Section 2: Installation
Keypad zones support Normally Closed Loops, Single End of Line, Double End of Line, and Triple End of Line resistors.
To connect the PGM output, run one wire to the P/Z terminal and the other to R.
Figure 2-30: Keypad terminals
R
B
Y
G
P/Z
Callout
Description
1
Red
2
Black
3
Yellow
4
Green
5
To zone or PGM ouput
Note:
When using end-of-line supervision, connect the zone according to one of the configurations outlined in
. End-of- line resistors must be placed on the device end of the loop, not at the keypad.
Assigning keypad zones
When using keypad zone inputs, each input used must be assigned a zone number in Installer Programming.
First, ensure that you have enrolled all installed keypads into the desired slots (
See "[902] Add/Remove Modules" on page 156
).
Next, assign keypad zones by entering programming section [861]-[892], subsection 011 for keypads 1-16. Enter a 3-digit zone
number for each of the keypad zones. This number must be programmed into the slot location that the keypad is assigned to.
Note:
A keypad zone overrides the corresponding hardwired or wireless zone.
Once the keypad zones are assigned, you must also program zone definitions and zone attributes.
See "[001] zone types" on page
and
.
HSM2955 wiring
For wiring information refer to HSM2955 Installation manual #29010198xxx.
Zone wiring
Power down the alarm controller and complete all zone wiring.
Zones can be wired to supervise normally open devices (e.g., smoke detectors) or normally closed devices (e.g., door contacts). The
alarm panel can also be programmed for single end-of-line, double end-of-line, and triple-end of line resistors.
Zone programming is done using the following programming sections:
l
[001] selects zone definition
l
[013] Opt [1] for normally closed or EOL; Opt [2] for SEOL or DEOL
l
[201] - [232] partition assignment.
Alternately, zones may be individually configured as NC, SEOL, DEOL or TEOL through section [002] Zone Attributes, toggles 9, 10,
11 and 15, which will override the option in [013].
Observe the following guidelines when wiring zones:
l
For UL listed installations use SEOL or DEOL only
l
Minimum 22 AWG wire, maximum 18 AWG
l
Do not use shielded wire
l
Do not exceed 100
Ω
wire resistance. Refer to the following table:
Table 2-4: Burglary zone wiring chart
Wire gauge
Maximum length to EOL resistor (ft/meters)
22
3000 / 914
20
4900 / 1493
- 42 -