Some flash codes indicate a warning condition. In a warning condition (such as the
indication of an invalid calibration), the servo recovers automatically. In this case,
default calibration automatically loads. This means the servo will operate, but it
may not be a perfect match to the actuator. If this happens, recalibrate the servo as
soon as possible.
Cmd Signal Fault
Command signal does not match input
setting
Adjust the input setting to match the
command signal used
Servo NXT is incorrectly wired
Verify wire connections against the wiring
diagram
Servo NXT is not receiving the command
signal
Test the Input Command connection with a
multimeter or oscilloscope
Limit switch fault
Both limit switches engaged
Adjust actuator cams
Servo NXT is incorrectly wired
Verify wire connections against the wiring
diagram
Travel limit switch failure
Test the switches to ensure that they
change states when engaged.
Hand wheel fault
Hand wheel is engaged
Disengage (push in) hand wheel
Servo NXT is incorrectly wired
Verify wire connections against the wiring
diagram
Hand wheel switch failure
Test the switch to ensure that it is changing
states when engaged.
FB pot fault
Potentiometer outside of travel range
Operate the actuator to the fully open and
fully closed position, and adjust the
potentiometer position as needed.
Servo NXT is incorrectly wired
Verify wire connections against the wiring
diagram
Torque switch fault
Torque switch setting enabled with no
torque switches connected
Disable torque switch settings
Torque switch or switches engaged
Check the valve and/or actuator for
obstructions.
Servo NXT is incorrectly wired
Verify wire connections against the wiring
diagram
Torque switch failure
Test the switches to ensure that they
change states when engaged.
Motor stall fault
Operational torque is exceeding the torque
rating of the actuator
Check the valve and/or actuator for
obstructions.
Measure the torque required to rotate the
valve and verify against the rated torque
Servo NXT is incorrectly wired
Verify wire connections against the wiring
diagram
Fault condition
during
autocalibration
Fault occurring during calibration
Operate the actuator to the fully open and
fully closed position, and correct any faults
that occur
Servo NXT is incorrectly wired
Verify wire connections against the wiring
diagram
Problem
Possible Cause
Solution