
2.4
3.4
7.9
12.9
9.4
0.73
0.34
13.8
38.6
7.3
0.59
5.6
84.9
3.6
3.2
5.5
12.7
13.0
9.5
0.73
0.33
13.9
39.4
7.5
0.60
5.8
85.4
3.7
40
1.6
1.9
4.3
12.2
9.1
0.75
0.38
13.2
32.2
9.0
0.63
7.2
88.8
4.2
2.4
3.3
7.6
12.3
9.1
0.74
0.37
13.3
33.8
9.0
0.63
7.2
88.9
4.2
3.2
5.3
12.2
12.4
9.2
0.74
0.36
13.4
34.5
9.2
0.63
7.3
89.2
4.2
50
1.6
1.8
4.1
11.6
8.8
0.76
0.43
12.8
27.1
9.7
0.65
7.8
90.4
4.4
2.4
3.1
7.2
11.8
8.9
0.76
0.41
12.9
28.7
10.0
0.66
8.1
91.2
4.5
3.2
5.1
11.7
11.8
8.9
0.75
0.40
12.9
29.4
10.3
0.66
8.3
91.8
4.5
60
1.6
1.7
3.9
11.1
8.6
0.78
0.49
12.5
22.7
10.9
0.67
8.9
93.3
4.8
2.4
3.0
6.9
11.2
8.6
0.77
0.47
12.6
23.9
11.4
0.67
9.4
94.4
5.0
3.2
4.8
11.1
11.3
8.7
0.77
0.46
12.6
24.4
11.8
0.67
9.8
95.2
5.2
70
1.6
1.6
3.7
10.6
8.4
0.79
0.56
12.2
19.0
12.3
0.67
10.3
96.5
5.4
2.4
2.9
6.6
10.7
8.5
0.79
0.54
12.3
19.9
12.9
0.67
10.9
97.9
5.6
3.2
4.6
10.6
10.8
8.4
0.78
0.53
12.3
20.4
13.4
0.68
11.4
99.0
5.8
80
1.6
1.5
3.6
10.1
8.2
0.81
0.63
11.9
16.1
13.8
0.69
11.7
99.9
5.9
2.4
2.7
6.3
10.2
8.3
0.81
0.61
12.0
16.8
14.5
0.70
12.4
101.6
6.1
3.2
4.4
10.1
10.3
8.2
0.80
0.60
12.0
17.2
15.0
0.72
12.9
102.8
6.2
90
1.6
1.5
3.4
9.6
8.0
0.84
0.70
11.7
13.7
15.3
0.72
13.1
103.4
6.2
2.4
2.6
6.0
9.7
8.0
0.83
0.68
11.7
14.3
16.1
0.73
13.9
105.2
6.5
3.2
4.2
9.6
9.8
8.0
0.82
0.67
11.8
14.6
16.7
0.75
14.5
106.6
6.6
100
1.6
1.4
3.2
9.0
7.8
0.86
0.78
11.4
11.6
2.4
2.5
5.7
9.2
7.8
0.85
0.76
11.5
12.1
3.2
4.0
9.1
9.2
7.8
0.85
0.75
11.5
12.4
110
1.6
1.3
3.0
8.5
7.4
0.88
0.86
11.1
9.8
2.4
2.3
5.3
8.6
7.5
0.87
0.84
11.2
10.2
3.2
3.7
8.6
8.7
7.5
0.86
0.83
11.2
10.4
• Cooling Performance is tabulated at 80.6 °F DB and 66.2 °F WB entering air. Heating performance tabulated at 68 °F EAT
• Tabulated data does not include AHRI/ISO corrections for fan and pump power.
• All capacities are expressed in MBH.
• Insulated water circuit is recommended for operation below 60 °F EWT.
• Operation below 60 °F EWT is based on 15% methanol.
• See performance correction tables for conditions beyond what is listed.
• Extrapolation is not permissible.
• Shaded areas indicate conditions where operation is not recommended.
• All performance is based on 208V on 208-230V units.
Summary of Contents for VPCS SERIES
Page 31: ...FORM 145 18 EG2 317 JOHNSON CONTROLS 31 Hose Kits NPSH Water Connection LD18126 LD18127 ...
Page 32: ...FORM 145 18 EG2 317 32 JOHNSON CONTROLS Hose Kits JIC Water Connection LD19518 LD19519 ...
Page 35: ...FORM 145 18 EG2 317 JOHNSON CONTROLS 35 REAR RISER ...
Page 36: ...FORM 145 18 EG2 317 36 JOHNSON CONTROLS Wiring Diagram ...