TM-11x1 Series Room Temperature Module Installation Instructions
5
The following messages apply to wiring this product.
Setup and Adjustments
Make temperature or fan speed adjustments to the
appropriate modules using the rotating dial, shown in
Figure 3 and Figure 4.
Repair Information
Do not field repair the TM-11x1 Series Room
Temperature Module. As with any electrical device,
keep the air vents clean and free from dust and
obstruction. To order replacement parts, contact the
nearest Johnson Controls representative.
Technical Specifications
!
CAUTION: Risk of Electric Shock.
Disconnect power supply before making
electrical connections to avoid electric
shock.
Mise En Garde: Risque de décharge
électrique.
Débrancher l'alimentation
avant de réaliser tout raccordement
électrique afin d'éviter tout risque de
décharge électrique.
!
CAUTION: Risk of Property Damage.
Do not run low voltage cable in the same
conduit or wiring troughs with high
voltage wires. Running low and high
voltage wires in the same conduit or
wiring troughs may damage the
equipment or cause system malfunction.
MISE EN GARDE : Risque de dégâts
matériels.
Ne pas faire courir un câble basse
tension dans les mêmes gaines ou
goulottes électriques que des câbles
haute tension. L'installation de fils basse
tension et haute tension dans les mêmes
gaines ou goulottes électriques risque
d'endommager l'équipement ou de
provoquer des dysfonctionnements du
système.
!
CAUTION: Risk of Property Damage.
Do not apply power to the system before
checking all wiring connections. Short
circuited or improperly connected wires
may result in permanent damage to the
equipment.
Mise En Garde: Risque de dégâts
matériels.
Ne pas mettre le système
sous tension avant d'avoir vérifié tous les
raccords de câblage. Des fils formant un
court-circuit ou connectés de façon
incorrecte risquent d'endommager
irrémédiablement l'équipement.
IMPORTANT:
Use copper conductors only. Make
all wiring connections in accordance with local,
national, and regional regulations. Do not exceed
the Command Module electrical ratings.
TM-11x1 Series
Room Temperature Module (Part 1 of 2
)
Models
TM-1141-0000
Temperature Output Only
TM-1151-0000
Temperature Output with Occupancy Override
TM-1161-000x
Temperature Output with Setpoint Adjustment and Occupancy
Override and Optional Fan Speed Adjustment
TM-1191-000x
Temperature Output with Setpoint Adjustment
Power Requirements
Powered from TC-9102 Controller.
Power Consumption
N/A: Refer to individual component specification.
Inputs
None
Adjustments
Temperature Setpoint, Fan Speed (Optional by Model)
Mode Indicator
Green LED (5 V, 4 mA)
Occupancy Button
Momentary Contact (Switches 5 V at 1 mA)
Output
Temperature Sensing
Element
Resistance Temperature Device (RTD) Thermistor Negative
Temperature Coefficient (NTC) 2,252 ohm at 77°F (25°C)
Fan Speed
10k ohm Potentiometer, with Mechanically-Guided Positions
at 0, 25, 50, 75, and 100% for Auto, Off, I (Low Speed),