Johnson Controls TrueRH Series Installation Instructions Manual Download Page 2

2

    T

RUE

RH Series HT-670x Humidity Transmitters Installation Instructions 

Mounting 

Location Considerations 

IMPORTANT: 

To avoid damage to the circuit 

board and components, do not mount the unit in a 
location where high concentrations of corrosive 
vapors are present. 

The HT-670x element comes with one mounting base 
for both surface and wallbox mounting. To mount the 
HT-670x, release the cover from the mounting base as 
described in Figure 1. 

Base

Cover

1.  Loosen (do not
     remove) the cover
     screw with a 1/16 in.
     (1.5 mm) Allen
     wrench.

2.  Swing the cover
     down from the
     base.

 

Figure 1: Removing the Cover from the Base 

Wallbox Mounting: Special Tools Needed 

Use a 1/16 in. (1.5 mm) Allen wrench or T-4000-119 
Allen-head adjustment tool for mounting. 

Wallbox Mounting: Location Considerations 

Locate the humidity transmitter on an inside wall, free 
from drafts, and out of direct sunlight. The HT-670x is 
shock and vibration resistant; however, be careful not 
to drop or mount the unit where it could be exposed to 
excessive vibration. The following ambient operating 
conditions apply: 

 

Temperature: 32 to 122°F (0 to 50°C) 

 

Humidity: 0 to 100% Relative Humidity (RH), 
noncondensing; 85°F (29°C) maximum dew point 

To mount the HT-670x to a wallbox: 

1.  Pull the cable or wiring through the wallbox and 

base. 

2.  Rotate the mounting base, so one of the arrows on 

the base points up. 

3.  Fasten the base to the wallbox with the 

No. 6 screws provided. (See Figure 2.) 

Note: 

These instructions assume a standard 

2 x 4 in. (52 x 104 mm) U.S. wallbox is used. 

No. 6

Screws

Cover

Screw

 

Figure 2: Wallbox Mounting

Place the bottom edge of 

the cover against the bottom lip of the base, and 
rotate it up onto the base. (See Figure 3.) 

5. 

Tighten the cover screw. 

Base

Cover

Screw

Cover

 

Figure 3: Attaching the Cover to the Base 

Once installed, the HT-670x cannot be removed from 
the wall unless the cover screw is loosened as 
described in Figure 1. 

IMPORTANT: 

Seal the drilled hole or use an 

ACC-INSL-0 Foam Pad Kit to help reduce drafts 
entering the unit. (See Table 1.) Drafts could result 
in false humidity or temperature readings. 

Summary of Contents for TrueRH Series

Page 1: ...against failure or malfunction of the HT 670x Series Humidity Transmitter IMPORTANT Le HT 670x Series Humidity Transmitter est destin transmettre des donn es entrantes un quipement dans des condition...

Page 2: ...eful not to drop or mount the unit where it could be exposed to excessive vibration The following ambient operating conditions apply Temperature 32 to 122 F 0 to 50 C Humidity 0 to 100 Relative Humidi...

Page 3: ...spacers for 5 8 in 16 mm drywall Note For replacement spring clips spacers and screws order the ACC DWCLIP 0 Drywall Clip Mounting Kit See Table 1 Base Cover Screw Cover Figure 4 Removing the Breakawa...

Page 4: ...ay be exposed to condensation To mount the duct probe humidity transmitter refer to Figure 6 and proceed as follows 1 Remove any excess insulation from the duct that prevents the probe from extending...

Page 5: ...ply 16 to 30 VDC Note Output is not used Common Figure 8 Wiring with Output Jumper Set for 4 to 20 mA Once installed the unit cannot be removed from the wall unless the cover screw is loosened as desc...

Page 6: ...sunlight for example 2 Check all supply voltage connections and make sure the wiring is correct Refer to Figure 10 or Figure 11 for the duct probe transmitter and Figure 7 or Figure 8 for the wall mou...

Page 7: ...0 to 80 C 0 to 100 RH noncondensing 85 F 29 C maximum dew point Materials Wall Mount White plastic enclosure for surface or standard wallbox mounting including hardware Duct Probe White plastic cover...

Reviews: