Table5: PC address settings

Address type

Default address

Subnet Mask

255.255.255.0

Default Gateway

192.168.92.1

Configuring the router

To configure the router:

1.  In your web browser address field, enter the router IP address: 

192.168.92.68

.

2.  Use the following table as a reference when you configure the router parameters.

Table6: Router parameters

Name

Description

Device Instance

Enter a unique 22-bit decimal value (0–4,194,303). Each network device

must have a unique device instance.

Default Value = 0

Ethernet Network

Enter a unique 16-bit decimal value (0–65,535). Each BACnet network,

regardless of technology, must have a unique network number.

By retaining a value of 0, BACnet Ethernet routing is disabled.

Default Value = 0

Note: 

The Ethernet Network field represents the BACnet over

Ethernet network number. BACnet over Ethernet is a different

networking technology than BACnet/IP. Ethernet Network and

BACnet/IP Network must each have a unique BACnet network

number.

BACnet/IP UDP Port

Enter a 16-bit hexadecimal value. All BACnet/IP devices on the same

BACnet network must have the same BACnet/IP UDP port assignment.

Normally, you do not need to change this value. If you do, avoid well-

known ports that have hexadecimal addresses, such as 15, 17, or 50.

Instead, choose port numbers in the range of BAC1 through BACF.

Default Value = BAC0 (hexadecimal)

Note: 

MS-CCT and FX-CommPro BACnet identify the BACnet/IP UDP

port number in decimal format, while the BACnet router identifies

the UDP port number in hexadecimal format. The decimal number

47808 is equivalent to the hexadecimal number BAC0.

BACnet/IP Network

Enter a unique 16-bit decimal value (0–65,535). Each BACnet network,

regardless of technology, must have a unique network number.

Default Value = 1

IP Address

Enter the IP address of the router in dotted decimal format. Select a valid

address in the range from 0.0.0.1 to 255.255.255.254.

Default Value = 192.168.92.68

IP Subnet

Enter a decimal value (0–30) for the IP subnet mask. This value is the

number of bits with a 1 in the mask.

Default Value = 24

IP Gateway

Enter the default gateway for the IP stack. This value is a dotted decimal

number that ranges from 0.0.0.1 to 255.255.255.254.

Default Value = 192.168.92.1

Portable BACnet/IP to MS/TP Router Installation Instructions

6

Summary of Contents for TL-BRTRP-0

Page 1: ...ics exist in a small portable case and are powered from the computer USB port however no USB drivers are needed The router contains a 10 100 Mbps Ethernet Auto Medium Dependent Interface Crossover MDIX port and an MS TP compatible port The MS TP port offers a choice of EIA 485 connectors an RJ 11 connector or a 3 pin terminal block with removable plug and is optically isolated from USB power The M...

Page 2: ...e unused RJ 45 Medium Dependent Interface MDI Ethernet Pin 1 TD 2 TD 3 RD 6 RD All other pins are unused USB port The BACnet router has a USB 2 0 Type B receptacle which is only used to obtain power from a computer No communications are supported via the USB port Note Since no USB driver is required disregard the unknown hardware window that appears when you connect the BACnet router to a computer...

Page 3: ...Cnet router to the FC RJ12 connector of a Metasys and FX controller A standard modular jack 6 pin cable does not function correctly The following figure and table provide the pinout required for the custom cable Figure 2 BACnet router to Field Controller cable pinout Table2 Custom RJ 11 Cable Connections BACnet Router Plug Field Controller Plug Terminal 2 Terminal 2 Terminal 4 COM Terminal 5 COM T...

Page 4: ... when sufficient power is provided from the USB host ETH An Ethernet LED glows green for 100 Mbps and yellow for 10 Mbps also indicates activities by flashing MS TP A green LED flashes when the router receives MS TP traffic Webpage consideration The BACnet IP to MS TP Router contains a web server that can be accessed from any Internet compatible computer on the local network Microsoft Internet Exp...

Page 5: ...ll the Internet Protocol TCP IP protocol 5 Click Use the following IP address and enter the values defined in Table 5 6 Click OK Windows Vista and later 1 Open the control panel 2 Click on Network and Sharing Center 3 In the View your active networks section click the Local Area Connection or Ethernet link or click the Internet connection name next to Connections 4 On the Local Area Connection or ...

Page 6: ...vices on the same BACnet network must have the same BACnet IP UDP port assignment Normally you do not need to change this value If you do avoid well known ports that have hexadecimal addresses such as 15 17 or 50 Instead choose port numbers in the range of BAC1 through BACF Default Value BAC0 hexadecimal Note MS CCT and FX CommPro BACnet identify the BACnet IP UDP port number in decimal format whi...

Page 7: ...exceed the highest MAC address for any master on the network Optimum performance occurs when this value equals the highest MAC address all masters use sequential MAC addresses Default Value 127 Max Info Frames Enter the maximum number of messages that can route onto the MS TP network by the router per token pass The range is 1 to 100 and the typical values are above 20 Smaller values provide less ...

Page 8: ...idity 10 to 95 noncondensing Signaling USB 1 1 2 0 compatible Ethernet 10BASE T 100BASE TX MS TP EIA 485 American National Standards Institute American Society of Heating Refrigerating and Air Conditioning Engineers ANSI ASHRAE 135 2004 Cable Length Limit USB 5 m Ethernet 100 m MS TP 1 200 m for 18 AWG MS TP bps 9600 19 200 38 400 76 800 MS TP Node Limit 127 devices 32 devices per segment LEDs MS ...

Page 9: ...55022 Class A CE Mark ROHS Patents Patents http jcipat com Product warranty This product is covered by a limited warranty details of which can be found at www johnsoncontrols com buildingswarranty Points of single contact APAC Europe NA SA JOHNSON CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 32 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN ...