![Johnson Controls VB09 Installation, Operation And Maintenance Manual Download Page 26](http://html1.mh-extra.com/html/johnson-controls/vb09/vb09_installation-operation-and-maintenance-manual_2024200026.webp)
26
FORM 145.18-IOM1
ISSUE DATE: 8/30/2018
SECTION 1 - INSTALLATION
TABLE 5 -
UNIT SUPPLY OPENING SIZES
HORIZONTAL OPENINGS
TOP OPENING
SINGLE HORIZONTAL
DOUBLE HORIZONTAL
TRIPLE
HORIZONTAL
MODEL
NO TOP
OPENING
TOP OPENING
NO TOP
OPENING
TOP OPENING
NO TOP
OPENING
9
14W x 12H
14W x 6H
14W x 8H
Not Available
Not Available
12 x 8
12
14W x 14H
14W x 6H
14W x 10H
Not Available
Not Available
12 x 8
15
16W x 14H
14W x 6H
14W x 10H
Not Available
14W x 8H
14 x 12
18
Not Available
14W x 6H
14W x 12H
14W x 6H
14W x 10H
14 x 12
24
Not Available
14W x 10H
16W x 14H
14W x 6H
14W x 10H
14 x 12
30
Not Available
14W x 6H
20W x 14H
14W x 6H
16W x 12H
18 x 16
36
Not Available
14W x 10H
Not Available
14W x 6H
16W x 14H
18 x 16
NOTES:
1.
Unit mounted supply grilles are supplied as double-deflection type.
2.
Grilles for unequal airflow applications (for example, unit mounted plus ducted supply) are provided with integral opposed blade dampers.
3.
All grilles are supplied in standard appliance white painted finish.
4.
Grilles are shipped loose for field installation upon completion of cabinet/ductwork/drywall installation.
5. Top opening size does not change. When combined with any other discharge arrangement, it is included in determining horizontal opening
grille size.
6. Openings marked Not Available result in face velocities outside the recommended 300–500 FPM range.
7. Hi-static blower option or single horizontal discharge openings with unit mounted supply grille are not recommended.
TABLE 6 -
UNIT SUPPLY FACE VELOCITY (FPM)
MODEL
HORIZONTAL OPENINGS
TOP OPENING
SINGLE HORIZONTAL
DOUBLE HORIZONTAL
TRIPLE
HORIZONTAL
NO TOP
OPENING
TOP OPENING
NO TOP
OPENING
TOP OPENING
NO TOP
OPENING
9
291
272
219
Not Available
Not Available
510
12
316
344
221
Not Available
Not Available
645
15
354
314
283
Not Available
236
471
18
Not Available
391
294
294
235
587
24
Not Available
397
273
364
291
729
30
Not Available
416
276
339
269
538
36
Not Available
410
Not Available
385
261
610
NOTES:
1. Tabulated face velocities do not account for supply grille free area factor. Face velocities at supply grille are higher depending on grille type.
2. Face velocities are based on the nominal rated CFM and feet per minute (FPM).
3. Face velocities are calculated by taking the average across all openings. Tabulated top opening face velocity is only for units with single
top opening and no horizontal openings.