background image

Table 8: Wireless field bus device address

Device address Address description

4 to 127

(Switch 128 ON)

Valid for MSTP Master field controllers on

wireless FC Buses only

.

Note: 

Do 

not

 connect a 

Metasys

 controller

with these device addresses to an active

wired

 SA or FC Bus. When a controller

with one of these device address is

connected to a wired field bus, the field

bus is rendered inoperable until the

controller is disconnected or Switch 128 is

set to OFF.

Setting the N2 Controller address to
be greater than 127

N2-configured controllers support the full range

of possible N2 device addresses provided by the

N2 protocol standard (1–254). However, these

controllers require special configuration for

addresses above 127.

Use the following instructions for controllers greater

than 127.

Note: 

This special configuration is required

because controller addresses above 127 were

originally intended for use with the Wireless

Field Bus system.

Note: 

Prior to performing this procedure,

be sure the controller has been converted

from BACnet to N2 protocol first. Refer to the

Modernization Guide for Legacy N2 Controllers

(LIT-12012005)

 for more information.

1. Disconnect the 24 VAC supply from the

controller.

2. Remove the FC Bus connector from the

controller.

3. Set the address switch set to the desired N2

address.

4. Set the address switch segment labeled 128 to

OFF.

5. Reconnect the 24 VAC supply to the controller.

6. Using an SA bus connection, download the

firmware and controller application file. The

download process asks to confirm switching the

communication protocol to N2.

7. Click 

OK

.

8. After the download is finished, disconnect the

24 VAC supply to the controller.

9. Set the address switch segment labeled 128 to

ON.

10. Reattach the FC Bus connector to the controller.

11. Reconnect the 24 VAC supply to the controller.

Setting the EOL switch

Each field controller has an EOL switch, which,

when set to ON (up), sets the field controller as

a terminating device on the bus. See  for the EOL

switch location on the field controller. The default

EOL switch position is OFF (down). The amber EOL

LED illuminates to show the EOL is active.

Figure 10: EOL switch positions

To set the EOL switch on a field controller:

1.  Determine the physical location of the

controller on the SA or FC Bus.

2.  Determine if the controller must be set as a

terminating device on the bus.

Note: 

The EOL termination rules for

SA Buses and FC Buses are different.

Refer to the 

MSTP Communications Bus

Technical Bulletin (LIT-12011034) 

for detailed

information regarding EOL termination

rules and EOL switch settings on SA and FC

Buses.

3.  If the controller is a terminating device on

the FC Bus, set the EOL switch to ON. If the

controller is not a terminating device on the

bus, set the EOL switch to OFF.

Note: 

When the EOL switch is set to ON,

the LED light on the face of the controller

is illuminated.

VMA1617 and VMA1632 VAV Controllers Installation Guide

17

Summary of Contents for VMA1617

Page 1: ...ning support and include tips for efficient and safe replacement Refer to the N2 Compatibility Options chapter of the Controller Tool Help LIT 12011147 for information about mapping N2 Objects in cont...

Page 2: ...25 mm 1 in screw Materials and special tools needed Several 6 mm 1 4 in female spade terminals for input and output wiring and crimping tool for spade mounted terminal blocks Small straight blade scr...

Page 3: ...pler Bolt see Mounting for information on setting the coupler bolt 9 Universal Input Voltage Analog Input 0 10 VDC Resistive Analog Inputs 0 600k ohm 0 2k Potentiometer RTD 1k Nickel 1k Platinum or A9...

Page 4: ...ng the sheet metal screw from the original installation preferred option On panel or enclosure mount applications observe these additional guidelines Do not install the controller in an airtight enclo...

Page 5: ...y installed on VAV boxes The models have either a round shaft up to 13 mm in diameter or a 10 mm square shaft Tighten the square coupler bolt to the shaft using an 8 mm 5 16 in wrench or 10 mm 3 8 in...

Page 6: ...For detailed information on configuring and wiring a SA Bus refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 VMA terminals and bus ports See for input and output terminal and bus...

Page 7: ...Wiring Important Exercise caution while rewiring the power plug when replacing a VMA1610 or VMA1620 controller with a VMA1617 or VMA1632 controller The supply power terminal on a new VMA is a two posi...

Page 8: ...to the appropriate device address Also activate the EOL switch if necessary 5 Connect the controller to 24 VAC Class 2 power Note If you are using the VMA1617 or VMA1632 controller with the Wireless...

Page 9: ...tive Temperature Coefficient NTC Sensor 10K Type L 10K Johnson Controls Type II is equivalent to Type L or 2 252K Type II See Guideline A in Table 3 INn Binary Input Dry Contact Maintained Mode 1 seco...

Page 10: ...e Size Gauge and Type Maximum Cable Length and Type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 297 m 975 ft twisted w...

Page 11: ...sted wire B 24 AWG stranded copper 107 m 350 ft twisted wire 61 m 200 ft twisted wire 100 mV maximum voltage drop Depending on the cable length and the connected input or output device you may have to...

Page 12: ...er VAV Balancing Tool One to One Wireless Receiver Network Sensor 24 AWG 4 pair CAT 5 Cable 30 5 m 100 ft HOT 24 VAC Power Supply Hot Supplies 20 30 VAC Nominal 24 VAC 24 COM 24 VAC Power Supply Commo...

Page 13: ...gures in this section for the applicable termination diagrams Table 6 Termination details Type of field device Type of Input Output Termination diagrams Voltage Input External Source UI Voltage Input...

Page 14: ...External Source CO 24 VAC Triac Output Switch Low External Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low External Source CO Note Applies to CO4 and CO5 Analog Output...

Page 15: ...damaging the controller Setting the device address Metasys field controllers are master devices on BACnet MSTP SA or FC Buses Before operating field controllers on a bus you must set a valid and uniqu...

Page 16: ...ZFR182x Pro Series Wireless Field Bus System Technical Bulletin LIT 12012356 or the ZFR1800 Series Wireless Field Bus System Technical Bulletin LIT 12011295 for more information on device addresses in...

Page 17: ...F 5 Reconnect the 24 VAC supply to the controller 6 Using an SA bus connection download the firmware and controller application file The download process asks to confirm switching the communication pr...

Page 18: ...efer to the Controller Tool Help LIT 12011147 and Controller Provisioning with Tools LIT 12013247 for detailed information about commissioning field controllers Note The MAP Gateway serves as a replac...

Page 19: ...must be no short circuit Note Some installations require the Secondary of the Transformer to be Earth Grounded If this is the case verify that the Earth Ground connection is valid and not shared betw...

Page 20: ...Gateway Refer to the Mobile Access Portal Gateway Catalog Page LIT 1900869 to identify the appropriate product for your region MS DIS1710 0 Local Controller Display MS BTCVTCBL 700 Cable Replacement S...

Page 21: ...F 1000 326 Flexible Tubing Extension with Barbed Fitting for VMA1617 and VMA1632 35 56 cm 14 in Length Bulk Pack of 20 MS VMAACT 701 VMA Actuator Assembly Gearbox Replacement Kit TE730 29C 0 Sensor wi...

Page 22: ...or N2 DIP switch set valid field controller device addresses 1 254 Communications Bus RS 485 selectable between BACnet MSTP or N2 FC Bus 0 6 mm 22 AWG standard 3 wire twisted shielded cable recommende...

Page 23: ...Testing Laboratories BTL Protocol Revision 7 Listed BACnet Application Specific Controller B ASC The performance specifications are nominal and conform to acceptable industry standard For application...

Page 24: ...2019 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www johnsoncontrols com...

Reviews: