Step D. 

After the wall has been 

installed or the finish coat has been 

applied, slide on the Style 20 Closure 

over the Type ULF AM33 Nozzle and 

push the Closure over the Mounting 

Plate until its flange comes in contact 

with the wall.

Step E.

 After installation is complete, 

remove bulb protector from nozzle.

Note: Absence of a Style 20 Recessed 

Escutcheon, which is used to cover a 

clearance hole, can delay the time to 

nozzle operation in a fire situation. 

Care and 

Maintenance

The TYCO Ultra Low Flow AQUAMIST 

Type ULF AM33 Horizontal Sidewall 

Nozzles must be maintained and ser-

viced in accordance with this section.
Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system 

that it controls, obtain permission to 

shut down the affected fire protection 

system from the proper authorities 

and notify all personnel who may be 

affected by this action.
Nozzles which are found to be leaking 

or exhibiting visible signs of corrosion 

must be replaced.
Automatic nozzles must never be 

painted, plated, coated, or other-

wise altered after leaving the factory. 

Modified nozzles must be replaced. 

Nozzles that have been exposed to 

corrosive products of combustion, but 

have not operated, should be replaced 

if they cannot be completely cleaned 

by wiping the nozzle with a cloth or by 

brushing it with a soft bristle brush.
Care must be exercised to avoid 

damage to the nozzles before, during, 

and after installation. Nozzles damaged 

by dropping, striking, wrench twist/

slippage, or the like, must be replaced. 

Also, replace any nozzle that has a 

cracked bulb or that has lost liquid from 

its bulb. Refer to the Installation section 

for more information.
Frequent visual inspections are recom-

mended to be initially performed for 

nozzles installed in potentially corro-

sive atmospheres to verify the integ-

rity of the materials of construction 

and finish as they may be affected by 

the corrosive conditions present for a 

given installation. Thereafter, annual 

inspections per applicable standards 

are required, in addition to inspec-

tions required by the authority having 

jurisdiction.
The owner is responsible for the 

inspection, testing, and maintenance of 

their fire protection system and devices 

in compliance with this document, as 

well as with the applicable standards 

of any other authorities having juris-

diction. Contact the installing contrac-

tor or product manufacturer with any 

questions.
Water mist systems should be in-

spected, tested, and maintained by a 

qualified Inspection Service in accor-

dance with local requirements and/or 

national codes.

Limited 

Warranty

For warranty terms and conditions, visit 

www.tyco-fire.com.

Ordering 

Procedure

Contact your local distributor for avail-

ability. When placing an order, indicate 

the full product name and part number 

(P/N).

Type ULF AM33 AQUAMIST Nozzles

Specify: Type ULF AM33 AQUAMIST 

Nozzle with 57ºC (135ºF) tempera-

ture rating, finish (specify), and P/N 

(specify):

Natural Brass . . . . . . . . . . . . . . . . . 49-033-1-135

Pure White (RAL9010)

a

  . . . . . . . . .49-033-3-135

Signal White (RAL9003)

b

. . . . . . . .49-033-4-135

Chrome Plated . . . . . . . . . . . . . . . .49-033-9-135

a.  Eastern Hemisphere sales only
b.  Formerly known as Bright White

Escutcheon

Specify: Style 20 Recessed Escutch-

eon with (specify*) finish, P/N (specify*)

* Refer to Technical Data Sheet TFP770

Wrench

Specify: W-Type 6 Sprinkler Wrench, 

P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench, 

P/N 56-850-4-001

Summary of Contents for tyco AQUAMIST ULF AM33

Page 1: ...e design of water mist systems for fire protec tion must only be performed by expe rienced designers who thoroughly understand the limitations as well as capabilities of such systems The owner is responsible for main taining their fire protection system and devices in proper operating con dition Contact the installing contrac tor or product manufacturer with any questions Approvals TYCO Ultra Low ...

Page 2: ...pipe thread sealant applied to the pipe threads hand tighten the nozzle into the nozzle fitting Step C Tighten the nozzle into the nozzle fitting using only the W Type 7 Recessed Sprinkler Wrench Refer to Figure 4 for more information With ref erence to Figure 1 apply the W Type 7 Recessed Sprinkler Wrench to the nozzle wrench flats Components Strainer Sealing Frame Button Diffuser Bulb Assembly E...

Page 3: ... has a cracked bulb or that has lost liquid from its bulb Refer to the Installation section for more information Frequent visual inspections are recom mended to be initially performed for nozzles installed in potentially corro sive atmospheres to verify the integ rity of the materials of construction and finish as they may be affected by the corrosive conditions present for a given installation Th...

Page 4: ...ire Protection Association TEFLON is a registered trademark of DuPont 1400 Pennbrook Parkway Lansdale PA 19446 Telephone 1 215 362 0700 2018 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice ...

Reviews: