background image

Model TSV-D SMART Air Vent, Dry

Page 1 of 6 

JUNE 2020 

TFP1263

Worldwide 

Contacts

www.tyco-fire.com

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.

General 

Description

The TYCO Model TSV-D SMART Air 

Vent, Dry provides automatic oxygen 

venting in dry pipe fire sprinkler 

systems. As a fire sprinkler system is 

filled with a continuous supply of nitro-

gen gas from the TYCO Nitrogen Gen-

erator, the SMART Air Vent  allows 

oxygen rich gas to be vented from the 

fire sprinkler system. Over a period of 

14 days, the SMART Air Vent almost 

completely removes oxygen from the 

fire sprinkler system (< 2% oxygen). 

After 14 days, the SMART Air Vent 

automatically closes and prevents con-

tinuous venting.
The SMART Air Vent includes two sep-

arate components:

•  vent assembly 
•  electric control box

The vent assembly is equipped with a 

ball valve to be connected to the fire 

sprinkler riser. The electric control box 

is available in two inline voltage models 

- 120 VAC/60 Hz or 230 VAC/50 Hz.
The SMART Air Vent must be installed 

as shown on the engineering design 

documents. If a location is not speci-

fied, install the SMART Air Vent on the 

fire sprinkler system riser on the system 

side of the main control valve. The elec-

tric control box must be installed on 

an adjacent wall near the fire sprinkler 

system riser, as shown in Figure 4.
The SMART Air Vent is equipped with 

a levered float valve that allows gas to 

discharge but prevents liquid water 

from leaking through the restricted 

venting orifice in the event that water 

enters the fire sprinkler system.

A back pressure regulator is also 

included to prevent total system 

depressurization from the vent assem-

bly before the vent is electronically 

closed.
The restricted venting orifice allows 

oxygen to be vented from the fire 

sprinkler system at a controlled rate to 

achieve a minimum nitrogen concen-

tration of 98%. A special fitting is pro-

vided to receive 5/32 in. tubing when 

the vent is used in conjunction with 

the TYCO Model TSGA SMART Gas 

Analyzer.
The SMART Air Vent is equipped with 

an electronic solenoid valve that must 

be wired to the electric control box 

(conductors not included). The control 

box automatically closes the vent after 

14 days as the desired nitrogen con-

centration will have been achieved. The 

control box is equipped with an on/off 

switch and a vent button to provide a 

means to restart of the venting process 

should oxygen be reintroduced into the 

fire sprinkler system. See Figure 1.

NOTICE

The TYCO Model TSV-D SMART Air 

Vent, Dry described herein must be 

installed and maintained in compli-

ance with this document, in addi-

tion to the standards of any other 

authorities having jurisdiction. 

Failure to do so may impair the per-

formance of the related devices. 

 

The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.

Technical 

Data

Service Pressure

Up to 175 psig (12 bar)

System Connection

1 in. NPT Male

Electrical Connection

120 VAC/60 Hz (230 VAC/50 Hz); 

<2 Amps

Temperature Range

40°F to 120°F (4.5°C to 49°C)

Dimensions

Vent Assembly:

13.5 in. (W) x 4.25 in. (D) x 7.5 in. (H) 

(343 mm (W) x 108 mm (D) X 191 mm (H))

Control Box:

9 in. (W) x 7 in. (D) x 10 in. (H) 

(229 mm (W) x 178 mm (D) x 254 mm (H))

Note:

 

A support hanger is not required.

Reviews: