Section 6: Programming
3/4 – Reserved
5/6 – Reserved
7/8 – Alt. Comm Radio/SIM Failure/Restore
Sent when the alternate communicator experiences trouble or restore of the radio/SIM.
[352] Alternate Communicator 2
1/2 – Alt. Comm Network Fault/Restore
Sent when the alternate communicator loses or restores communication with the network.
5/6 – Alt. Comm Ethernet Trouble /Restore
Sent when the alternate communicator detects a network absent condition or DHCP failure or restore.
[354] Alternate Communicator 4
Receiver 1 to 4 Trouble and Restore
Sent when the alternate communicator detects a trouble or restore condition on receiver 1-4.
1/2 – Receiver 1 Trouble/Restore
3/4 – Receiver 2 Trouble/Restore
5/6 – Receiver 3 Trouble/Restore
7/8 – Receiver 4 Trouble/Restore
[355] Alternate Communicator 5
Receiver 1 to 4 Supervision Failure and Restore
Sent when the alternate communicator detects a supervision trouble for the Ethernet receiver (1, 2) or the GPRS receiver (3, 4).
1/2 – Receiver 1 Supervision Failure/Restore
3/4 – Receiver 2 Supervision Failure/Restore
5/6 – Receiver 3 Supervision Failure/Restore
7/8 – Receiver 4 Supervision Failure/Restore
[361] Wireless Device Events
1/2 – Wireless Device AC Failure/Restore
These options are used to enable wireless device AC failure/restore reporting codes. These reporting codes are sent when a
wireless device experiences an AC failure/restore.
3/4 – Wireless Device Low Battery Trouble/Restore
These options are used to enable wireless device low battery trouble/restore reporting codes. These codes are sent when a wireless
device experiences a low battery trouble/restore.
5/6 – Wireless Device Fault/Restore
These options are used to enable wireless device fault/restore reporting codes. This reporting code is sent when a wireless device
experiences a supervisory fault.
[401] System Test Events
1/2 – Walk Test Start/End
Sent when installer walk test is initiated and terminated.
These reporting codes are in addition to the alarm reporting codes for the zones that are tripped during the walk test period.
3 – Periodic Test Transmission
Sent when the test transmission programmed in section
"[401] System Test Events" on page 129
occurs.
4 – Periodic Test Transmission with Trouble
Sent when any of the following trouble conditions are present during a periodic test transmission:
l
Fire Zone Trouble
l
Battery Trouble
l
Fire Zone Alarm (2-Wire Smoke)
l
Aux Trouble
l
Fire Trouble
l
Bell Trouble
l
Fire Tamper/Low Sensitivity (Wireless)
l
Module Supervisory
l
Fire Zones Bypassed
- 129 -