Johnson Controls VA-8051 Specification Download Page 3

VA-8051 Product Bulletin

     3

Wiring is to a terminal strip
labeled DWN (Down), COM
(Common) and UP,
respectively. Wiring is to the
terminals labeled R (Retracted
end), W (Wiper), and S (Stroked
end) for the feedback
potentiometer.
(See Fig. 6).

Retrofit Installation

!

CAUTION:

 Do not use on

valves having a stroke over
3/4 in. Actuator travel over
3/4 in. will damage the
actuator.

!

WARNING:

 Equipment

Damage Hazard.  Do not
drive the VA-8051 actuator
unless it is mounted to a
valve.  This can result in
permanent damage to the
actuator.

1.  Remove the V-3000

actuator, upper spring plate
and spring.  (See Fig. 2).

a.

Disconnect the air line
to the actuator.

b.

Remove the actuator
by loosening the
actuator set screw on
the bottom of the lower
diaphragm case. Lift
the actuator off of the
valve.

c.

Hold the stem
extension firmly with a
9/16 in. box-head
wrench and with a
small screwdriver,
loosen the stem locking
screw.

d.

For V-3000 valves,
compress the spring
using the X-200-8058
spring compression
tool. For V-3800
valves, compress the
spring with hand
pressure.

e.

Using a 9/16 in. box-
head wrench, unscrew
the stem extension. Lift
the spring and upper

spring plate off the
valve. Remove the
spring compression
tool if used.

f.

Thread the lower spring
plate up the
centerpiece stuffing box
to increase spacing
between the spring
plate and the flat valve
yoke mounting surface.

2.

Unpack the actuator and
make sure the lever plate is
within 1/4 in. of the upper
stop.

3.

Install the valve packing
that is provided according
to the instructions included
with the parts.

4.

Thread the 1/4 in. Palnut,
open side down, onto the
valve stem and all the way
to the end of the threads.

5.

Loosely install the actuator
by sliding the actuator yoke
between the spring plate
and the yoke surface.
Finger tighten the plate to
hold the actuator in place.
(See Fig. 3).

6.

Obtain a source of 24 volt
AC power. Wire a switch to
allow control of the 24 volts
AC to the DWN and COM
terminals of the actuator.

7.

Thread the coupler onto the
valve stem while applying
24 volts AC as necessary.

The coupler should thread
down the stem until
approximately 1/8 in. of
thread remains between the
coupler and the Palnut.

Fig. 2: Exposed V-3000 Actuator

Summary of Contents for VA-8051

Page 1: ...tops the motor Field calibration of the force sensor is not required The actuator maintains the shutoff force even if power to the controller is lost When the controller signals the valve to move in the opposite direction the shutoff force will be reduced and the valve will modulate The internal position feedback potentiometer is connected to the R W and S terminals Specifically the wiper is conne...

Page 2: ... 8051 Product Bulletin Wiring All wiring must be in accordance with applicable electrical code requirements Input lines to the actuator must be wired correctly for the valve to move in the proper direction ...

Page 3: ...ves compress the spring with hand pressure e Using a 9 16 in box head wrench unscrew the stem extension Lift the spring and upper spring plate off the valve Remove the spring compression tool if used f Thread the lower spring plate up the centerpiece stuffing box to increase spacing between the spring plate and the flat valve yoke mounting surface 2 Unpack the actuator and make sure the lever plat...

Page 4: ...n fully up to hold tension on the stem and coupler thread the Palnut up the stem until it contacts the coupler Tighten Palnut to coupler with 1 2 in and 7 16 in wrenches 10 Secure the actuator in place by tightening the spring plate with a large screwdriver See Fig 3 11 Drive the actuator fully up and down at least three complete cycles before again checking that the lever and its drive coupler st...

Page 5: ...Information Field repairs must not be made For a replacement VA 8051 contact the nearest Johnson Controls branch office Application and Drawing Identification Fig 3 Isometric Drawing Fig 4 VA 8051 1 Dimensions in mm Fig 5 Internal View ...

Page 6: ...051 Product Bulletin Fig 6 DSC 8500 Application Wiring Incremental Control with Position Indication or Proportional Control Controls Group 507 E Michigan Street P O Box 423 Printed in U S A Milwaukee WI 53202 ...