Johnson Controls tyco TAV-D Manual Download Page 1

Model TAV-D 

Air Vent, Dry

Page 1 of 4 

NOVEMBER 2019 

TFP1262

Worldwide 

Contacts

www.tyco-fire.com

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.

General 

Description

The TYCO Model TAV-D Air Vent, Dry, 

provides oxygen venting in dry pipe 

fire sprinkler systems. As a fire sprin-

kler system is filled with a continuous 

supply of nitrogen gas from the TYCO 

Nitrogen Generator, the Air Vent allows 

oxygen rich gas to be vented from the 

fire sprinkler system. Over a short 

period of time the Air Vent will almost 

completely remove oxygen from the fire 

sprinkler system (< 2% oxygen).
The Air Vent must be installed as 

shown on the engineering design doc-

uments. If a location is not specified, 

install the Air Vent on the fire sprinkler 

system riser on the system side of the 

main control valve. The vent is also 

installed to provide source gas when 

used in conjunction with the TYCO 

TSGA SMART Gas Analyzer.
The Air Vent is equipped with a levered 

Float Valve that allows oxygen to 

discharge but prevents water from 

leaking through the restricted venting 

orifice in the event that water enters 

the fire sprinkler system, as shown 

in Figure 1. A Backpressure Regula-

tor is also included to prevent total 

system depressurization from the vent 

assembly.

The Restricted Venting Orifice allows 

oxygen to be vented from the fire 

sprinkler system at a controlled rate to 

achieve a minimum nitrogen concen-

tration of 98%. A special fitting is pro-

vided to receive 5/32 in. tubing when 

the vent is used in conjunction with 

the TYCO Model TSGA SMART Gas 

Analyzer.
There are two models of the TYCO Air  

Vent, the TAV-D and the TSV-D. The 

units both operate as described above 

but the TSV-D model includes an elec-

tronic solenoid valve wired to a control 

panel that automatically closes the vent 

once the desired nitrogen concentra-

tion is reached. The control panel is 

also equipped with a reset switch to 

allow the venting process to restart 

should oxygen be reintroduced into the 

fire sprinkler system.

NOTICE

The TYCO Model TAV-D Air Vent, Dry, 

described herein must be installed and 

maintained in compliance with this 

document, in addition to the standards 

of any other authorities having jurisdic-

tion. Failure to do so may impair the 

performance of the related devices. 

 

The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.

Technical 

Data

Service Pressure

Up to 175 psig (12 bar)

System Connection

1 in. NPT Male

Temperature Range

40°F to 120°F (4.5°C to 49°C)

Dimensions

13.5 in. (W) x 4.25 in. (D) x 7.5 in. (H) 

(343 mm (W) x 108 mm (D) X 191 mm (H))

Reviews: