TEC3000 Series Wireless Proportional Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
38
Equipment Setup
(Cont)
Supply Temp Sensor*
Nickel
Nickel, Platinum, A99B, 2.25k ohm NTC,
10k ohm NTC, 10k ohm NTC Type 3
* Supply temp type = analog sensor
Supply Temp Offset*
0°F
-5 to 5°F (-3 to 3°C)
* Supply temp type = analog sensor
Trend
EFF-ZNT
—
-50 to 250°F (-45.56 to 121.11°C)
EFF-SETPOINT
—
45 to 100°F (7.22 to 37.78°C)
EFF-ZNH
—
0 to 100%RH
B1 Status
—
On or Off
B2 Status
—
On or Off
EFF-OAT
—
-50 to 250°F (-45.56 to 121.11°C)
EFF-SAT
—
-50 to 250°F (-45.56 to 121.11°C)
FANSPD-S
—
On or Off
HTG-O
—
0 to 100%
CLG-O
—
0 to 100%
System Status
Occupancy Source
Local Schedule
Occupancy BI
Temp Occ BI
Temp Occ
Occ Override
Local Schedule
BAS Schedule
Occupancy Sensor
Unit Status
Cooling
System Fault
Airflow Fault
Open Window
Control Off
Unreliable Temperature
Dehumidification
Idle
Cooling
Heating
Cooling Unavailable
Heating Unavailable
Cooling Unavailable due to Changeover
Cooling Unavailable due to OA Temp
Cooling Unavailable due to Control Mode
Heating Unavailable due to Changeover
Heating Unavailable due to OA Temp
Heating Unavailable due to Control Mode
Supply Air Temperature
75°F
-50 to 250°F (-45 to 121°C)
Table 10: Menus and Submenus (Part 6 of 8)
Level 1
Level 2
(LCD Screen Name)
Level 3
(Default Values)
Available Values
1