TFP630
Page 7 of 8
Installation
The Model CC1 Sprinklers must be
installed in accordance with this
section.
General Instructions
The Model CC1 Sprinklers are to be
installed upright and with their frame
arms (Ref. Figure 1) parallel with the
wood trusses, top chord of the bar joist,
or wood joists, as opposed to being
necessarily parallel with the pipe (Ref.
Figures 2 through 7 as applicable).
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 in.
(1,6 mm) for the 175°F (79°C) tempera-
ture rating.
A leak-tight 1/2 in. NPT sprinkler joint
should be obtained with a torque of 7 to
14 lb-ft (9,5 to 19,0 N
∙
m). Higher levels
of torque may distort the sprinkler inlet
with consequent leakage or impairment
of the sprinkler.
The Model CC1 Sprinklers must only
be installed in the upright position with
the deflector parallel to the upper deck.
With pipe thread sealant applied to the
pipe threads, use only the W-Type 20
(End B) Sprinkler Wrench (Ref. Figure
9) for installation of the Model CC1
Sprinklers by applying the wrench to
the sprinkler wrench flats only.
0"
2-1/2"
(63,5 mm)
3-1/2"
(88,9 mm)
5-1/2"
(139,7 mm)
7-1/2"
(190,5 mm)
9-1/2"
(241,3 mm)
12"
(304,8 mm)
14"
(355,6 mm)
16-1/2"
(419,1 mm)
(0 mm)
Maximum Allowable
Distance of Deflector
Above Bottom of
Obstruction
(B)
Distance from
Centerline of
Sprinkler to Side
of Obstruction
(A)
A≥3C or 3D
A≤24" (609,6 mm)
(Use dimension C or D, whichever is greater)
<12"
<(304,8 mm)
12" to <18"
(304,8 mm to <457,2 mm)
18" to <24"
(457,2 mm to <609,6 mm)
24" to <30"
(609,6 mm to <762,0 mm)
30" to <36"
(762,0 mm to <914,4 mm)
36" to <42"
(914,4 mm to <1066,8 mm)
42" to <48"
(1066,8 mm to <1219,2 mm)
48" to <54"
(1219,2 mm to <1371,6 mm)
54" to <60"
(1371,6 mm to <1524,0 mm)
NOTE:
WEB MEMBERS AND GUSSETS
SHALL NOT BE CONSIDERED
OBSTRUCTIONS PROVIDED THE
MINIMUM 4-1/2 INCH LATERAL
DISTANCE (FIG. 2) REQUIRED
BY THE SPECIFIC APPLICATION
LISTING IS MAINTAINED.
OBSTRUCTION
MODEL CC1
SPRINKLER
C
D
A
OBSTRUCTION
UPPER
DECK
LOWER
DECK
A
MODEL CC1
SPRINKLER
MODEL CC1
SPRINKLER
A
UPPER DECK
OR BOTTOM OF
NON-COMUSTIBLE
INSULATION
B
ELEVATION VIEW
PLAN VIEW
C
D
OBSTRUCTION
WRENCH RECESS
(USE END "B" FOR
MODEL CC1)
FIGURE 8
NFPA 13 OBSTRUCTION TO WATER DISTRIBUTION CRITERIA
(REFERENCE)
FIGURE 9
W-TYPE 20
SPRINKLER WRENCH