Step 7.

 When installing an Air and 

Dust Seal, refer to Figure 4, otherwise 

proceed to Step 8. To attach the Air 

and Dust Seal, verify the angle of the 

outside edge of the seal is oriented 

according to Figure 4. Start the edge of 

the Retainer in the grooved slot of the 

Air and Dust Seal and continue around 

the retainer until the entire Air and Dust 

Seal is engaged.

Step 8.

 Screw on the Cover Plate/

Retainer Assembly until the Retainer 

Figure 2 (or Air and Dust Seal - Figure 

4) makes contact with the ceiling. Do 

not continue to screw on the Cover 

Plate/ Retainer Assembly such that it 

lifts a ceiling panel out of its normal 

position. If the Cover Plate/Retainer 

Assembly cannot be engaged with 

the Support Cup or the Cover Plate/

Retainer Assembly cannot be engaged 

sufficiently to contact the ceiling, the 

Sprinkler Fitting must be repositioned.

3-3/16" DIA.

(81,0 mm)

2-1/2" DIA.

(63,5 mm)

MOUNTING

SURFACE

3/16"

(4,8 mm)

FACE OF

SPRINKLER

FITTING

DEFLECTOR IN

OPERATED POSITION

3/4" (19,1 mm)

THREADED

ADJUSTMENT

SPRINKLER-

SUPPORT CUP

ASSEMBLY

OPERATED

SPRINKLER

SPRINKLER-

SUPPORT CUP

ASSEMBLY

COVER-

RETAINER

ASSEMBLY

COVER

PLATE

RETAINER

DISPOSABLE

PROTECTIVE CAP

3/4"

NPT

TIP

3/8" (9,5 mm)

1-1/8" (28,6 mm)

3/32" GAP

(2,4 mm)

2-1/8"±3/8"

(54,0 mm

±9,5 mm)

FRAME

ARM

SUPPORT

CUP

ACCEPTS

1/2" DRIVE OR

7/8" OPEN-END

WRENCH

ALIGN

ARROWS WITH

FRAME ARMS

SPRINKLER

WRENCHING

HEX

WRENCH HEX

RECESS

FIGURE 2 

THE ILLUSION PENDENT SPRINKLER INSTALLATION DIMENSIONS

FIGURE 3 

W-TYPE 18 SPRINKLER WRENCH

Summary of Contents for tyco ILLUSION

Page 1: ...rarily removed for installation and it can be replaced to help protect the sprinkler while the ceiling is being installed or finished The tip of the Protective Cap can also be used to mark the center of the ceiling hole into plaster board ceiling tiles etc by gently pushing the ceiling product against the Protective Cap When the ceiling installation is complete the Pro tective Cap is re moved and ...

Page 2: ...ler must only be installed in the pendent position and with the centerline of the sprinkler per pendicular to the mounting surface Step 2 Remove the Protective Cap Step 3 With pipe thread sealant applied to the pipe threads hand tighten the sprinkler into the sprinkler fitting Step 4 Wrench tighten the sprinkler using only the W Type 18 Sprinkler Wrench Ref Figure 3 The W Type 18 Sprinkler Wrench ...

Page 3: ...osition If the Cover Plate Retainer Assembly cannot be engaged with the Support Cup or the Cover Plate Retainer Assembly cannot be engaged sufficiently to contact the ceiling the Sprinkler Fitting must be repositioned 3 3 16 DIA 81 0 mm 2 1 2 DIA 63 5 mm MOUNTING SURFACE 3 16 4 8 mm FACE OF SPRINKLER FITTING DEFLECTOR IN OPERATED POSITION 3 4 19 1 mm THREADED ADJUSTMENT SPRINKLER SUPPORT CUP ASSEM...

Page 4: ...ged by dropping striking wrench twist slippage or the like must be replaced Also replace any sprin kler that has a cracked bulb or that has lost liquid from its bulb Ref Installa tion Section If a sprinkler must be removed do not reinstall it or a replacement without reinstalling the Cover Plate Assembly If a Cover Plate Assembly becomes dislodged during service replace it immediately The owner is...

Reviews: