
LED states
Table 13: Status LEDs and description of LED states
LED label
LED color
Normal state
Descriptions of LED states
POWER
Green
On steady
Off steady = No power
On steady = Power is supplied by primary voltage
FAULT
Red
Off steady
Blink - 2 Hz = Startup in progress, not ready for normal operation
Two blinks and then a long pause = Device on in default state
Rapid blink = SA Bus devices offline (such as netsensors)
Off steady = No faults
On steady = Device fault or no application loaded
FC BUS
Green
Blink - 2 Hz
Blink - 2 Hz = Data transmission (normal communication)
Off steady = No data transmission (auto baud in progress)
On steady = communication lost, waiting to join communication ring
SA BUS
Green
Blink - 2 Hz
Blink - 2 Hz = Data transmission (normal communication)
Off steady = No data transmission (n/a - auto baud not supported)
On steady = Communication lost, waiting to join communication ring
EOL
Amber
Off
On steady = EOL is active
Off steady = EOL is not active
Accessories
Table 14: Controller accessories (order separately)
Product code number
Description
TL-CCT-0
License enabling Controller Configuration Tool (CCT) software for one user
MS-FCP-0
License enabling Metasys Equipment Controller Firmware Package Files required for CCT
FX-FCP-0
License enabling Facility Explorer Equipment Controller Firmware Package Files required for
CCT
CH-FCP-0
License enabling BCPro Controller Firmware Package Files required for CCT
TL-MAP1810-0PA
Portable MAP Gateway - Australia, China, India, Japan, Malaysia, New Zealand, Singapore,
South Korea, Thailand
TL-MAP1810-0PM
Portable MAP Gateway - Bahrain, Egypt, Iraq, Kuwait, Oman, Pakistan, Qatar, South Africa,
UAE
TL-MAP1810-0PE
Portable MAP Gateway - Turkey
TL-MAP1810-0PS
Portable MAP Gateway - Saudi Arabia
Y64T15-0
Transformer, 120/208/240 VAC primary to 24 VAC secondary, 92 VA, foot mount, 72.2 cm (30
in.) primary leads and 76.2 cm (30 in.) secondary leads, Class 2
Y65A13-0
Transformer, 120 VAC primary to 24 VAC secondary, 40 VA, foot mount (Y65AS), 20.32 cm (8
in.) primary leads and 76.2 cm (30 in.) secondary leads, Class 2
Y65T42-0
Transformer, 120/208/240 VAC primary to 24 VAC secondary, 40 VA, hub mount (Y65SP+),
20.32 cm (8 in.) primary leads and secondary screw terminals, Class 2
Y65T31-0
Transformer, 120/208/240 VAC primary to 24 VAC secondary, 40 VA, foot mount (Y65AR+),
20.32 cm (8 in.) primary Leads and secondary screw terminals, Class 2
AP-TBK1002-0
2-position screw terminal that plugs onto the controller spade lugs
AP-TBK1003-0
3-position screw terminal that plugs onto the controller spade lugs
AP-TBK4FC-0
Replacement MS/TP FC bus terminal, 4-position connector, blue, bulk pack of 10
AS-CBLTSTAT-0
Cable adapter for connection to 8-pin TE-6700 Series sensors
TE730-29C-0
Sensor with temperature setpoint adjustment
TE730-39C-0
Sensor with temperature setpoint adjustment and occupancy button
TL-BRTRP-0
Portable BACnet/IP to MS/TP router
VAV1717 and VAV1732 VAV Controllers Installation Guide
20