Johnson Controls VMA1200 Series Mounting And Wiring Instruction Download Page 1

Technical Bulletin

Issue Date

July 1, 2003

© 2003 Johnson Controls, Inc.

www.johnsoncontrols.com

Code No. LIT-1162360

M-Tool Release 5.3

Mounting and Wiring VMA1200 Series Controllers

Mounting and Wiring VMA1200 Series Controllers............................2

Introduction......................................................................................................... 2

Key Concepts...................................................................................................... 3

VMA Position and Orientation ........................................................................................... 3

Determine and Set Damper Polarity ................................................................................. 3

Wiring and Cabling Precautions........................................................................................ 4

VMA Internal Schematic Diagram ..................................................................................... 6

Phone Jack Polarization.................................................................................................... 8

Detailed Procedures......................................................................................... 10

Preparing the VMA for Mounting..................................................................................... 10

Mounting the VMA........................................................................................................... 11

Setting the Damper Position ........................................................................................... 12

Wiring the VMA ............................................................................................................... 14

Connecting the L

ON

W

ORKS

 Network Bus........................................................................ 15

Summary of Contents for VMA1200 Series

Page 1: ...Wiring VMA1200 Series Controllers 2 Introduction 2 Key Concepts 3 VMA Position and Orientation 3 Determine and Set Damper Polarity 3 Wiring and Cabling Precautions 4 VMA Internal Schematic Diagram 6...

Page 2: ...mbly VMA which is a controller actuator pressure sensor mounts on the Variable Air Volume VAV terminal box and fastens to the damper shaft Instructions for wiring the VMA and its accessory devices are...

Page 3: ...VMA so that it has adequate clearance for future servicing and is protected from moisture and corrosive fumes Determine and Set Damper Polarity Damper polarity is established upon installation Incorr...

Page 4: ...d destroys the VMA triac Read these precautions before touching the terminals or wiring the VMA and its accessories Make all wiring connections in accordance with the National Electrical Code NEC and...

Page 5: ...put Output wiring where convenient The following are additional general wiring considerations The VMA includes an isolated LONWORKS Network Bus isolated binary outputs and isolated 24 VAC See VMA Inte...

Page 6: ...ed Power Supply 2 Earth Ground Connection 3 Airflow and High Temperature Safety Switches 4 Isolated Triacs and Power Wiring for the Airflow and High Temperature Safety Switches 5 Isolated LONWORKS Net...

Page 7: ...han 150 VAC 1 2 XFR Synchronous Motor Actuator COM Water Valve 1 2 4 3 In LONWORKS Network Bus VMA 15V 5V Triacs COM COM AO 15 23 14 OPTO 24 VAC BCOM CablePRO or CVTPRO Laptop R R Reheat BO 3 Reheat B...

Page 8: ...own cable refer to Fabricating Your Own Interconnection Cable in Appendix A Reference Information located in the Variable Air Volume Modular Assembly VMA 1200 Series Overview and Engineering Guidelin...

Page 9: ...VDC 6 Power Common and Zone Bus Common and Manual Override Common and LED Common 7 Zone Bus 8 LED and Manual Override Manual Override for Temporary Occupied Mode is selected using DIP switches for ei...

Page 10: ...ional Note The VMA requires a damper shaft protrusion of at least 44 mm 1 3 4 in from the VMA mounting surface 3 Ensure the VMA installation site meets the following environmental requirements The VMA...

Page 11: ...crew provided into the VMA mounting slot using a power screwdriver and socket with 4 in extension Alternate mounting 1 Perform Step 1 as shown previously 2 Use a punch to mark the position of the shou...

Page 12: ...elease lever down and position the actuator collar against its internal stop corresponding to the fully closed position This provides a hard stop for this position The hard stop for the open position...

Page 13: ...A coupler by hand to ensure that the damper can rotate from full closed to full open positions without binding 6 Plug or seal the end of a hollow damper shaft to stop cold duct air from affecting the...

Page 14: ...2 or 3 position screw terminals or phone cable is to be used See the Variable Air Volume Modular Assembly VMA 1200 Series Overview and Engineering Guidelines Technical Bulletin LIT 1162350 for screw...

Page 15: ...they are internal and no wiring is required Connecting the LONWORKS Network Bus A connection between the VMA and the Network Control Module NCM is required if the VMA is to communicate with the Metas...

Page 16: ...Shield LON A LON B LON A LON B NCMConnect To Next L W Compatible Device or NCM ON ORKS Figure 9 Connecting the VMA to an NCM 2 Apply power Locate and observe the VMA LEDs See Tables 7 and 8 for detail...

Page 17: ...ED SHLD Description LED Color Included on VMA1220 Only Safety Isolation Transformer in Europe Earth Ground COM CW End Stop 3 Controller operating properly The network table is not configured Use Comm...

Page 18: ...en received Table 8 Running LED Color Name State Description Blinking Application is running normally LED blinks at one second interval On Steady Application is not running Try the following 1 Check t...