Johnson Controls VAV1717 Installation Manual Download Page 5

Callout

Description and references

13

TSTAT modular port: RJ-45 8-pin modular jack, see 

TSTAT port

14

Captive spacer and screw

15

Alignment marks

16

SA bus modular port: RJ-12 6-pin modular jack, see 

SA bus port

17

LED status indicators, see 

LED states

Mounting the controller

About this task:  

Observe the following guidelines when you mount the

VAV controller:

Note: 

When the air supply to the VAV box is below

10°C (50°F), ensure that condensation on the VAV

box, particularly on the damper shaft, does not enter

the VAV controller.

• Ensure that the mounting surface can support the

controller and any user-supplied enclosure and

electronics.

• Mount the controller on a hard, even surface whenever

possible.

• Use shims or washers to mount the controller securely

and evenly on the mounting surface.

• Mount the controller in an area that is free of corrosive

vapors and where the ambient conditions match the

conditions specified in the 

Technical specifications

section.

• Provide at least 50 mm (2 in.) on the top, bottom,

sides, and front of the controller for cable and wire

connections and adequate ventilation through the

controller.

• Mount the controller vertically above the damper shaft

to allow any shaft condensation to fall away from the

controller.

• Do not mount the controller in areas where

electromagnetic emissions from other devices or wiring

can interfere with controller communication.

• Avoid mounting the controller on surfaces with

excessive vibration.

• When this installation replaces another controller,

plug the unused open hole in the duct work from the

original controller mounting. To plug the hole, use the

sheet metal screw from the original installation.

For panel mounting or enclosure mounting, observe these

additional guidelines:
• Do not install the controller in an airtight enclosure.

• Mount the controller so that the enclosure walls do

not obstruct cover removal or ventilation through the

controller.

• Mount the controller so that the power transformer

and other devices do not radiate excessive heat to the

controller.

To mount the controller, complete the following steps:

1. Set all the switches on the controller to their correct

values.

2. Place the controller in the correct mounting

position on the damper shaft so that the wiring

connections are easily accessible. Ensure that

the controller base is parallel to the VAV box and

perpendicular to the damper shaft. If needed, use a

spacer to offset tipping of the controller caused by

the shaft bushings.

Note: 

Use the alignment marks to center the

captive spacer to ensure sufficient movement

in either direction.

3. Secure the self-drilling No. 10 screw through the

captive spacer with a power screwdriver and 100

mm (4 in.) extension socket. Alternatively, you can

use a punch to mark the position of the shoulder

washer, and then drill a hole into the VAV box with

a 3.5 mm (9/64 in.) drill bit. Insert the mounting

screw and tighten it against the spacer.

Important: 

Do not overtighten the screw,

or the threads may strip. If you mount the

controller to the VAV box, ensure that the

screws do not interfere with damper blade

movement.

4. Locate the damper position. Use the typical

marking on the end of the damper shaft as shown

in the following figure.

Figure 3: Typical damper end shaft markings

5. Note the direction, clockwise (CW) or

counterclockwise (CCW), required to close the

damper. Grasp the damper shaft firmly with pliers,

and choose one of the following options:

- For 90° boxes, manually close the damper.

- For 45° or 60° boxes, manually open the

damper.

6. Push down and hold the 

Manual Override

 button

(see 

Physical features

) and turn the controller

coupler until it contacts the mechanical end-stop at

either the full-closed (90° boxes) or full-open (45°

and 60° boxes) position.

7. If the damper for a 90° box closes CCW, rotate

the coupler to the CCW mechanical limit. If the

damper for a 90° box closes CW, rotate the coupler

to the CW mechanical limit. The open end-stop is

automatically set for 90° boxes.

VAV1717 and VAV1732 VAV Controllers Installation Guide

5

Summary of Contents for VAV1717

Page 1: ...ls provide a cost effective upgrade and modernization path for customers with existing N2 controllers For installation and commissioning support and tips for efficient and safe replacement refer to th...

Page 2: ...Universal inputs Voltage analog input 0 VDC to 10 VDC Resistive analog input 0 ohm to 600k ohm qualified sensors 0 ohm to 2k ohm potentiometer RTD 1k Nickel 1k Platinum or A99B Si NTC 10k Type L 10k...

Page 3: ...Callout Description and references 15 SA bus modular port RJ 12 6 pin modular jack see SA bus port 16 LED status indicators see LED states VAV1717 and VAV1732 VAV Controllers Installation Guide 3...

Page 4: ...n see Mounting the controller 7 Controller coupler see Mounting the controller 8 Coupler bolt see Mounting the controller 9 Universal inputs Voltage analog input 0 VDC to 10 VDC Resistive analog input...

Page 5: ...ontroller Mount the controller so that the power transformer and other devices do not radiate excessive heat to the controller To mount the controller complete the following steps 1 Set all the switch...

Page 6: ...N Risk of Electric Shock Disconnect the power supply before making electrical connections to avoid electric shock Important Do not connect supply power to the controller before you finish wiring and b...

Page 7: ...on the SA bus 2 Daisy chained device on the SA bus 3 Cable shield connection 4 Connection to another device on the SA bus TSTAT port The TSTAT port on the face of the controller is an RJ 45 8 position...

Page 8: ...ontroller does not require an earth ground connection However when you need to ground the secondary of the 24 VAC transformer make only one ground connection near the transformer See the following fig...

Page 9: ...n for all Universal IN terminals Note All Universal ICOMn terminals are isolated from all other commons Same as Universal INn OUTn Binary Output 24 VAC Triac Internal Power Sources internal 24 VAC pow...

Page 10: ...BUS SA BUS RJ 12 6 position modular port that provides communications and 15 VDC power for the following devices NS and NSA Series network sensors MAP Gateway 4 2 or later Bluetooth Commissioning Conv...

Page 11: ...tput point 1 0 mm 18 AWG stranded copper 229 m 750 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 137 m 450 ft twisted wire 0 6 mm 22 AWG stranded copper 183 m 600 ft twisted...

Page 12: ...controller Table 9 Termination diagrams Type of field device Type of input or output Termination diagrams Voltage Input External Source UI Voltage Input Internal Source UI Voltage Input Self Powered U...

Page 13: ...External Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low Externally Sourced CO Note Applies to CO4 and CO5 Analog Output Voltage CO Incremental Control to Actuator Swi...

Page 14: ...th Phone Jack Fixed Address 199 SA Bus Note The bottom jack J2 on the TE 700 and TE 6x00 Series Sensors is not usable as a zone bus or an SAB connection Network Stat with Terminals Addressable SA Bus...

Page 15: ...ock at the top of the controller see Physical features Device addresses 4 through 127 are the valid addresses for these controllers on an MS TP FC bus The DIP switch block has eight switches numbered...

Page 16: ...ch to OFF Note When the EOL switch is set to ON the EOL LED on the front of the controller is illuminated Commissioning the controller About this task To commission the controller use the Controller C...

Page 17: ...ries Fan On off heating water valve and variable speed series fan 8 On Off Series Fan Single speed series fan 8 Incr HW Reheat Var Speed Series Fan Incremental heating water valve and variable speed s...

Page 18: ...LED status indicator information for troubleshooting the controllers Note If you experience short circuits in the 24 VAC power supply causing protective devices such as breakers or fuses to trip make...

Page 19: ...nd COM Ensure that no short circuit occurs Note Some installations require the secondary of the transformer to be earth grounded If this is the case verify that the earth ground connection is valid an...

Page 20: ...BCPro Controller Firmware Package Files required for CCT TL MAP1810 0PA Portable MAP Gateway Australia China India Japan Malaysia New Zealand Singapore South Korea Thailand TL MAP1810 0PM Portable MAP...

Page 21: ...er TE730 Analog sensors with occupancy option TSTAT port NSA7000 Network sensors with occupancy option and RH display option NS7000 NS8000 Network sensors with occupancy option CO2 display option and...

Page 22: ...ded between the supervisory controller and the VAV controller SA bus 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended from the VAV controller to network sensors and other senso...

Page 23: ...ns consult the local Johnson Controls office Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products Repair information If the controller fails to oper...

Page 24: ...anty Software terms Use of the software that is in or constitutes this product or access to the cloud or hosted services applicable to this product if any is subject to applicable end user license ope...

Reviews: