Johnson Controls tyco TAV-D Manual Download Page 2

TFP1262

Page 2 of 4

FIGURE 1 

MODEL TAV-D AIR VENT DRY 

ASSEMBLY

Operation

Step 1.

 Verify the vent assembly is 

equipped with a restricted venting 

orifice downstream of the backpres-

sure regulator. 

Note:

 If the vent assembly is not equipped 

with a restricted venting orifice, one will be 

provided by TYCO during system commis-

sioning. The restricted venting orifice must 

be installed before proceeding with the 

steps below.

Step 2.

 Determine the low air alarm 

pressure and the turn-on pressure of 

the nitrogen generator.

Step 3.

 Choose a pressure setting 

for the backpressure regulator that 

is 3 to 5 psig (0,2 to 0,3 bar) above 

the low air alarm pressure but below 

the turn-on pressure of the nitrogen 

generator.

Step 4.

 Pull the knob out from the reg-

ulator to adjust the pressure setting. 

Turn the knob clockwise to raise the 

pressure, counter-clockwise to lower 

the pressure.

Step 5.

 Close the ball valve and allow 

the device to depressurize through 

the restricted venting orifice to the 

pressure setting. Adjust the pressure 

setting using the knob, then open the 

ball valve to pressurize the device and 

close the ball valve again to check the 

pressure setting. Repeat the process 

until the desired pressure setting is 

achieved.

Note:

 This process can only be performed 

when the fire sprinkler system is at normal 

operating pressure. 

Step 6. 

Push the knob back into the 

regulator until it clicks into place.

Step 7.

 Once the TYCO Nitrogen Gen-

erator is commissioned, open the iso-

lation ball valve on the vent assembly. 

The Air Vent is now open and actively 

venting oxygen from the fire sprin-

kler system. It should remain open 

for approximately 14 days or until the 

system nitrogen concentration reaches 

98% or greater. Use a TYCO Model 

THGA Handheld Gas Analyzer to verify 

the gas concentration inside the fire 

sprinkler system.

Step 8.

 Close the isolation ball valve. 

Failure to close the manual ball valve 

after 14 days or once the fire sprinkler 

system nitrogen concentration reaches 

98% will result in additional oxygen 

corrosion damage to the system and 

unnecessary run time of the air com-

pressor and nitrogen generator.

Step 9.

 If the sprinkler system actuates 

or another event introduces oxygen 

to the sprinkler system the manual 

ball valve must be opened again for a 

period of 14 days to vent oxygen from 

the system.

Installation

The TYCO Model TAV-D Air Vent, Dry 

must be installed in accordance with 

this section.

Step 1. 

The Model TAV-D Air Vent is 

equipped with a ball valve to be con-

nected to the fire sprinkler riser. The 

contractor must install a 1 in. outlet 

(welded or mechanical) to connect the 

vent assembly to the sprinkler system 

on the system side of the main control 

valve as shown in Figure 2. The ball 

valve must remain in the closed posi-

tion until the TYCO Nitrogen Generator 

is  commissioned.

Step 2. 

Install the vent assem-

bly in a level position. The recom-

mended mounting height is between 

5 ft to 10 ft (2 m to  3 m) above the fin-

ished floor. 

Note:

 Piping to the vent assembly cannot be 

installed in a configuration that would trap 

water and prevent drainage to the sprinkler 

system; a water trap impedes the ability of 

the vent assembly to vent oxygen from the 

fire sprinkler system.

Step 3. 

Inspection of the vent assem-

bly should be performed after installa-

tion and hydrostatic testing of the fire 

sprinkler system. Inspection should 

be performed periodically thereaf-

ter in accordance with the applicable 

NATIONAL FIRE PROTECTION ASSO-

CIATION (NFPA) codes and standards 

and/or the authority having jurisdiction.

Note:

 Inspection must include the condition 

of the in-line filter and checking for blockage 

in the “Y” strainer and the restricted venting 

orifice.

RESTRICTED VENTING ORIFICE

IN-LINE FILTER

MUFFLER

GAS SAMPLE PORT

BACKPRESSURE REGULATOR

CONNECTION TO 

SPRINKLER SYSTEM

ISOLATION 

BALL VALVE

QUICK CONNECT

“Y” STRAINER 

WITH BALL VALVE

FLOAT 

VALVE

Reviews: