Johnson Controls VMA1200 Series Mounting And Wiring Instruction Download Page 3

Mounting and Wiring VMA1200 Series Controllers Technical Bulletin

3

Key Concepts

 

VMA Position and Orientation

Note:

 

Extra mounting brackets, linkage, or couplers are not

required for standard mounting.

 

Consider the following when positioning and orienting the VMA:

 

Mount the VMA on a vertical and flat surface where it functions
best, such as the side of the VAV box.

 

Route the tubing so a portion of it is lower than the pressure sensor
or loop the tubing. This creates a moisture trap that prevents any
condensation from entering the sensor.

 

Do not make any sharp bends in the tubing. This could collapse the
tube and block the pressure path.

 

Ensure that wiring terminals and service pin are accessible.

 

Make sure the 

VMA1200 Installation Bulletin (Part No. 24-9310-5)

is available for properly identifying terminals.

 

Locate the VMA so that it has adequate clearance for future
servicing and is protected from moisture and corrosive fumes.

 

Determine and Set Damper Polarity

Damper polarity is established upon installation. Incorrect damper
positions in a zone easily result in misdiagnosis of readings, resulting
in unnecessary repetition of setup and diagnostics.
Many dampers seal properly only when closed in the rotation direction
specified by the manufacturer. To simplify maintenance, use the same
direction to close on all boxes of the same type.

 

To determine whether the damper is closed Clockwise (CW) or
Counterclockwise (CCW):

 

Visually verify which direction opens the damper before duct work
is completed and note the information for future reference.

 

Look up the manufacturer’s damper model specifications.

 

Once there is airflow in the zone, use a commissioning tool to
command the actuator to 100%. If this causes the flow to decrease,
it is an indication that the Damper Polarity configuration property
must be reversed from its current setting.

Summary of Contents for VMA1200 Series

Page 1: ...Wiring VMA1200 Series Controllers 2 Introduction 2 Key Concepts 3 VMA Position and Orientation 3 Determine and Set Damper Polarity 3 Wiring and Cabling Precautions 4 VMA Internal Schematic Diagram 6...

Page 2: ...mbly VMA which is a controller actuator pressure sensor mounts on the Variable Air Volume VAV terminal box and fastens to the damper shaft Instructions for wiring the VMA and its accessory devices are...

Page 3: ...VMA so that it has adequate clearance for future servicing and is protected from moisture and corrosive fumes Determine and Set Damper Polarity Damper polarity is established upon installation Incorr...

Page 4: ...d destroys the VMA triac Read these precautions before touching the terminals or wiring the VMA and its accessories Make all wiring connections in accordance with the National Electrical Code NEC and...

Page 5: ...put Output wiring where convenient The following are additional general wiring considerations The VMA includes an isolated LONWORKS Network Bus isolated binary outputs and isolated 24 VAC See VMA Inte...

Page 6: ...ed Power Supply 2 Earth Ground Connection 3 Airflow and High Temperature Safety Switches 4 Isolated Triacs and Power Wiring for the Airflow and High Temperature Safety Switches 5 Isolated LONWORKS Net...

Page 7: ...han 150 VAC 1 2 XFR Synchronous Motor Actuator COM Water Valve 1 2 4 3 In LONWORKS Network Bus VMA 15V 5V Triacs COM COM AO 15 23 14 OPTO 24 VAC BCOM CablePRO or CVTPRO Laptop R R Reheat BO 3 Reheat B...

Page 8: ...own cable refer to Fabricating Your Own Interconnection Cable in Appendix A Reference Information located in the Variable Air Volume Modular Assembly VMA 1200 Series Overview and Engineering Guidelin...

Page 9: ...VDC 6 Power Common and Zone Bus Common and Manual Override Common and LED Common 7 Zone Bus 8 LED and Manual Override Manual Override for Temporary Occupied Mode is selected using DIP switches for ei...

Page 10: ...ional Note The VMA requires a damper shaft protrusion of at least 44 mm 1 3 4 in from the VMA mounting surface 3 Ensure the VMA installation site meets the following environmental requirements The VMA...

Page 11: ...crew provided into the VMA mounting slot using a power screwdriver and socket with 4 in extension Alternate mounting 1 Perform Step 1 as shown previously 2 Use a punch to mark the position of the shou...

Page 12: ...elease lever down and position the actuator collar against its internal stop corresponding to the fully closed position This provides a hard stop for this position The hard stop for the open position...

Page 13: ...A coupler by hand to ensure that the damper can rotate from full closed to full open positions without binding 6 Plug or seal the end of a hollow damper shaft to stop cold duct air from affecting the...

Page 14: ...2 or 3 position screw terminals or phone cable is to be used See the Variable Air Volume Modular Assembly VMA 1200 Series Overview and Engineering Guidelines Technical Bulletin LIT 1162350 for screw...

Page 15: ...they are internal and no wiring is required Connecting the LONWORKS Network Bus A connection between the VMA and the Network Control Module NCM is required if the VMA is to communicate with the Metas...

Page 16: ...Shield LON A LON B LON A LON B NCMConnect To Next L W Compatible Device or NCM ON ORKS Figure 9 Connecting the VMA to an NCM 2 Apply power Locate and observe the VMA LEDs See Tables 7 and 8 for detail...

Page 17: ...ED SHLD Description LED Color Included on VMA1220 Only Safety Isolation Transformer in Europe Earth Ground COM CW End Stop 3 Controller operating properly The network table is not configured Use Comm...

Page 18: ...en received Table 8 Running LED Color Name State Description Blinking Application is running normally LED blinks at one second interval On Steady Application is not running Try the following 1 Check t...

Reviews: