1.1.10 Factory settings
On delivery Unisab III is preset with factory settings for all appropriate points. Although other
values may have been entered from factory or after delivery, Unisab III can always be reset
to its factory settings. A factory reset affects the following points:
•
Alarm and shutdown limits
•
Regulator settings
•
Timer setup
•
Control mode
The factory settings are stated in the tables in the sections Alarm and shutdown, Timers and
Compressor regulation (Engineering manual). Before performing a factory reset, always stop
the compressor for safety reasons. Select Setup/Configuration/Factory Reset and change Fac-
tory Reset from No to Yes.
Now press
and within a few seconds Unisab III will restart and display the Favourites/De-
fault picture shown in Fig. 1. The reset operation is complete and Unisab III is now restored to
its factory settings. Unisab III must then be adjusted to the actual operating conditions. Re-
member to fill in the forms for actual settings before making a factory reset. These forms
(Settings for Unisab III) are included in the back of this manual.
1.1.11 Set values
The following tables show the different set values for pressures, temperatures and timers re-
spectively. The stated values are minimum, maximum and factory settings.