Configuring the Wireless Mesh Network Settings
Use the following process to configure the wireless
mesh network.
1.
Select a
PAN ID
and
Channel
. Use these same
values for every TEC Wireless Thermostat
Controller (and the associated TEC20 Coordinator)
on the same wireless mesh network. See Table 6.
2.
Select a
Com Address
for each TEC Wireless
Thermostat Controller (1 to 254). This address
must be unique to each TEC Wireless Thermostat
Controller on the same wireless network (that is,
unique to the
PAN ID
/
Channel
combination). See
Table 6.
After configuring the wireless mesh network settings,
refer to the
TEC Series Wireless Thermostat Controller
System Technical Bulletin (LIT-12011414)
for directions
on integrating the TEC Wireless Thermostat
Controllers and TEC20 Coordinator with a supervisory
controller.
Dehumidification (TEC2036[H]-2 and TEC2056[H]-2
Models Only)
Upon detection of room humidity above the adjustable
humidity setpoint as sensed by the integral humidity
sensor, dehumidification activates.
Note:
Dehumidification operation functions only in the
Cooling mode; dehumidification operation does not
function in either the Off or the Heating mode.
Note:
A central network command can globally
lock out dehumidification operation to all thermostat
controllers.
If the room temperature resides in the deadband
between the Heating and Cooling setpoint:
•
the thermostat controller forces the fan to low
speed
•
the chilled water valve opens to the specified
maximum value set by
CoolMax
•
the thermostat controller stages Heating to
maintain the room temperature at the Cooling
setpoint, as sensed by the thermostat controller
If the room temperature falls below the current Heating
setpoint, the thermostat controller disables
dehumidification operation.
If the thermostat controller is in Cooling demand:
•
the chilled water valve opens to 100%
•
the thermostat controller stages Heating to
maintain the room temperature at the Cooling
setpoint, as sensed by the thermostat controller
If the thermostat controller is in Cooling demand and
the room temperature rises 2F°/1C° above the Cooling
setpoint, the thermostat controller automatically
disables dehumidification operation. Likewise, if the
thermostat controller is in Cooling demand and the
room temperature falls below the current Heating
setpoint, the thermostat controller disables
dehumidification operation.
Table 6: Installer Configuration Menu
(Part 1 of 7)
Parameter
Appearing
on Display
Description and Default
Selection Options
Com addr
Wireless address at the thermostat
controller; Default:
4
Range:
000
to
254
Addresses of each item on the wireless bus must be uniquely
numbered, increasing from 1.
Note:
Setting this parameter to 0 disables the function.
PAN ID
Sets the Personal Area Network
Identification (PAN ID) of the
wireless network. All devices on a
network must have the same
PAN ID setting to communicate with
each other. Default:
0
Range:
0
to
500
Note:
Setting this parameter to 0 disables the function.
Channel
Sets the mesh network channel the
device uses for communication.
Only devices using the same mesh
network channel can communicate
with each other. Default:
10
Range:
11
to
26
Note:
Setting this parameter to 10 disables the function.
GET FROM
Parameter not available at this time.
N/A