background image

TEC2102-3 N2 Networked Heat Pump Thermostat Installation Instructions 

13

Operation

Programming/Operating the TEC2102-3 
Thermostat

Once the thermostat is configured via the Installer 
Configuration Menu, its operating parameters can be 
programmed via the Main User Menu. Access this 
menu by pressing the 

MENU

 key during normal 

thermostat operation. The Main User Menu contains 
the basic operating features of the thermostat.

The Main User Menu also uses Auto Help, which is 
displayed automatically in the menu when there is a 
pause in programming activity. To exit Auto Help, 
continue with the programming selection. When the 
thermostat is in the Main User Menu and is left 
unattended for 45 seconds, the menu reverts to the 
Status Display Menu.

Enabling Override Schedule

Note:

Enabling Override Schedule only appears when 

in the Unoccupied Mode.

The override schedule prompt only appears when the 
thermostat is in the unoccupied state. This menu 
selection gives the user the option of overriding the 
unoccupied setpoints with the occupied setpoints for 
the amount of time specified under the 

TOccTime

 

parameter. See the 

Configuring the TEC2102-3 

Thermostat

 section.

Note:

If one of the digital inputs is configured to 

operate as a remote override contact, this menu is 
disabled.

To override the unoccupied state while in the Main User 
Menu:

1.

Press the 

NO

 key to all prompts until the Override 

Schedule prompt appears. If the thermostat is in 
the unoccupied state, this is the first prompt.

2.

Press the 

YES

 key to enable the temporary 

override. The thermostat returns to the Status 
Display Menu.

When scrolling through the Status Display Menu, 
Override now appears for the occupancy status 
parameter.

Resuming the Programmed Schedule

This menu only appears when the thermostat is in the 
unoccupied override mode.

To resume the schedule while in the Main User Menu:

1.

Press the 

NO

 key to all prompts until the Cancel 

ovrd Y/N prompt appears. If the thermostat is in the 
unoccupied override state, this is the first prompt.

2.

Press the 

YES

 key to resume the programmed 

schedule.

The thermostat returns to the Status Display Menu.

Entering Permanent Temperature Setpoints

The first prompt appearing in the Main User Menu of 
the thermostat when in the occupied state is to set the 
permanent temperature setpoint.

Comp/aux

Sets the mode of interaction 
between the heat pump and the 
auxiliary heat.
Default:

 off

(on)

 – in the heating mode only: If the heat pump is not able to 

satisfy the heating setpoint, the auxiliary heat is energized and the 
heat pump is shut off. This typically applies when the air handler 
heat pump coil is installed after the auxiliary heat. There is a 
2-minute delay to restart the heat pump after the auxiliary heat is 
shut down.

(off) 

– in the heating mode only: If the heat pump is not able to 

satisfy the heating setpoint, the auxiliary heat is energized at the 
same time as the heat pump stage. This typically applies when the 
air handler heat pump coil is installed before the auxiliary heat (all 
electric systems).

1.

When adjusting the numeric value, press the 

UP

 or 

DOWN

 arrow key to change the value by single increments; press and 

hold the 

UP

 or 

DOWN

 arrow key to change the numeric value in increments of ten.

2.

When adjusting the temperature, press the 

UP

 or 

DOWN

 arrow key to change the value in 0.5F°/0.5C° increments; press 

and hold the 

UP

 or 

DOWN

 arrow key to change the value in 5.0F°/5.0C° increments.

3.

When the outdoor air sensor is not connected or it has a short, the thermostat bypasses heating lockout, cooling lockout, 
high balance point, and low balance point. Emergency mode bypasses heating lockout and permits auxiliary heating 
whenever a heating demand occurs.

Table 2:  Installer Configuration Menu  (Part 5 of 5)

Parameter 
Appearing 
on Display

Description and Default

Selection Options

Summary of Contents for TEC2102-3

Page 1: ... damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of or protect against failure or malfunction of the thermostat This equipment has been tested and found to comply with the limits for a Class A digital device pu...

Page 2: ...rmostat mounting base so that the arrow on the base points upward to indicate the top of the thermostat 6 Drill a 3 16 in 5 mm hole at each of the two marked locations and tap nylon anchors included with the thermostat flush to the wall surface 7 Position the thermostat mounting base on the wall and use the two mounting screws included with the thermostat to secure the base to the surface as illus...

Page 3: ...material to prevent drafts from affecting the ambient temperature readings 3 Reinsert the screw terminal blocks onto the PCB 4 Reattach the thermostat cover to the mounting base top side first 5 Use a Phillips head screwdriver to reinstall the security screw on the bottom of the thermostat cover CAUTION Risk of Electric Shock Disconnect the power supply before making electrical connections to avoi...

Page 4: ...ut 1 Configurable Digital Input 2 Remote Room Temperature Sensor Sensor Common Outdoor Air Sensor N2 Bus Mixed Air or Discharge Air Sensor Function Y1 Y2 G RC C RH W1 O B Aux DI1 DI2 RS Scom OS REF MS Terminal DI1 DI2 If using the same power source for the thermostat and heating loads install a jumper across RC and RH Scom OS Outdoor Air Sensor 24 VAC Thermostat Power Y2 Y1 RC C Aux Heat RH W1 Aux...

Page 5: ...cent N2 command received by any of the Object Types listed in Table 1 controls the thermostat Overrides take priority over any local adjustment or command in the thermostat If a setpoint is overridden the thermostat adjusts the other setpoint if necessary to maintain the minimum deadband between the two setpoints The setpoints can be spread farther apart but can never be adjusted closer than 2F 1C...

Page 6: ...del Point Type Override Range Room Temp1 ADI 1 N2 AI CSAD 32 to 122 F 0 to 50 C Aux Temp Outdoor Temp1 ADI 2 N2 AI CSAD 40 to 122 F 40 to 50 C Heating SP1 2 Occupied Heating SP ADI 3 N2 AO CSAD 40 to 90 F 4 5 to 32 C Cooling SP1 2 Occupied Cooling SP ADI 4 N2 AO CSAD 54 to 100 F 12 to 37 5 C Setback Heating SP1 2 Unoccupied Heating SP ADI 5 N2 AO CSAD 40 to 90 F 4 5 to 32 C Setback Cooling SP1 2 U...

Page 7: ...10 read only If a setpoint is overridden the TEC if necessary adjusts the other setpoint to maintain the minimum deadband between the setpoints The setpoints can be spread further apart but can never be adjusted closer than the current minimum deadband value Failure to stay within the limits for a command results in an N2 Negative Acknowledge NAK error from the TEC2102 3 thermostat Overrides take ...

Page 8: ...menu item stop the Status Display Menu from scrolling and to manually scroll to the next parameter on the menu Note When the thermostat is left unattended for 45 seconds the thermostat display resumes scrolling Use the NO key to decline a parameter change and to advance to the next menu item Use the MENU key to access the Main User Menu or to exit the menu See the Programming Overview section acce...

Page 9: ... the YES key to choose the desired selection option 4 Press the YES key and then the NO key to continue scrolling through the parameters To exit the Installer Configuration Menu at any time press the MENU key and press the YES key at the exit prompt To pass over a parameter without changing it press the NO key When the thermostat is in the Installer Configuration Menu and left unattended for appro...

Page 10: ...ess Temporary Temperature Setpoints Access Access No Access System Mode Setting Access No Access No Access Fan Mode Setting Access No Access No Access Pwr del1 Sets the delay time period at thermostat powerup or at each time power is removed and reapplied before any operation fan heating or cooling is authorized Also can be used to sequence the startup of multiple units in one location Default 10 ...

Page 11: ...fan operation after a heating or cooling cycle has ended The fan delay is only active when the fan is in the Auto mode Com addr N2 network address at the thermostat coincides with the address assigned at the supervisory controller Default 4 Range 1 to 255 TOccTime Sets the duration of the Temporary Occupancy Time when the thermostat is in the Unoccupied mode when a Schedule Override Function is en...

Page 12: ...pump operation may still be used above the high balance point Lo b p 3 Sets the low balance point the outdoor air temperature at which the heat pump operation terminates when the heat pump is in the heating mode Default 12 0 F 24 0 C Range 40 0 F 40 C to 30 0 F 1 0 C Below the low balance point only the auxiliary heat is used to maintain the heating setpoint Heat pump operation may still be used b...

Page 13: ... mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts until the Cancel ovrd Y N prompt appears If the thermostat is in the unoccupied override state this is the first prompt 2 Press the YES key to resume the programmed schedule The thermostat returns to the Status Display Menu Entering Permanent Temperature Setpoints The first prompt appearing in the Main User ...

Page 14: ... to all prompts until the temperature setpoint prompt appears on the display it may be the first prompt Press the YES key to enter the temperature setting menu Press the YES key to change the occupied cooling setpoint Press the NO key to advance to the occupied heating setpoint menu Press the UP DOWN arrow keys to set the temperature Press the YES key to store the value and advance to the next men...

Page 15: ...he fan all the time for occupied states and only on a call for heating or cooling in unoccupied states This is the default setting To select the fan mode while in the Main User Menu 1 Press the NO key to all prompts until the fan mode prompt appears on the display Press the YES key to set the fan mode 2 Press the UP DOWN arrow keys to locate the desired fan mode Press the YES key to select the des...

Page 16: ...o not exceed the maximum number of devices allowed on the N2 Bus per supervisory controller limitations The thermostat does not have power Apply power to the thermostat The N2 cable runs are broken Locate the break and correct the wiring The thermostat device type is incorrect Change the thermostat device type to VND N2 Bus is Offline The wiring on the N2 Bus is broken Repair the wiring No point m...

Page 17: ...0 C in 0 5 Increments Heating Control 40 0 F 4 5 C to 90 0 F 32 0 C Cooling Control 54 0 F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F 21 0 C Typical Calibrated Default Minimum Deadband 2F 1C between Heating and Cooling Ambient Conditions Operating 32 to 122 F 0 to 50 C 95 RH Maximum Noncondensing Storage 22 to 122 F 30 to 50 C 95 RH Maximum Noncondensing Compliance United St...

Reviews: