TFP633

Page 2 of 8

Operation

The glass bulb contains a fluid that 

expands when exposed to heat. When 

the rated temperature is reached, the 

fluid expands sufficiently to shatter the 

glass bulb allowing the sprinkler to acti-

vate and flow water.

Design 

Criteria

Design criteria is provided as follows:
•  200°F (93°C), Model CC3 Combusti-

ble Concealed Sprinklers with CPVC 

pipe and horizontal slope above 

sprinklers not exceeding 2:12. See 

Page 2.

•  200°F (93°C), Model CC3 Combus-

tible Concealed Sprinklers with steel 

pipe and horizontal slope above 

sprinklers not exceeding 2:12 See  

Page 4.

•  For the installation of Model CC3 

Combustible Concealed Sprinklers 

installed with baffles at 2000 ft² 

(186 m²), the design of the system 

should be 6 sprinklers or 1000 sq. ft., 

whichever is greater.

Design Criteria, 

CPVC Pipe

Area of Use (CPVC Pipe)

Horizontal (slope not exceeding 2:12) 

combustible concealed spaces of:
•  Unobstructed wood truss construc-

tion or unobstructed bar joist con-

struction. See Figure 2.

•  Non-combustible, insulation-filled 

solid wood or composite wood joist 

construction.  See Figure 3.

NOTE: In order to be considered 

“non-combustible insulation-filled 

solid wood or composite wood joist 

construction,” the insulation (includ-

ing insulation provided with a combus-

tible vapor barrier), must completely fill 

the pockets between the joists to the 

bottom of the joists, and the insulation 

must be secured in place with metal 

wire netting. The metal wire netting is 

intended to hold the insulation in place 

should the insulation become wetted 

by the operation of the Model CC3 

Sprinklers in the event of a fire.

Concealed Space Area (CPVC Pipe)

The area of the concealed space is not 

limited; however, for both Figure 2 and 

Figure 3, where CPVC pipe is being uti-

lized, draft curtains or full height walls 

must be provided at 1000 ft² (93 m²) 

areas. In addition, the 5.6K sprinkler is 

UL Listed for a 2000 ft² (186 m²) draft 

curtain area for solid wood open truss 

construction on edge or on face.
This draft curtain shall be at least 1/3 

the depth of the concealed space or 8 

in. (200 mm), whichever is greater, and 

be constructed using a material that 

will not allow heat to escape through 

or above the draft curtain.
For information about antifreeze com-

patibility and approved configurations, 

see the Technical Data section.

Concealed Space Size (CPVC Pipe)

The depth of the concealed space is 

60 in. (1524 mm) maximum to 6 in. (152 

mm) minimum.

System Type (CPVC Pipe)

Light hazard, wet pipe system

Maximum Distance Between Model 

CC3 Sprinklers (CPVC Pipe)

TY2199 4.2K. . . . . . . . . . . . . .  14 ft (4,3 m)
TY3199 5.6K. . . . . . . . . . . . . .  16 ft (4,9 m)

Maximum Coverage Area 

(CPVC Pipe)

TY2199 4.2K. . . . . . . . . . . 196 ft² (18,2 m²)
TY3199 5.6K. . . . . . . . . . . 256 ft² (23,8 m²)

Minimum Distance Between Model 

CC3 Sprinklers (CPVC Pipe)

Minimum sprinkler spacing is 7 ft 

(2,1 m)

NOTE: Minimum spacing does not 

apply to any additional sprinklers 

required for protection of CPVC pipe 

that is offset over an obstruction.

Deflector Position (CPVC Pipe)

•  1-1/2 in. to 4 in. (40 to 100 mm) below 

upper deck for wood truss construc-

tion or bar joist construction. See 

Figure 2.

•  1-1/2 in. to 4 in. (40 to 100 mm) below 

solid wood or composite wood joists. 

See Figure 3.

Minimum Distance Away From 

Trusses (CPVC Pipe)

4-1/2 in. (114 mm)

Remote Area (CPVC Pipe)

The remote area is 1000 ft² (93 m²)

NOTE: The remote area does not 

include any additional sprinklers 

required for protection of CPVC pipe 

that is offset over an obstruction.

Required Minimum Density 

(CPVC Pipe)

0.10 gpm/ft² (4,1 mm/min)

Minimum Operating Pressure 

(CPVC Pipe)

7 psi (0,48 bar)

Obstructions (CPVC Pipe)

See Figure 8 in this data sheet for 

obstructions rules.

Use of UL Listed BLAZEMASTER 

CPVC Pipe with Model CC3 

Sprinklers

BLAZEMASTER CPVC product may 

be used in concealed spaces requir-

ing automatic sprinklers, when used 

in conjunction with Model CC3 Sprin-

klers. In order to use the BLAZEMAS-

TER CPVC product for wood truss or 

bar joist construction, the horizon-

tal run of pipe must be a maximum 

of 6 in. (150 mm) above the ceiling or 

noncombustible ceiling insulation, 

or 1/3 the depth of concealed space 

(as measured from the top surface of 

the ceiling to the bottom of the deck 

above), whichever is smaller, see Figure 

2. For insulation-filled solid wood or 

composite wood joist construction, 

the horizontal run of pipe must be a 

maximum of 6 in. (150 mm) above 

ceiling or non-combustible ceiling 

insulation, or 1/3 the depth of con-

cealed space (as measured from the 

top surface of the ceiling to the bottom 

surface of the joist insulation above), 

whichever is smaller, see Figure 3. The 

CPVC pipe can then be used to supply 

the Model CC3 Sprinklers, as well as 

the sprinklers below the ceiling. Unless 

modified by this technical data sheet, 

-

-

-

-

-

-

-

2

7

4

6

5

3

1

Frame

Button

Sealing

Assembly

Deflector

Bulb

Compression

Screw

2

1

3

4

Components:

5

6

WRENCH

FLATS

7/16" (11,1 mm)

NOMINAL MAKE-IN

SPRINKLER

FRAME

ARMS

1-11/16"

(42,9 mm)

2-1/4"

(57,2 mm)

1/2" NPT

7

Ejection

Spring

FIGURE 1 

MODEL CC3 SPRINKLER

Summary of Contents for tyco CC3

Page 1: ...m from floor to ceiling 60 in 1524 mm maximum height for truss and bar joist The 4 2K and 5 6K sprinklers are UL Listed for use with LFP Antifreeze For information about antifreeze compatibility and a...

Page 2: ...oncealed space is 60 in 1524 mm maximum to 6 in 152 mm minimum System Type CPVC Pipe Light hazard wet pipe system Maximum Distance Between Model CC3 Sprinklers CPVC Pipe TY2199 4 2K 14 ft 4 3 m TY3199...

Page 3: ...ECK NON COMBUSTIBLE INSULATION 6 152 mm MINIMUM 60 1524 mm MAXIMUM 1 1 2 40 mm MINIMUM 4 102 mm MAXIMUM 6 152 mm MAXIMUM FOR CPVC PIPE COMPOSITE WOOD JOISTS SOLID WOOD JOISTS FRAME ARMS OF SPRINKLER M...

Page 4: ...ches 150 mm or 1 3 the depth of the con cealed space whichever is greater and run parallel with the joist spaced at 31 ft 9 4 m width maximum to limit the area to a maximum of 1000 ft 93 m For informa...

Page 5: ...AXIMUM CEILING UPPER DECK FRAME ARMS OF SPRINKLER MUST BE INSTALLED IN LINE WITH PIPE RUN UPPER DECK CEILING FRAMING 84 2134 mm MAXIMUM 2x FLOOR SOLID WOOD JOISTS 6 152 mm MINIMUM 60 1524 mm MAXIMUM M...

Page 6: ...E ARMS OF SPRINKLER MUST BE INSTALLED IN LINE WITH PIPE RUN UPPER DECK MODEL CC3 SPRINKLER CEILING FRAMING 2x FLOOR SOLID WOOD JOISTS NON COMBUSTIBLE INSULATION COMPOSITE WOOD JOISTS 1 1 2 38 mm MINIM...

Page 7: ...read sealant applied to the pipe threads use only the W Type 6 End A Sprinkler Wrench see Figure 9 for installation of the Model CC3 Sprin klers by applying the wrench to the sprinkler wrench flats on...

Page 8: ...e completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush Care must be exercised to avoid damage to the sprinklers before during and after installation Spri...