TEC2664Z-3 BACnet® MS/TP Rooftop Controller for Stand-Alone and Networked Zoning Systems
Installation Instructions
10
Units
Sets the display scale of the rooftop
controller.
Default:
Imp
(Si):
Celsius/Pa
(Imp):
Fahrenheit/in. W.C.
Fan del
Fan delay extends fan operation
after a heating or cooling cycle has
ended.
Default:
off
(on):
Extends fan operation by 60 seconds after a heating or cooling
cycle has ended.
(off):
No extension of fan operation after a heating or cooling cycle
has ended.
Note:
The fan delay is only active when the GUI System Mode is
set at Auto and the GUI Occupancy is set at Unoccupied.
DI1
Configuration of Digital Input 1.
Default:
None
(None):
No function is associated with an input.
(RemNSB):
Remote Night Setback (NSB) via a time clock input
disables the internal scheduling of the thermostat. The scheduling is
now set per the digital input. The time information still displays, but
the menu information related to the schedule is disabled and no
longer accessible. Contact open = Occupied; contact closed =
Unoccupied
(RemOVR):
Temporary occupancy request via a remote input. This
override function is controlled by a manual remote occupancy
override. When enabled, this condition disables the override
capacity of the rooftop controller.
(Filter):
A Filter alarm is displayed. This alarm can be connected to
a differential pressure switch that monitors a filter.
(Service):
A Service alarm is displayed on the rooftop controller
when the input is energized. This input can be tied into the air
conditioning unit control card, which provides an alarm should there
be a malfunction.
TOccTime
Sets the duration of the Temporary
Occupancy Time when the heating
or cooling setpoints in the Occupied
mode are established by:
•
an Override Function enabled in
the Main User Menu (when the
rooftop controller is in the
Unoccupied mode)
•
a temporary heating or cooling
setpoint
Default:
3.0 hrs
Range:
0.0
to
12.0 hrs
Note:
When adjusting the TOccTime, press the
UP/DOWN
arrow
keys to change the time in 1-hour increments; press and hold the
UP/DOWN
arrow keys to change the time in 10-hour increments.
Cal RS
Sets the desired Room Air
Temperature Sensor Calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default:
0.0F°/0.0C°
Range:
-5.0F°/-2.5C°
to
5.0F°/2.5C°
adjustable in 1.0F°/0.5C°
increments
Cal OS
Sets the desired Outside Air
Temperature Sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed outside air temperature.
Default:
0.0F°/0.0C°
Range:
-5.0F°/-2.5C°
to
5.0F°/2.5C°
adjustable in 1.0F°/0.5C°
increments
H stage
Sets the number of Heating stages.
Default:
2
(1):
One stage of heating
(2):
Two stages of heating
Note:
Two-stage rooftop controller operation reverts to one-stage
operation only when the second heating step is not required.
Table 2: Installer Configuration Menu (Part 3 of 5)
Parameter
Appearing
on Display
Description and Default
Selection Options