Johnson Controls TE-6800 Series Installation Manual Download Page 5

Troubleshooting

About this task:

TE-6800 Series Temperature Sensors are recommended

for use only with Johnson Controls

®

 digital controllers. If

the TE-6800 is not functioning properly, use the following

procedure to identify the problem and determine a

solution:

1. Check that the TE-6800 is mounted in a location

indicative of the space temperature (for example,

away from drafts or sunlight).

2. Check the wiring:

- Verify that the wiring is correct. The modular

jack connector must be inserted with the

proper polarity (not reversed). Misalignment

can cause damage.

- Check all supply voltage connections. See

Figure 2Figure 3, or Figure 4, if necessary.

3. Check the settings:

- Verify that any scaling modifications, setpoint

adjustments, and overrides have been saved

and downloaded to the controller.

- Check the override status (Temporary

Occupancy mode vs. Unoccupied mode) at the

controller.

- Check the setpoint settings.

4. Confirm DIP switch positions if:

- the LED remains on or is dim

- the room sensor reading is outside of the

normal range for the space being sensed

Note: 

Make sure the DIP switch setting is

correct for the controller used with the TE-6800.

5. Replace the TE-6800 if the troubleshooting

suggestions fail to remedy the problem.

Repair Information

Do not field repair the TE-6800 temperature sensors. As

with any electrical device, keep the air vents clean and

free from dust or obstruction. If the TE-6800 temperature

sensor fails to operate within its specifications, replace

the unit. For a replacement sensor, contact the nearest

Johnson Controls representative.

Technical Specifications

Table 5: TE-6800 Series Temperature Sensors technical specifications

Specification

Description

Temperature Sensor

1000 ohm thin-film nickel

Temperature Coefficient

Approximately 3 ohms per F° (5.4 ohms per C°)

Reference Resistance

1000 ohms at 70°F (21°C)

Nickel Sensor

Accuracy

±0.34F° at 70°F (±0.18C° at 21°C)

Temperature Sensor

1000 ohm thin-film platinum

Temperature Coefficient

Approximately 2 ohms per F° (3.9 ohms per C°)

Reference Resistance

1000 ohms at 32°F (0°C)

Platinum Sensor

Accuracy

±0.35F° at 70°F (±0.19C° at 21°C)

Range

Warmer/cooler

Setpoint

Resistance

1500 Ohms

Sensor Response

Time

10 minutes at 10 feet per minute

Modular Jack

8-position modular jack connector

Field

Connections

Terminal Block

Screw type terminals for 18 to 24 AWG wire

Zone Bus Access

6-pin connector with front bottom access for a laptop with HVAC PRO software and CVTPRO

converter

Manual Override

Integral momentary push button (DIP switch selectable)

LED Light

Green LED light indicates two modes of operation (VMA1200 and VMA1400 Series controllers only)

Ambient

Operating

Conditions

32 to 131°F (0 to 55°C) 10 to 95% RH, noncondensing; 86°F (30°C) maximum dew point

Ambient Storage

Conditions

-40 to 140°F (-40 to 60°C) 5 to 95% RH, noncondensing; 86°F (30°C) maximum dew point

Materials

White thermoplastic

TE-6800 Series Temperature Sensors Installation Guide

5

Summary of Contents for TE-6800 Series

Page 1: ...pervision ou d alarme ou des dispositifs de sécurité ou de limitation ayant une fonction d avertissement ou de protection en cas de défaillance ou de dysfonctionnement du sensor Installation Special Tools Needed A 1 16 in 1 5 mm hex wrench or a Johnson Controls T 4000 119 hex head adjustment tool is required during installation Accessories To install the TE 6800 Series Temperature Sensor on a wall...

Page 2: ...ons in accordance with local national and regional regulations Figure 1 Modular Jack Pin Number Assignments Keep wires as short as possible to minimize sensor error Each 250 ft 76 m run of 18 AWG wire or 50 ft 15 m of 24 AWG wire creates 1F 0 56C error for a nickel sensor or 1 5F 0 83C error for a platinum sensor due to wire resistance To maintain less than 1F 0 56C error for nickel or 1 5F 0 83C ...

Page 3: ...ity not reversed Misalignment can cause damage Refer to the controller documentation to determine the appropriate cable assembly Important Do not insert a 6 pin connector or anything other than an RJ 45 8 pin connector into the 8 pin jack on the back of the TE 6800 Temperature Sensor to prevent damaging the modular jack Table 2 Modular Jack Pin Designations Modular Jack Pin Number Signal Designati...

Page 4: ...ctory set up down and up The controller determines the LED mode LED Mode NO PB LED and PB Disabled but Sensor Enabled Switch positions are all down LED is off and the PB does not function Figure 5 DIP Switch Positions Table 4 Controller Compatibility with LED Mode and PB Features Recognized by Controller Types of TE 6800 LED Mode Figure 5 Features Enabled on TE 6800 AHU UNT1100 VAV1xx or UNT1xx 1 ...

Page 5: ... free from dust or obstruction If the TE 6800 temperature sensor fails to operate within its specifications replace the unit For a replacement sensor contact the nearest Johnson Controls representative Technical Specifications Table 5 TE 6800 Series Temperature Sensors technical specifications Specification Description Temperature Sensor 1000 ohm thin film nickel Temperature Coefficient Approximat...

Page 6: ...om misapplication or misuse of its products Product warranty This product is covered by a limited warranty details of which can be found at www johnsoncontrols com buildingswarranty Software terms Use of the software that is in or constitutes this product or access to the cloud or hosted services applicable to this product if any is subject to applicable end user license open source software infor...

Reviews: