background image

TFP312

Page 4 of 6

Description

Specification, UL

Sprinkler Type

ESFR

Temperature Rating ˚F (˚C)

165˚F (74˚C)  

212˚F (100˚C)

Response Type

QR

Sprinkler Position

Pendent, frame arms aligned with pipe,  

deflectors parallel with ceiling or roof

System Type

Wet

Maximum Area of Coverage

100 ft

2

 (9,3 m

2

)

Minimum Area of Coverage

64 ft

2

 (5,8 m

2

)

Maximum Slope Ceiling

2 in. rise for 12 in. run (16.7%)

Maximum Spacing

10 ft (3,1 m)

Minimum Spacing

8 ft (2,4 m)

Deflector Distance from Walls

Minimum of 4 in. (100 mm) from walls but no more than 1/2 the 

allowable distance permitted between sprinklers

Deflector to Top of Storage

Minimum of 36 in. (914 mm)

Deflector to Ceiling Distance

6 in. to 14 in. (152 mm to 356 mm)

Maximum Ceiling Height

48 ft (14,6 m)

Maximum Storage Height

43 ft (13,1 m)

Storage Arrangement

Palletized, solid piled, open frame; single row or double row

Commodity

Class I - IV, Cartoned unexpanded plastic

Sprinkler System Design

NFPA 13 for ESFR Sprinklers based upon 45 psi (3,1 bar) design 

pressure 169 gpm (640 Lpm) with 12 sprinkler remote area

Obstruction Criteria

Reference NFPA 13, Chapter 8

Minimum Aisle Width

5 ft (1,5 m)

Hose Stream allowance and Water Supply Duration

250 gpm for 60 minutes (950 Lpm for 60 minutes)

TABLE C 

MODEL ESFR-25 PENDENT SPRINKLER 

SPECIFIC APPLICATION LISTING (UL) 

COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW